Operation
Manual Single Power Unit BUM64S/A/F
Document no.: 5.01056.03
67
8
"ready-for-use controller" are present, the message "ready-for-use group" will be gener-
ated (see
figure 24: „ready-for-use“
In the following sections we will give information about the different "ready-for-use" mes-
sages.
"ready-for-use
feed module"
When the "infeed module monitoring functions" do not detect any errors, the monitoring
function generates the "ready-for-use feed module" message.
m
if "
ready-for-use feed module
" is erased by the monitoring function, the BUM 64S/A/
F switches the drive to a torque-free state, the power module will produce no more
power.
The BUM 64S/A/F displays this message by use of a LED. At the same time the message
is transmitted to the relay contacts. Information about this you will find under
The term "ready-for-use feed module" is also called "ready-for-use internal" (terminal des-
ignation BB int) respectively "ready-for-use external" (terminal designation BB ext).
The distinction has its reason only in the construction of the unit.
At the infeed module output the "ready-for-use feed module" is also called "ready-for-use
internal". After the message has been transmitted inside the unit to the power module,
the "ready-for-use feed module" message is also referred to as "ready-for-use external".
NOTE
After ap24V-supply and mains input voltage it will take approximately 5 s for the ap-
pliance to be ready-for-service.
"ready-for-use power module" after approx. 0.5 s, „ready-for-use feed module" after approx.
2 s, "ready-for-use controller" after approx. 4.5 s