Opening delay time (for 8 pin module)
The delay module is equipped with a controller, which is responsible for
the response time of the relay. This is the time at which the relays will switch
from one position to another when the opening signal to them is received via
the RS-485 interface, the “Lock” input and the exit buttons are pressed.
Opening
lock time
adjustment
Less
More
The use of electromagnetic locks.
When connecting electromagnetic locks, the controlling resistor needs
to be rotated to the right, and adjust the delay time so that it is in the range
of 4 to 8 seconds. If you need to use other values, this time can set more or less
recommended values, but not less than 2 seconds.
The use of electromechanical locks.
When connecting electromechanical locks, the controller must be turned
to the left, and the delay time is adjusted so that it is in the range
of 0.5 to 1 second. If necessary, the time can be slightly increased, but
it is absolutely not recommended to set this time for more than 2 seconds!
If you set a delay time of more than 2 seconds and use electromechanical
locks as part of a system, there is a high probability of failure of these
locks due to the technological design features of the magnetic coils
in these types of locks!