9171400990 Rev G
BE1-59N General Information
1-5
Inductive Ratings
120 Vac, 125 Vdc, 250 Vdc:
Break 0.3 A (L/R = 0.04)
Power Supply
Power supply types and specifications are listed in Table 1-1.
Table 1-1. Power Supply Ratings
Type
Nominal
Input Voltage
Input Voltage Range
Burden at Nominal
K (midrange)
48 Vdc
24 to 150 Vdc
3.4 W
125 Vdc
24 to 150 Vdc
3.6 W
J (midrange)
120 Vac
90 to 132 Vac
22.1 VA
L (low range)
24 Vdc
12 to 32 Vdc
∗
3.5 W
48 Vdc
24 to 150 Vdc
3.4 W
Y (midrange)
125 Vdc
24 to 150 Vdc
3.6 W
250 Vdc
68 to 280 Vdc
3.7 W
Z (high range)
240 Vac
90 to 270 Vac
37.6 VA
∗
Type L power supply initially requires 14 Vdc to begin operating. Once operating, the input voltage may
be reduced to 12 Vdc and operation will continue.
Target Indicators
Electronically latched, manually reset target indicators are optionally available to indicate closure of the
trip output contacts. Either internally operated or current operated targets may be specified. Internally
operated targets should be selected when normally closed (NC) output contacts are specified.
Current Operated Targets
Minimum Rating:
200 mA flowing through the trip circuit
Continuous Rating:
3 A
1 Second Rating:
30 A
2 Minute Rating:
7 A
Type Tests
Shock:
Withstands 15 G in each of three mutually perpendicular planes
without structural damage or performance degradation.
Vibration:
Withstands 2 G in each of three mutually perpendicular planes,
swept over the range of 10 to 500 Hz for a total of six sweeps, 15
minutes each sweep, without structural damage or degradation of
performance.
Dielectric Strength:
Tested in accordance with IEC 255-5 and IEEE C37.90: 2,000 Vac
applied for 1 min
Radio Frequency Interference:
Field tested using a five watt, hand-held transceiver operating at
random frequencies centered around 144 MHz and 440 MHz, with
the antenna located six inches from the relay in both horizontal and
vertical planes.
Surge Withstand Capability:
Qualified to IEEE C37.90.1-1989,
Standard Surge Withstand
Capability (SWC) Tests for Protective Relays and Relay Systems
.
Summary of Contents for BE1-59N
Page 2: ......
Page 6: ...iv BE1 59N Introduction 9171400990 Rev G This page intentionally left blank ...
Page 8: ...vi BE1 59N Introduction 9171400990 Rev G This page intentionally left blank ...
Page 16: ...1 8 BE1 59N General Information 9171400990 Rev G This page intentionally left blank ...
Page 22: ...3 4 BE1 59N Functional Description 9171400990 Rev G This page intentionally left blank ...
Page 24: ...4 2 BE1 59N Installation 9171400990 Rev G Figure 4 1 Panel Cutting Drilling Semi Flush Case ...
Page 32: ...4 10 BE1 59N Installation 9171400990 Rev G Figure 4 9 Sensing Input Connections ...
Page 38: ...5 4 BE1 59N Testing 9171400990 Rev G This page intentionally left blank ...