background image

Manual   2100-426
Page    2

WALL MOUNT GENERAL INFORMATION

AIR CONDITIONER WALL MOUNT MODEL NOMENCLATURE

WL    70    1   –   B    09    X    X    X    X    X    J

NOTE:  For 0KW and circuit breakers (230/208 V) or pull disconnects (460 V) applications, insert 0Z in the KW field of model number.

MODEL NUMBER

CAPACITY
70 - 6 Ton

REVISION

VOLTS & PHASE
A - 230/208-1
B - 230/208/60-3
C - 460/60-3

CONTROL MODULES
J - Standard on all

   Models

COIL OPTIONS
X - Standard
1 - Phenolic Coated Evaporator
2 - Phenolic Coated Condenser
3 - Phenolic Coated Evaporator

   and Condenser

COLOR OPTIONS
X - Beige

(Standard)

1 - White

OUTLET OPTIONS
X - Front (Standard)

FILTER OPTIONS
X - One Inch Throwaway

    (Standard)

W - One Inch Washable
P - Two Inch Pleated

KW
00 - No KW
0Z - No KW

w/Circuit Breaker
or Pull
Disconnect

05 - 5 KW
09 - 9 KW
10 - 10 KW
15 - 15 KW
18 - 18 KW

VENTILATION OPTIONS
X - Barometric Fresh Air Damper

(Standard)

B - Blank-off Plate
M - Motorized Fresh Air Damper

V - Commercial Room Ventilator -

Motorized with Exhaust

E - Economizer (Internal) - Fully

Modulating with Exhaust

R - Energy Recovery Ventilator -

with Exhaust

j

k

l

Maximum size of the time delay fuse or HACR type circuit breaker for protection of field wiring conductors.

Based on 75°C copper wire.  All wiring must conform to the National Electric Code (NEC) and all local codes.

These "Minimum Circuit Ampacity" values are to be used for sizing the field power conductors.  Refer to the
National Electric Code (latest version), Article 310 for power conductor sizing.    CAUTION:  When more than one
filed power conductor circuit is run through one conduit, the conductors must be derated.  Pay special attention to
Note * of Table 310 regarding Ampacity Adjustment Factors when more than 3 conductors are in a raceway.

TABLE  1

ELECTRICAL SPECIFICATIONS

s

l

e

d

o

M

d

e

t

a

R

f

o

.

o

N

r

e

w

o

P

s

t

i

u

c

r

i

C

t

i

u

c

r

i

C

e

l

g

n

i

S

t

i

u

c

r

i

C

l

a

u

D

3

A

C

M

1

P

O

M

2

d

l

e

i

F

e

r

i

W

e

z

i

S

2

d

n

u

o

r

G

e

r

i

W

e

z

i

S

3

A

C

M

1

P

O

M

2

e

r

i

W

d

l

e

i

F

e

z

i

S

2

d

n

u

o

r

G

e

z

i

S

e

r

i

W

T

K

C

A

T

K

C

B

T

K

C

A

T

K

C

B

T

K

C

A

T

K

C

B

T

K

C

A

T

K

C

B

Z

0

A

,

0

0

A

-

2

0

7

L

W

5

0

A

-

0

1

A

-

5

1

A

-

1

-

8

0

2

/

3

0

2

1

-

8

0

2

/

0

3

2

1

-

8

0

2

/

0

3

2

1

-

8

0

2

/

0

3

2

1
1
1

2

r

o

1

8

4

8

4

9

5

5

8

0

6

0

6

0

6

0

9

8
8
6
4

0

1

0

1

0

1

8

A

N

A

N

A

N

9

5

A

N

A

N

A

N

6

2

A

N

A

N

A

N

0

6

A

N

A

N

A

N

0

3

A

N

A

N

A

N

6

A

N

A

N

A

N

0

1

A

N

A

N

A

N

0

1

A

N

A

N

A

N

0

1

Z

0

B

,

0

0

B

-

1

0

7

L

W

9

0

B

-

5

1

B

-

3

-

8

0

2

/

0

3

2

1
1
1

6

3

6

3

2

5

0

5

0

5

0

6

8
8
6

0

1

0

1

0

1

A

N

A

N

A

N

A

N

A

N

A

N

A

N

A

N

A

N

A

N

A

N

A

N

A

N

A

N

A

N

A

N

A

N

A

N

A

N

A

N

A

N

A

N

A

N

A

N

Z

0

C

,

0

0

C

-

1

0

7

L

W

9

0

C

-

5

1

C

-

3

-

0

6

4

1
1
1

7

1

7

1

6

2

5

2

5

2

0

3

2

1

2

1

0

1

2

1

2

1

0

1

A

N

A

N

A

N

A

N

A

N

A

N

A

N

A

N

A

N

A

N

A

N

A

N

A

N

A

N

A

N

A

N

A

N

A

N

A

N

A

N

A

N

A

N

A

N

A

N

Summary of Contents for WL701-B

Page 1: ...Volume III Tab 16 Date 01 01 03 Copyright 2003 Bard Manufacturing Company Bryan Ohio 43506 Since 1914 Moving ahead just as planned Model WL701 B WL701 C WL702 A WALL MOUNTED PACKAGED AIR CONDITIONER...

Page 2: ...11 Maximum ESP of Operation Electric Heat Only 15 Table 12 Cooling Pressure 16 Table 13 Optional Accessories 16 Getting Other Information and Publications For more information contact these publisher...

Page 3: ...culation for ACCA Manual J or Residential Winter and Manual N Summer Air Conditioning Low Pressure Low Velocity Duct ACCA Manual D or System Design for Winter and Manual Q Summer Air Conditioning FOR...

Page 4: ...inimum Circuit Ampacity values are to be used for sizing the field power conductors Refer to the National Electric Code latest version Article 310 for power conductor sizing CAUTION When more than one...

Page 5: ...1 8 5 1 4 0 3 6 1 1 1 2 4 7 3 4 3 4 4 2 1 2 4 4 1 3 3 4 8 7 3 3 0 1 TABLE 3 ELECTRICHEATTABLE s l e d o M A 2 0 7 L W B 1 0 7 L W C 1 0 7 L W 1 V 0 4 2 1 V 8 0 2 3 V 0 4 2 3 V 8 0 2 3 V 0 6 4 W K S P...

Page 6: ...regulations are at a variance with instructions installer should adhere to local codes DUCT WORK All duct work supply and return must be properly sized for the design air flow requirement of the equip...

Page 7: ...to the unit The damper blade is locked in the closed position to allow the damper to operate the maximum and minium blade position stops must be installed See Figure 2 All capacity efficiency and cos...

Page 8: ...and supply air frames or collars can be drilled and screwed or welded to the structural wall itself depending upon wall construction Be sure to observe required clearance if combustible wall 9 On side...

Page 9: ...t and while the unit is operating at full load maximum amperage operating condition Five 5 wires should be run from thermostat subbase to the 24V terminal board in the unit A five conductor 18 gauge c...

Page 10: ...2 TABLE 6 WALLTHERMOSTATANDSUBBASECOMBINATIONS t a t s o m r e h T e s a b b u S s e r u t a e F e t a n i m o d e r P 2 0 0 3 0 4 8 1 1 1 3 F 7 8 T 3 0 0 4 0 4 8 0 2 2 1 A 9 3 5 Q l o o c e g a t s 1...

Page 11: ...6 Page 9 FIGURE 6 WALL MOUNTINGINSTRUCTIONS MIS 1051 MIS 948 SEE FIGURE 3 MOUNTING INSTRUCTIONS FIGURE 5 WALL MOUNTINGINSTRUCTIONS SEE UNIT DIMENSIONS FIGURE 1 FOR ACTUAL DIMENSIONS SEE FIGURE 1 FOR D...

Page 12: ...Manual 2100 426 Page 10 FIGURE 7 COMMONWALL MOUNTINGINSTALLATIONS MIS 1050...

Page 13: ...Manual 2100 426 Page 11 FIGURE 8 LOWVOLTAGEWIRING MIS 1373C...

Page 14: ...compressor is change or rewired If improper rotation is corrected at this time there will be no negative impact on the durability of the compressor However reverse operation for over one hour may hav...

Page 15: ...k all power fuses or circuit breakers to be sure they are the correct rating 3 Periodic cleaning of the outdoor coil to permit full and unrestricted airflow circulation is essential During routine ope...

Page 16: ...be found later in the manual covering all models It is imperative to match the correct pressure table to the unit by model number ADJUSTMENTS Adjustable Delay on Make and Delay on Break Timer The pot...

Page 17: ...NT CHARGE The correct system R 22 charge is shown on the unit rating plate Optimum unit performance will occur with a refrigerant charge resulting in a suction line temperature 6 inches from compresso...

Page 18: ...9 6 3 3 3 0 7 1 5 3 B D 0 8 B W 7 6 e d i S w o L e d i S h g i H 7 6 0 2 2 8 6 6 3 2 9 6 4 5 2 0 7 1 7 2 1 7 7 8 2 2 7 6 0 3 3 7 4 2 3 4 7 2 4 3 5 7 0 6 3 B D 5 8 B W 2 7 e d i S w o L e d i S h g i...

Page 19: ......

Page 20: ......

Page 21: ......

Reviews: