8/28/20
12
3.
Output On
–
Wind speed is above the activation set point, output triggers after activatation
delay
4.
Output On
–
Wind speed is below the activation set point and the output has been triggered
5.
Output Off
–
Wind speed is below the activation and drop out set points, output turns off after
drop out delay
Diagram 2
–
No Delays
The WeatherBoss will close any open roof vents to the first programmed position when the
when the wind speed exceeds 20 miles per hour. The roof vents will return control of the roof vents to
the environmental controller when the wind speed drops below 15 miles per hour.
Activation Set Point
–
20 MPH
Drop Out Set Point
–
15 MPH
Activation Delay
–
0 Seconds
Drop Out Delay
–
0 Seconds
Activation
Set Point
Drop Out
Set Point
Relay Output
20 MPH
15 MPH
ON
OFF
OFF
1
2
3
4
5
Output
On
Output
depends on
wind speed
history
Output
Off