Tab.25 PC = Process Counter = Process counter
Parameter
Description
Unit
EHC–05
SCB-10
PC000
Number of compressor operating hours in Heat
ing mode
hours
X
PC005
Number of compressor operating hours in Cool
ing mode
hours
X
CODE
Enter the installer code to access the following
parameters.
X
AC002
Number of hours that the appliance has been
producing energy since last service
hours
X
AC003
Number of hours since the previous servicing of
the appliance
hours
X
AC004
Number of heat generator starts since the
previous servicing.
X
SERVICE
Resetting the maintenance service
CLR: the AC002, AC003, and AC004 counters
are reset to zero.
X
6.3.2
COUNTERS, TIME PROG, CLOCK \ DHW, CIRCA0 ,
CIRCA1, CIRCB1, DHW1, CIRCC1, CIRCAUX1 menus
Tab.26
Menu
Description
DHW
Timer programming for the main domestic hot water circuit
06:00 - 23:00 ON
23:00 - 06:00 OFF
CIRCA0
Timer programming for the main direct heating
06:00 - 23:00 ON
23:00 - 06:00 OFF
CIRCA1
Timer programming for the additional heating circuit
06:00 - 22:00 ON
22:00 - 06:00 OFF
CIRCB1
TP.H: Timer programming for the additional heating circuit
06:00 - 22:00 ON
22:00 - 06:00 OFF
TP.C: Timer programming for cooling
14:00 - 23:00 ON
23:00 - 14:00 OFF
DHW1
Timer programming for the secondary domestic hot water circuit
06:00 - 22:00 ON
22:00 - 06:00 OFF
CIRC1
Timer programming for the heating of an additional circuit if the optional AD249 is
connected
06:00 - 22:00 ON
22:00 - 06:00 OFF
CIRCAUX1
Timer programming for the heating of an auxiliary circuit if the optional AD249 is
connected
06:00 - 22:00 ON
22:00 - 06:00 OFF
6.3.3
COUNTERS, TIME PROG, CLOCK \CLK menus
Tab.27
CLK parameter
Unit
HMI
HOURS
Can be set from 0 to 23
available
MINUTE
Can be set from 0 to 59
available
6 Settings
24
iHPI
7701562 - v02 - 22052018