PHASE MONITOR

All units with three phase scroll compressors are
equipped with a 3 phase line monitor to prevent
compressor damage due to phase reversal.

The phase monitor in this unit is equipped with two
LEDs.  If the Y signal is present at the phase monitor
and phases are correct the green LED will light.

If phases are reversed, the red fault LED will be lit and
compressor operation is inhibited.

If a fault condition occurs, reverse two of the supply
leads to the unit.  Do not reverse any of the unit factory
wires as damage may occur.

PRESSURE SERVICE PORTS

High and low pressure service ports are installed on all
units so that the system operating pressures can be
observed. Pressure tables can be found later in the
manual covering all models. It is imperative to match
the correct pressure table to the unit by model number.

ADJUSTMENTS

Adjustable Delay on Make and Delay on Break
Timer

The potentiometer is used to select Delay on Break time
from 30 seconds to 5 minutes.  Delay on Make (DOM)
timing on power-up and after power interruptions is
equal to 2 minutes plus 10% of Delay on Break (DOB)
setting:

0.5 minute (30 seconds) DOB = 123 second DOM
1.0 minute (60 seconds) DOB = 126 second DOM
2.0 minute (120 seconds) DOB = 132 second DOM
3.0 minute (180 seconds) DOB = 138 second DOM
4.0 minute (240 seconds) DOB = 144 second DOM
5.0 minute (300 seconds) DOB = 150 second DOM

During routine operation of the unit with no power
interruptions the compressor will operate on demand
with no delay.

Typical Settings for Dual Unit Installation:

Unit 1:  DOB set at 2 minutes, and DOM is 132 seconds

Unit 2:  DOB set at 4 minutes, and DOM is 144 seconds

Summary of Contents for WL701-B

Page 1: ...Volume III Tab 16 Date 01 01 03 Copyright 2003 Bard Manufacturing Company Bryan Ohio 43506 Since 1914 Moving ahead just as planned Model WL701 B WL701 C WL702 A WALL MOUNTED PACKAGED AIR CONDITIONER...

Page 2: ...11 Maximum ESP of Operation Electric Heat Only 15 Table 12 Cooling Pressure 16 Table 13 Optional Accessories 16 Getting Other Information and Publications For more information contact these publisher...

Page 3: ...culation for ACCA Manual J or Residential Winter and Manual N Summer Air Conditioning Low Pressure Low Velocity Duct ACCA Manual D or System Design for Winter and Manual Q Summer Air Conditioning FOR...

Page 4: ...inimum Circuit Ampacity values are to be used for sizing the field power conductors Refer to the National Electric Code latest version Article 310 for power conductor sizing CAUTION When more than one...

Page 5: ...1 8 5 1 4 0 3 6 1 1 1 2 4 7 3 4 3 4 4 2 1 2 4 4 1 3 3 4 8 7 3 3 0 1 TABLE 3 ELECTRICHEATTABLE s l e d o M A 2 0 7 L W B 1 0 7 L W C 1 0 7 L W 1 V 0 4 2 1 V 8 0 2 3 V 0 4 2 3 V 8 0 2 3 V 0 6 4 W K S P...

Page 6: ...regulations are at a variance with instructions installer should adhere to local codes DUCT WORK All duct work supply and return must be properly sized for the design air flow requirement of the equip...

Page 7: ...to the unit The damper blade is locked in the closed position to allow the damper to operate the maximum and minium blade position stops must be installed See Figure 2 All capacity efficiency and cos...

Page 8: ...and supply air frames or collars can be drilled and screwed or welded to the structural wall itself depending upon wall construction Be sure to observe required clearance if combustible wall 9 On side...

Page 9: ...t and while the unit is operating at full load maximum amperage operating condition Five 5 wires should be run from thermostat subbase to the 24V terminal board in the unit A five conductor 18 gauge c...

Page 10: ...2 TABLE 6 WALLTHERMOSTATANDSUBBASECOMBINATIONS t a t s o m r e h T e s a b b u S s e r u t a e F e t a n i m o d e r P 2 0 0 3 0 4 8 1 1 1 3 F 7 8 T 3 0 0 4 0 4 8 0 2 2 1 A 9 3 5 Q l o o c e g a t s 1...

Page 11: ...6 Page 9 FIGURE 6 WALL MOUNTINGINSTRUCTIONS MIS 1051 MIS 948 SEE FIGURE 3 MOUNTING INSTRUCTIONS FIGURE 5 WALL MOUNTINGINSTRUCTIONS SEE UNIT DIMENSIONS FIGURE 1 FOR ACTUAL DIMENSIONS SEE FIGURE 1 FOR D...

Page 12: ...Manual 2100 426 Page 10 FIGURE 7 COMMONWALL MOUNTINGINSTALLATIONS MIS 1050...

Page 13: ...Manual 2100 426 Page 11 FIGURE 8 LOWVOLTAGEWIRING MIS 1373C...

Page 14: ...compressor is change or rewired If improper rotation is corrected at this time there will be no negative impact on the durability of the compressor However reverse operation for over one hour may hav...

Page 15: ...k all power fuses or circuit breakers to be sure they are the correct rating 3 Periodic cleaning of the outdoor coil to permit full and unrestricted airflow circulation is essential During routine ope...

Page 16: ...be found later in the manual covering all models It is imperative to match the correct pressure table to the unit by model number ADJUSTMENTS Adjustable Delay on Make and Delay on Break Timer The pot...

Page 17: ...NT CHARGE The correct system R 22 charge is shown on the unit rating plate Optimum unit performance will occur with a refrigerant charge resulting in a suction line temperature 6 inches from compresso...

Page 18: ...9 6 3 3 3 0 7 1 5 3 B D 0 8 B W 7 6 e d i S w o L e d i S h g i H 7 6 0 2 2 8 6 6 3 2 9 6 4 5 2 0 7 1 7 2 1 7 7 8 2 2 7 6 0 3 3 7 4 2 3 4 7 2 4 3 5 7 0 6 3 B D 5 8 B W 2 7 e d i S w o L e d i S h g i...

Page 19: ......

Page 20: ......

Page 21: ......

Reviews: