Manual 2100-587C
Page
27 of 59
19. MANIFOLD PRESSURE
ADJUSTMENT
A 0 to 15 inch water manometer with 0.1 inch
resolution and a 1/8” NPT manual shut off valve is
needed to measure actual manifold pressure.
Depending on your local gas heating value and
elevation, you may need to adjust manifold pressure
or change orifices to get proper gas input rate. Check
with your local gas supplier to determine heating value
(BTU/cu. ft.) of natural gas in your area.
NOTE: If furnace is being installed at an altitude
of more than 6,000 feet above sea level, you
must derate the furnace. See Section 21
“Standard Orifice Sizing and High Altitude
Derate”.
20. CHECKING GAS INPUT RATE
It is the installer’s responsibility to see that the
BTU input rate of the furnace is properly adjusted.
Under-firing could cause inadequate heat, excessive
condensation or ignition problems. Overfiring could
cause sooting, flame impingement or overheating of
heat exchanger.
1. Turn off gas at equipment shut off valve in gas
supply line just ahead of furnace.
2. Remove plug from outlet pressure tap in gas control
or gas manifold.
3. Install 1/8” NPT manual shut off valve in hole
vacated by plug. Make sure shut off valve is in off
position.
4. Attach manometer to 1/8” NPT manual shut off
valve just installed.
PROPANE (LP) GAS CONVERSION
This unit may be converted in the field for
use with Propane (LP) gas. Propane gas
conversion kit number WGCK-1 is designed
for conversions of units installed from
0 – 6,000 feet elevations. Propane gas
conversion kit number WGCK-2 is designed
for conversions of units installed from 6,001
– 10,000 feet elevations. These kits may be
purchased from your local distributor.
5. Slowly open equipment shut off valve in gas supply
line just ahead of furnace. Start furnace following
“Operating Instructions” on front door.
6. Slowly open 1/8” NPT manual shut off valve leading
to manometer.
7. Read manifold pressure on manometer.
8. Adjust manifold pressure by turning gas control
regulator adjusting screw clockwise to increase
pressure or turning counterclockwise to decrease
pressure. Manifold pressure must be within
allowable range as follows:
• Natural gas manifold pressure must be between
3.2 and 3.8 inches W.C. Rated pressure is 3.5
inches.
• Propane gas (LP) manifold pressure must be
between 9.7 and 10.3 inches W.C. Rated
pressure is 10 inches.
NOTE: For natural gas, if gas flow rate can’t be
properly set within these pressure ranges
then you must change main burner orifices to
obtain proper gas flow rate.
9. Shut off furnace. Turn off gas at equipment shut off
valve in gas supply line just ahead of furnace. Install
outlet pressure tap plug in gas control. Turn on gas.
10. Check regulator adjustment cover screw and gas
control plug for gas leaks. Use a commercial soap
solution made for leak detection.
WARNING
Failure to adjust furnace to the proper firing
rate could cause heat exchanger failure.
WARNING
When converting from propane (LP) gas to
natural gas, the gas orifice spuds and gas
valve spring must be replaced and the gas
valve regulator pressure must be adjusted
correctly. Failure to do so can result in fire,
injury or death. Refer to Tables 8 and 8A for
proper orifice sizing.
Natural gas spring kit, Part number 5603-
007, can be purchased through your local
distributor.
WARNING
Correct manifold pressure is necessary for
proper ignition and burner operation. Failure
to accurately adjust pressure could cause
heat exchanger failure.
Summary of Contents for WG3S2-A
Page 11: ...Manual 2100 587C Page 11 of 59 FIGURE 2A MOUNTING INSTRUCTIONS FOR WG3S2...
Page 12: ...Manual 2100 587C Page 12 of 59 FIGURE 2B MOUNTING INSTRUCTIONS FOR WG4S2 AND WG5S2...
Page 15: ...Manual 2100 587C Page 15 of 59 FIGURE 6 COMMON WALL MOUNTING INSTALLATIONS...
Page 25: ...Manual 2100 587C Page 25 of 59 FIGURE 11 GAS PIPE CONNECTION...