background image

Manual   2100-426
Page    6

WALL MOUNTING INFORMATION

1. Two holes, for the supply and return air openings,

must be cut through the wall as shown in Figure 3.

2. On wood-frame walls, the wall construction must be

strong and rigid enough to carry the weight of the
unit without transmitting any unit vibration. See
Figures 5 and 6.

INSTALLATION INSTRUCTIONS

         WARNING

Fire hazard can result if 1/4 inch clearance to
combustible materials for supply air duct is not
maintained. See Figure 3.

3. Concrete block walls must be thoroughly inspected to

insure that they are capable of carrying the weight of
the installing unit. See Figure 5.

MOUNTING THE UNIT

1. These units are secured by wall mounting brackets

which secure the unit to the outside wall surface at
both sides. A bottom mounting bracket is provided
for ease of installation.

2. The unit itself is suitable for “0” inch clearance, but

the supply air duct flange and the first 3 feet of
supply air duct require a minimum of 1/4 inch
clearance to combustible material. If a combustible
wall, use a minimum of 30-1/2" x 10-1/2"
dimensions for sizing. However, it is generally
recommended that a 1 inch clearance is used for ease
of installation and maintaining the required clearance
to combustible material. The supply air opening
would then be 32" x 12". See Figures 3, 4 and 5 for
details.

3. Locate and mark lag bolt locations and bottom

mounting bracket location. See Figure 5.

4. Mount bottom mounting bracket.

5. Hook top rain flashing under back bend of top. Top

rain flashing is shipped secured to the right side of
the back.

6. Position unit in opening and secure with 5/16 lag

bolts; use 7/8 inch diameter flat washers on the lag
bolts.

7. Secure rain flashing to wall and caulk across entire

length of top. See Figure 3.

8. For additional mounting rigidity, the return air and

supply air frames or collars can be drilled and
screwed or welded to the structural wall itself
(depending upon wall construction). Be sure to
observe required clearance if combustible wall.

9. On side by side installations, maintain a minimum of

20 inches clearance on left side to allow access to
heat strips and control panel and to allow proper
airflow to the outdoor coil. Additional clearance may
be required to meet local or national codes.

TYPICAL INSTALLATIONS

See Figure 6 for common ways to install the wall-mount
unit.

WIRING — MAIN POWER

Refer to the unit rating plate for wire sizing information
and maximum fuse or “HACR" type circuit breaker
size. Each outdoor unit is marked with a “Minimum
Circuit Ampacity”. This means that the field wiring
used must be sized to carry that amount of current.
Depending on the installed KW of electric heat, there
may be two field power circuits required. If this is the
case, the unit serial plate will so indicate. All models are
suitable only for connection with copper wire. Each unit
and/or wiring diagram will be marked “Use Copper
Conductors Only”. These instructions must be adhered
to. Refer to the National Electrical Code (NEC) for
complete current carrying capacity data on the various
insulation grades of wiring material. All wiring must
conform to NEC and all local codes.

The electrical data lists fuse and wire sizes (75ºC
copper) for all models, including the most commonly
used heater sizes. Also shown are the number of field
power circuits required for the various models with
heaters.

The unit rating plate lists a “Maximum Time Delay
Relay Fuse” or “HACR" type circuit breaker that is to
be used with the equipment. The correct size must be
used for proper circuit protection and also to assure that
there will be no nuisance tripping due to the momentary
high starting current of the compressor motor.

         WARNING

Failure to provide the 1/4 inch clearance
between the supply duct and a combustible
surface for the first 3 feet of duct can result in
fire.                                                    

Summary of Contents for WL701-B

Page 1: ...Volume III Tab 16 Date 01 01 03 Copyright 2003 Bard Manufacturing Company Bryan Ohio 43506 Since 1914 Moving ahead just as planned Model WL701 B WL701 C WL702 A WALL MOUNTED PACKAGED AIR CONDITIONER...

Page 2: ...11 Maximum ESP of Operation Electric Heat Only 15 Table 12 Cooling Pressure 16 Table 13 Optional Accessories 16 Getting Other Information and Publications For more information contact these publisher...

Page 3: ...culation for ACCA Manual J or Residential Winter and Manual N Summer Air Conditioning Low Pressure Low Velocity Duct ACCA Manual D or System Design for Winter and Manual Q Summer Air Conditioning FOR...

Page 4: ...inimum Circuit Ampacity values are to be used for sizing the field power conductors Refer to the National Electric Code latest version Article 310 for power conductor sizing CAUTION When more than one...

Page 5: ...1 8 5 1 4 0 3 6 1 1 1 2 4 7 3 4 3 4 4 2 1 2 4 4 1 3 3 4 8 7 3 3 0 1 TABLE 3 ELECTRICHEATTABLE s l e d o M A 2 0 7 L W B 1 0 7 L W C 1 0 7 L W 1 V 0 4 2 1 V 8 0 2 3 V 0 4 2 3 V 8 0 2 3 V 0 6 4 W K S P...

Page 6: ...regulations are at a variance with instructions installer should adhere to local codes DUCT WORK All duct work supply and return must be properly sized for the design air flow requirement of the equip...

Page 7: ...to the unit The damper blade is locked in the closed position to allow the damper to operate the maximum and minium blade position stops must be installed See Figure 2 All capacity efficiency and cos...

Page 8: ...and supply air frames or collars can be drilled and screwed or welded to the structural wall itself depending upon wall construction Be sure to observe required clearance if combustible wall 9 On side...

Page 9: ...t and while the unit is operating at full load maximum amperage operating condition Five 5 wires should be run from thermostat subbase to the 24V terminal board in the unit A five conductor 18 gauge c...

Page 10: ...2 TABLE 6 WALLTHERMOSTATANDSUBBASECOMBINATIONS t a t s o m r e h T e s a b b u S s e r u t a e F e t a n i m o d e r P 2 0 0 3 0 4 8 1 1 1 3 F 7 8 T 3 0 0 4 0 4 8 0 2 2 1 A 9 3 5 Q l o o c e g a t s 1...

Page 11: ...6 Page 9 FIGURE 6 WALL MOUNTINGINSTRUCTIONS MIS 1051 MIS 948 SEE FIGURE 3 MOUNTING INSTRUCTIONS FIGURE 5 WALL MOUNTINGINSTRUCTIONS SEE UNIT DIMENSIONS FIGURE 1 FOR ACTUAL DIMENSIONS SEE FIGURE 1 FOR D...

Page 12: ...Manual 2100 426 Page 10 FIGURE 7 COMMONWALL MOUNTINGINSTALLATIONS MIS 1050...

Page 13: ...Manual 2100 426 Page 11 FIGURE 8 LOWVOLTAGEWIRING MIS 1373C...

Page 14: ...compressor is change or rewired If improper rotation is corrected at this time there will be no negative impact on the durability of the compressor However reverse operation for over one hour may hav...

Page 15: ...k all power fuses or circuit breakers to be sure they are the correct rating 3 Periodic cleaning of the outdoor coil to permit full and unrestricted airflow circulation is essential During routine ope...

Page 16: ...be found later in the manual covering all models It is imperative to match the correct pressure table to the unit by model number ADJUSTMENTS Adjustable Delay on Make and Delay on Break Timer The pot...

Page 17: ...NT CHARGE The correct system R 22 charge is shown on the unit rating plate Optimum unit performance will occur with a refrigerant charge resulting in a suction line temperature 6 inches from compresso...

Page 18: ...9 6 3 3 3 0 7 1 5 3 B D 0 8 B W 7 6 e d i S w o L e d i S h g i H 7 6 0 2 2 8 6 6 3 2 9 6 4 5 2 0 7 1 7 2 1 7 7 8 2 2 7 6 0 3 3 7 4 2 3 4 7 2 4 3 5 7 0 6 3 B D 5 8 B W 2 7 e d i S w o L e d i S h g i...

Page 19: ......

Page 20: ......

Page 21: ......

Reviews: