Opening delay time (for 8 pin module)

The delay module is equipped with a controller, which is responsible for
the response time of the relay. This is the time at which the relays will switch
from one position to another when the opening signal to them is received via
the RS-485 interface, the “Lock” input and the exit buttons are pressed.

Opening

lock time

adjustment

Less

More

The use of electromagnetic locks.

When connecting electromagnetic locks, the controlling resistor needs
to be rotated to the right, and adjust the delay time so that it is in the range
of 4 to 8 seconds. If you need to use other values, this time can set more or less
recommended values, but not less than 2 seconds.

The use of electromechanical locks.

When connecting electromechanical locks, the controller must be turned
to the left, and the delay time is adjusted so that it is in the range
of 0.5 to 1 second. If necessary, the time can be slightly increased, but
it is absolutely not recommended to set this time for more than 2 seconds!

If you set a delay time of more than 2 seconds and use electromechanical
locks as part of a system, there is a high probability of failure of these
locks due to the technological design features of the magnetic coils
in these types of locks!

Summary of Contents for SH-42

Page 1: ...USER MANUAL TWO LOCKS CONTROL MODULE SH 42 ...

Page 2: ...vice description wiki bas ip com TWO LOCKS CONTROL MODULE Main feature Module supply voltage 12 V Power consumption in operating mode 1 W Standby power consumption 0 06 W Maximum current of connected load 7 A per channel Maximum constant load voltage 30 V Maximum AC load voltage 250 V Operating temperature 40 75 C Storage temperature 15 65 C Permissible humidity 20 80 Degree of protection IP30C Ov...

Page 3: ... Lock input only the first relay will act on switching For the Lock input it is necessary to use a low voltage external signal with a DC voltage from 9 to 12 V 12V DC Ground 485 485 Lock 12V DC Ground Lock SH 42 RS 485 Outdoor panel From the external signal source Relay Outputs It is possible to connect both electromagnetic and electromechanical locks to the relay outputs In this case two relays ar...

Page 4: ... Exit 2 and GND contacts 12V DC Ground 485 485 Lock Exit 1 Exit2 Fire input 12V DC Ground 485 485 Lock SH 42 module Outdoor panel Exit Button 1 Exit Button 2 12V DC Ground 485 485 Lock Exit 1 Exit2 Fire input 12V DC Ground 485 485 Lock SH 42 module Outdoor panel Exit Button 1 Exit Button 2 Fire alarm The option of connecting the exit and fire alarm buttons To connect the output control button of th...

Page 5: ...t the delay time so that it is in the range of 4 to 8 seconds If you need to use other values this time can set more or less recommended values but not less than 2 seconds The use of electromechanical locks When connecting electromechanical locks the controller must be turned to the left and the delay time is adjusted so that it is in the range of 0 5 to 1 second If necessary the time can be sligh...

Page 6: ...in the original packaging in a full complete set appearance corresponding to the new equipment and presence of all relevant properly filled documents This warranty is in addition to the constitutional and other consumer rights and in no way restrict them Terms of warranty The warranty card must indicate the name of the model serial number purchase date name of the seller seller company stamp and th...

Page 7: ...Notes EAN 5060514910559 ...

Page 8: ...www bas ip com ...

Reviews: