Product name
iHPI
AWHP 22 TR–2
iHPI
AWHP 27 TR-2
Annual energy consumption under warmer conditions
Q
HE
kWh 10025
11541
Rated air flow rate, outdoors for air-to-water heat pumps
—
m
3
/h 6000
6000
(1) The rated heat output
Prated is equal to the design load for heating Pdesignh, and the rated heat output of a supplementary heater
Psup is equal to the supplementary capacity for heating sup(Tj).
(2) If
Cdh is not determined by measurement, the default degradation coefficient is Cdh = 0.9.
See
The back cover for contact details.
3.2.4
Circulating pump
Important
The benchmark for the most efficient circulating pumps is EEI ≤
0.20.
3.2.5
Sensor specifications
Tab.9
Outside sensor
Temperature in
°C
-20
-16
-12
-8
-4
0
4
8
12
16
20
24
Resistance in Ω
2392
2088
1811
1562
1342
1149
984
842
720
616
528
454
Tab.10 Domestic hot water sensor/Flow sensor
Temperature in
°C
0
10
20
25
30
40
50
60
70
80
90
Resistance in Ω
32014
19691
12474
10000
8080
5372
3661
2535
1794
1290
941
3 Technical specifications
12
iHPI
7701562 - v02 - 22052018