Baumer Hübner
Installation
|
5
V1, T1 | HMG10 & HMG10P SSI
Operating Manual
19
f) Attach cover using the Torx/ slotted screws (4x).
g) Mount the torque arm together with threaded rod, washers (3x) and self-locking nuts (3x).
Observe the torque arm mounting instructions (see further links).
h) Attach grounding strap using cheese head screw and washer.
Also see about this
2
Mounting the torque arm at drive [
2
Avoiding and calculating angular errors [
5.5
Hollow shaft mount
DANGER
Injuries caused by shaft rotation
Hair and clothing may get caught in rotating shafts which may lead to serious personal injury.
a) Make sure the device is idle.
b) Before performing any work at the device, make sure power supply is and remains discon-
nected.
DANGER
Explosion
Sparks may cause fire or explosion.
a) Do not use the device in the near vicinity of explosive or highly flammable materials.
NOTICE
Severe concentricity errors of drive shaft will reduce service life and entail angular er-
rors.
Severe runout errors of the drive shaft cause vibrations that cut down on the encoder service
live and may cause angular errors.
a) Keep concentricity errors of drive shaft down to a minimum (recommended ≤ 0.2 mm; ≤ 0.03
mm).
NOTICE
Equipment damage by mechanical overload
Rigid mounting may cause overload by constraining forces.
a) Do not limit the device mobility.
b) Observe the mounting instructions.
c) Adhere to the specified distances and/or angles.