background image

8/28/20 

Drop Speed - 

If the wind speed is less than the drop out set point the alarm will decactivate. 

When the alarm deactivates, the roof vents will be under the control of the environmental 
controller. The drop out set point may be programmed for any wind speed between 0 and 120 
miles per hour (0 and 192 kilometers per hour).  

 

Drop Delay 

 

The drop out delay is the length of time that the wind speed will need to be below 

the drop out set point for the alarm to deactivate. When the alarm deactivates, the roof vents 
will be under the control of the environmental controller. The drop out delay may be 
programmed from 00:00 (MM:SS) to 99:99 (99 minutes:99 seconds).  

 

 

Temperature Sensor 

 

The WeatherBoss’s

 thermistor takes the outside temperature reading. This is an informational 

only sensor for outside temperature.  
 

Humidity Sensor (Optional) 

 

The humidity sensor is used to monitor the humidity in the outside air. The humidity probe 

needs to be calibrated before proper monitory of humidity levels can occur. The calibration code for 
your humidity sensor (found on the paperwork provided with your humidity sensor) needs to be entered 
into the WeatherBoss. Go to Menu -> Configuration -> Humidity Cal and enter the 4 digit code provided 

and press “

Save

”. 

If a humidity sensor is not being used, the setting should be set to 0 and the controller 

will display a 0% humidity level at all times. If the WeatherBoss is connected through Radio Link or 
Headgrower, the humidity levels sensed can be used to open and close programmed vents and other 

High Activate Speed

 

Click to select the high 

activate speed for either 

Wind A1 or A2. Represented 

by the green bar in the 

directional grid on the right. 

Low Activate Speed

 

Click to select the low 

activate speed for either 

Wind A1 or A2. Represented 

by the red bar in the 

directional grid on the right. 

Wind Direction Settings 

Represents the 8 directions sensed 

by the directional wind sensor. 

Click on a direction to toggle 

between which Activate Speed 

should be used (Green = High, Red 

= Low) for each direction.   

 

Activate Delay 

Activate Delay time in MM:SS 

(Minutes:Seconds) 

Drop Speed 

When the wind speed is 

less than the Drop Speed 

for the Drop Delay time, 

the Alarm will deactivate. 

Drop Delay 

The drop delay is the length of 

time the wind speed will need to 

be below the Drop Speed before 

the alarm will deactivate.  

 

Summary of Contents for WeatherBoss

Page 1: ...8 28 20 1 WeatherBoss Operation Manual BARTLETT Instrument Co 1032 Ave H Fort Madison IA 52627 319 372 8366 www bartinst com...

Page 2: ...MENU SCREEN 5 SETTINGS 5 CONFIGURATION 5 SENSOR READINGS 7 RAIN SENSOR 7 WEATHER SENSOR 7 TEMPERATURE SENSOR 8 HUMIDITY SENSOR OPTIONAL 8 LIGHT PHOTO SENSOR OPTIONAL 9 MANUALLY ACTIVATE ALARM 9 BLOCK...

Page 3: ...e East but a low speed for winds from the West Alarm 2 could be the opposite having a high speed alarm set for wind from the West and low speed alarm from the East This alarm could be assigned to Vent...

Page 4: ...arm is active it will change to either be yellow Force or red Alarm Light Sensor Reading Displays the current light sensor reading in micro moles per second per meter squared Wind A2 Reading Displays...

Page 5: ...the Headgrower cloud platform for remote monitoring and control of the WeatherBoss See the WiFi section for more information about firmware updates WiFi Set up Wi Fi for Firmware download and for rem...

Page 6: ...hannel for the Headgrower app See your Headgrower manual for more information Headgrower ID Displays the HEadgrower ID for your controller This is similar to your controllers serial number and cannot...

Page 7: ...rection if a standard anemometer is being used High Activation Speed If the wind speed is greater than the High Activation Speed the alarm will activate When the alarm activates the environmental cont...

Page 8: ...work provided with your humidity sensor needs to be entered into the WeatherBoss Go to Menu Configuration Humidity Cal and enter the 4 digit code provided and press Save If a humidity sensor is not be...

Page 9: ...larm The Force button may be pressed at any time to activate the output of the Weather Alarm this is a manual override feature The Weather Alarm will close any open vents to the first programmed posit...

Page 10: ...estore factory default settings The default settings are Activation Set Point 20 MPH Drop Out Set Point 15 MPH Activation Delay 4 Seconds Drop Out Delay 6 Seconds Units English Response Time 1 Wind Al...

Page 11: ...peed drops below 15 miles per hour for 6 seconds Activation Set Point 20 MPH Drop Out Set Point 15 MPH Activation Delay 4 Seconds Drop Out Delay 6 Seconds 1 Output Off Wind speed is below the activati...

Page 12: ...ays The WeatherBoss will close any open roof vents to the first programmed position when the when the wind speed exceeds 20 miles per hour The roof vents will return control of the roof vents to the e...

Page 13: ...on set point and the output has not been triggered 3 Output On Wind speed is above the activation set point output triggers immediately 4 Output On Wind speed is below the activation set point and the...

Reviews: