background image

Base Products Corporation          www.basepump.com          800 554 1426

                                                      page 6 

Models: RB750, HB1000, CB1500     Copyright by Base Products Corporation     2015   Rev.  May/2015 

Clamp to Pipe 

 

 

 

_________________________________________________________________

 

 

Step 6. Connect Water Supply

 

 

See recommended pipe and sizes on page 2. Use approved plumbing procedures and materials to connect the water 
supply from your home water source to the pump.  

 

NOTE:

 Flush the water pipe before final connection to the pump to remove any debris that may be inside the pipe 

before it clogs or damages the Ejector.

 

 

PRO-V Models Only:

 This model includes a vented dual check valve along with a drain hose. Connect the drain hose 

to the barbed fitting on the Dual Check Valve Vent, turn the valve so the drain faces the floor, and direct the hose into 
the sump.  

_________________________________________________________________

 

 
Step 7. Install Water Alarm (see specifications with alarm) 

 

Install the battery:

 Remove battery compartment cover on the back of the alarm. Pull out float and wire stored inside. 

Snap a 9-volt battery onto the battery connector, place the battery inside compartment, line up float wire into slot at 
bottom of alarm, and replace cover. 

 

Mount the Alarm:

 Stick plastic cable tie mount to upper back of alarm; wrap releasable cable tie 

through the mount and around the suction pipe ~4 feet above floor,

 

or to a wall using screws. 

 

Position the sensor float:

 Clamp bracket to the pipe (shown here) or screw to the sump wall. 

Typical height would be just above the normal high water level in the sump, so it alarms at the 
same time as the pump turns on.  

 

Replace the battery

 when the alarm has operated for an extended period of time. Alarm will 

“chirp” when the battery needs to be replaced. A new battery should last a year, on standby. 

 

Relay Outputs:

 These are no volt, 

Normally Open

“dry” contacts that close when the alarm 

sounds and open when it stops. These may be connected to a security system or auto-dialer. 

 

Operation:

 When the float is up the alarm sounds and the relays close. When float drops, the alarm will silence and 

the relays will open. 

Start Up Procedure 

 
Open the water shut-off valve and check for leaks. 

Note:

 Pump may turn on at this time so be sure the discharge piping is 

completed. Lift the float ball for 10 seconds to release air trapped in the Ejector and Transfer Tube. Air and water will 
release from the drain port on the float unit just above the float ball. The first cycle may take longer than normal to shut off. 
Factory setting is approximately 

30 seconds after the float ball drops

 to its lowest position. Pump should stop after 30-

60 seconds. Lift the float a second time after the first run is over. If pump continues running too long or shuts off too 
quickly, see 

“Adjusting the Timing Control”

 on page 8. 

 

Operating Instructions 

 

Pump operates automatically. To operate manually, lift the float ball in the sump to its upper position for a few seconds till 
the water starts running and then lower it, simulating a normal rise and fall of the water and allowing the pump to operate 
through a complete cycle. This flushes the water pipes and confirms that the pump is functioning properly.  
 

Periodic Testing Procedures 

It is necessary to test this pump at least once every 3-4 months to ensure proper basement flood protection and to protect 
your warranty. Follow the procedures noted here, write down each of your test dates, and keep it with these instructions in 
a convenient location on or near the pump. 

Confirm that: 

 

When float ball is lifted, water flows from the port just above the float ball and the pump turns on. 

 

The pump runs and removes water from the sump at a normal rate. 

 

Pump then turns itself off approximately 30-40 seconds AFTER the float ball drops to its lowest position. This is the 
factory setting, but it may have been adjusted to run longer or shorter depending on sump water inflow rates. If 
needed, see 

“Adjusting the Timing Control”

 on page 8. 

 

Water should stop flowing from the port above the ball when you lower the float ball. 

 
 

Water Supply 

Water Alarm Kit 

Summary of Contents for RB750

Page 1: ...e If absolutely necessary may be used on RB750 only Note If using tubing RB750 only use a x reducer 4 Pipeline Restrictions Pump should be teed in before these devices that restrict water flow stop waste valves globe type valves and some Pressure Regulator Valves PRV Basepump MUST tee in before water softeners conditioners and or water filters Water meter must be minimum 5 8 or 3 4 standard Averag...

Page 2: ...C Check Valve 3 PVC Exit Unit with Internal Diffuser Disk 4 2 Clip on Hangers 5 Polypro Male Adapter 1 Float Assembly 2 12 Feet of Transfer Tube 3 5 Cable Ties 4 6 Clear tube To be used in Step 5 Parts Kit Water Alarm Kit 1 3 Wood Screws 2 Clip on Hanger for Suction Pipe 3 Suction Screen with PVC Adapter 4 2 Hose Clamps 3 Feet of Discharge Hose not shown 1 Alarm Battery 2 Mounting Bracket Screw 3 ...

Page 3: ...000 Male threaded Suction and Discharge Opening 1 1 4 socket CB1500 1 or Male threaded Suction and Discharge Opening 1 1 2 socket Water service requirements Minimum pressure 40 lb PSI Maximum pressure 90 lb PSI Minimum City Water Flow Rate RB750 7 GPM HB1000 10 GPM CB1500 15 GPM Back flow Prevention Check with your local plumbing or water department for their requirements regarding back flow preve...

Page 4: ...pendicular to exterior wall with discharge turned at an angle Under Joist Outdoor Discharge Basepump mounted under ceiling joist with Discharge hose sloping upward and out Suction Pipe Options Pump does not need to be directly above the sump in case of an obstacle such as a heat duct electrical panel window stairway etc Horizontal distance up to 10 Feet across Shared discharge with Primary Pump Yo...

Page 5: ...e to the proper length cement the upper end into the Ejector check valve making sure that the lower end of the Suction Screen is approx 2 4 inches above the bottom of the sump Either 45 or 90 degree elbows maybe used to offset the suction pipe if necessary See page 4 Suction pipe may be fastened to the side of the sump if necessary using the gray clamp included in the parts kit ___________________...

Page 6: ...ed to a security system or auto dialer Operation When the float is up the alarm sounds and the relays close When float drops the alarm will silence and the relays will open Start Up Procedure Open the water shut off valve and check for leaks Note Pump may turn on at this time so be sure the discharge piping is completed Lift the float ball for 10 seconds to release air trapped in the Ejector and T...

Page 7: ...ter supply to the pump and remove the tube from the top of the Float Assembly PUSH in the plastic ring while you PULL out the tube Point the end of the tube into the sump and turn the water on to the pump If water shoots out of the tube and the pump turns on then it appears the float is the problem Call the factory for support and or replacement If no water comes out check the other end of the Tra...

Page 8: ...rrants the Basepump the Product against defects in material and workmanship for a period of Five Years from the date of the shipment In the event of any defect within the warranty period the Company will at its option replace or recondition the Product without charge providing the Product is returned prepaid to our offices in Buffalo New York The replacement or reconditioning of the Product shall ...

Reviews: