Figure 4-32. Three-Phase Connections, Autotransformer With Loaded Delta Tertiary
The transformer in the example shown in Figure 4-32 has a delta connection on the tertiary winding. The
currents in each winding of the delta are A, B, and C respectively as reflected from the wye or auto
connected winding. The delta connection of the transformer windings causes the current flowing in the
phase leads connected to the delta winding to be A-B, B-C and C-A respectively. The CT currents on the
wye or auto windings must be combined similarly to provide A-B, B-C and C-A to compensate. This is
shown in Figure 4-32 by selecting phase compensation jumper position
Δ
2 for these inputs. This also
provides zero sequence blocking for these inputs since this transformer configuration is a source of zero
sequence currents.