AM012 =Status Appliance
AM014 =Appliance sub status
16 = Frost protection
30= normal operation
The compressor or the back-ups are running.
31= internal set point limited
If the heating set point on the heat pump differs from the system set point.
60= pump post-operation
Heat pump and back-up shut-down, system pump post-operation.
65= compressor bypass and back-ups running
66= the temperature exceeds the compressor's maximum operating temperature
The compressor has stopped. The back-ups are operating.
67= the outside temperature is lower than the compressor's maximum operating tempera
ture
The compressor has stopped. The back-ups are operating.
68= the hybrid function requests compressor shut-down
The compressor has stopped. The back-ups are operating.
69= defrosting running
The compressor is running.
70= defrosting conditions not met
The compressor has stopped. The back-ups are operating.
71= defrosting running.
The compressor and the back-ups are running.
17 =DeAiration
30= normal operation
The compressor or the back-ups are running.
31= internal set point limited
If the heating set point on the heat pump differs from the system set point.
60= pump post-operation
Heat pump and back-up shut-down.
65= compressor bypass and back-ups running
66= the temperature exceeds the compressor's maximum operating temperature
The compressor has stopped. The back-ups are operating.
67= the outside temperature is lower than the compressor's maximum operating tempera
ture
The compressor has stopped. The back-ups are operating.
68= the hybrid function requests compressor shut-down
The compressor has stopped. The back-ups are operating.
69= defrosting running
The compressor is running.
70= defrosting conditions not met
The compressor has stopped. The back-ups are operating.
71= defrosting running.
The compressor and the back-ups are running.
20 = Self-filling
46 = Self-filling the installation
47 = Operating pressure top-up
6 Settings
34
iHPI