8/28/20
8
Drop Speed -
If the wind speed is less than the drop out set point the alarm will decactivate.
When the alarm deactivates, the roof vents will be under the control of the environmental
controller. The drop out set point may be programmed for any wind speed between 0 and 120
miles per hour (0 and 192 kilometers per hour).
Drop Delay
–
The drop out delay is the length of time that the wind speed will need to be below
the drop out set point for the alarm to deactivate. When the alarm deactivates, the roof vents
will be under the control of the environmental controller. The drop out delay may be
programmed from 00:00 (MM:SS) to 99:99 (99 minutes:99 seconds).
Temperature Sensor
The WeatherBoss’s
thermistor takes the outside temperature reading. This is an informational
only sensor for outside temperature.
Humidity Sensor (Optional)
The humidity sensor is used to monitor the humidity in the outside air. The humidity probe
needs to be calibrated before proper monitory of humidity levels can occur. The calibration code for
your humidity sensor (found on the paperwork provided with your humidity sensor) needs to be entered
into the WeatherBoss. Go to Menu -> Configuration -> Humidity Cal and enter the 4 digit code provided
and press “
Save
”.
If a humidity sensor is not being used, the setting should be set to 0 and the controller
will display a 0% humidity level at all times. If the WeatherBoss is connected through Radio Link or
Headgrower, the humidity levels sensed can be used to open and close programmed vents and other
High Activate Speed
Click to select the high
activate speed for either
Wind A1 or A2. Represented
by the green bar in the
directional grid on the right.
Low Activate Speed
Click to select the low
activate speed for either
Wind A1 or A2. Represented
by the red bar in the
directional grid on the right.
Wind Direction Settings
Represents the 8 directions sensed
by the directional wind sensor.
Click on a direction to toggle
between which Activate Speed
should be used (Green = High, Red
= Low) for each direction.
Activate Delay
Activate Delay time in MM:SS
(Minutes:Seconds)
Drop Speed
When the wind speed is
less than the Drop Speed
for the Drop Delay time,
the Alarm will deactivate.
Drop Delay
The drop delay is the length of
time the wind speed will need to
be below the Drop Speed before
the alarm will deactivate.