Maintenance
48
Basic Supply Unit BUG 622, 623
5.94034.07a
Baumüller Nürnberg GmbH
7.2
Environmental conditions
If you keep to the environmental conditions during the entire period of storage, you can assume, that the
device will not be damaged.
7.3
Recommissioning
Carry out commissioning as with a new device.
WARNING
From six months storage period on, the capacitors are destroyed during commissioning, if they are not
reformed beforehand.
Reform the capacitors by supplying the device ready-for use for at least 48 hours with supply voltage,
but no impulse enable.
WARNING
From six months storage period on, the capacitors are destroyed during commissioning, if they are not
reformed beforehand.
Reform the capacitors by supplying the device ready-for use for at least 48 hours with supply voltage,
but no impulse enable.