Required environmental conditions
Manual Single Power Unit BUM64S/A/F
Document no.: 5.01056.03
Baumüller Nürnberg Electronic GmbH & Co. KG
100
D.2
4)
characteristic curve: power output of appliance in dependence of mounting height at normal pressure
5)
EN 50178, chapter 9.4.3.2
6)
EN 50178, table 2
7)
As coolant use clear, suspended matter- and dirt-free, desalinated and demineralized water. The water may hold a maximum of 100
ppm (0.01%) natrium chloride (salinity). Mix in an anticorrosive. The total water hardness must be between 8° and 14° dH (1° dH = 0.179
mmol Ca
2+
/l). A pH-value between 6.5 and 7.5 must be kept. Use a closed loop coolant circulation!
8)
Air inside and outside switching cabinet.
9)
Air inside switching cabinet.