Installation
Basic Supply Unit BUG 622, 623
33
Baumüller Nürnberg GmbH
5.94034.07a
Filtering
No filters are necessary for the function of the converter. To maintain EMC regulations, filters at the input
or output side may be required.
If you have any queries about the filter dimensioning, please ask for the description ”5.95237.xx
Baumüller Filters for Mains Applications BFN”.
Filter assembly
y
Mount the filter next to the converter. If the cables are longer than 30 cm, screen the mains cable
between converter and filter (grounding at both ends).
y
Input and output cables of the filter must be separated physically (distance > 30 cm).
y
Connect the filter housing to ground over a large surface.
Leakage currents
Due to the principle of operation, stray capacitances in the filter, power stage, motor cable and motor
winding cause leakage currents of 100 mA and higher.
This means that converters with current-operated e.l.c.b. can be incompatible!
Observe the safety information in EN 50178/VDE 0160/4.98 Section 5.2.11.2.