background image

Manual 2100-635A
Page 

12 of 18

BASIC INSTALLATION

(Factory-Installed Versions)

1.  Remove blower access door and service door.  

Room filter located above air circulation blower.  
Install filter.

2.  Remove and install air intake hood (see Step 15 of 

Basic Field Installation on page 11).

3.  Refer to Control Wiring section for suggested 

control schemes for the WERVP.

4.  After wiring, replace all panels.

CONTROL WIRING

The WERVP comes from the factory with the low 
voltage control wires connected to the wall mount 
low voltage terminal strip.  Care must be taken when 
deciding how to control the operation of the ventilator.  
When designing the control circuit for the ventilator, 
the following requirements must be met.

Control Requirements

1.  Indoor blower motor must be run whenever the 

WERVP is run.

2.  Select the correct motor speed tap in the WERVP.  

Using Table 1, determine the motor speed needed 
to get the desired amount of ventilation air needed.  
For instance, do not use the high speed tap on 
a WERVPA5 if only 300 CFM of ventilation air is 
needed.  Use the low speed tap instead.  Using the 
high speed tap would serve no useful purpose and 
significantly affect the overall efficiency of the air 
conditioning system.  System operating cost would 
also increase.

TABLE 1

Ventilation Air (CFM)

Model

High Speed

(Black)

Medium Speed

(Blue)

Low Speed

(Red)

WERVPA5
WERVPC5

450

375

300

system that in some way can control the system 
based on occupancy.

!

IMPORTANT

Operating the WERVP during unoccupied 

periods can result in a buildup of moisture 

in the structure. 

3.  Run the WERVP only during periods when the 

conditioned space is occupied.  Running the 
WERVP during unoccupied periods wastes energy, 
decreases the expected life of the WERVP and can 
result in a large moisture buildup in the structure.  
The WERVP removes 60-70% of the moisture in 
the incoming air, not 100% of it.  Running the 
WERVP when the structure is unoccupied allows 
moisture to build up in the structure because 
there is little or no cooling load.  Thus, the air 
conditioner is not running enough to remove the 
excess moisture being brought in.  Use a control 

Recommended Control Sequences

Several possible control scenarios are listed below:

1.  Use a programmable electronic thermostat with 

auxiliary terminal to control the WERVP based 
on daily programmed occupance periods.  Bard 
markets and recommends Bard Part No. 8403-
060 programmable electronic thermostat for air 
conditioner and heat pump applications (see Figure 
10 on page 14).

2.  Use a CO

2

 sensor in conjunction with a mechanical 

thermostat to keep CO

2

 at required levels.  Bard 

recommends using Bard CO

2

 controller 8403-067 

(see Figure 11 on page 15).

3.  Use a motion sensor in conjunction with a 

mechanical thermostat to determine occupancy 
in the structure.  Bard recommends Bard Model 
CS9B*-**** CompleteStat for this application (see 
Figure 11 on page 15). 

4.  Use a DDC control system to control the WERVP 

based on a room occupancy schedule to control 
the WERVP.

5.  Tie the operation of the WERVP into the light 

switch.  The lights in a room are usually on only 
when occupied.

6.  Use a manual timer that the occupants turn to 

energize the WERVP for a specific number of hours.

7.  Use a programmable mechanical timer to energize 

the WERVP and indoor blower during occupied 
periods of the day.

Summary of Contents for WERVPA5

Page 1: ...ND OUTDOOR AIR SHUT OFF DAMPER Models INSTALLATION INSTRUCTIONS WERVPA5 WERVPC5 Bard Manufacturing Company Inc Bryan Ohio 43506 www bardhvac com Manual 2100 635A Supersedes 2100 635 Date 3 21 18 For U...

Page 2: ...Assembly and Discard Shipping Plate 5 Figure 2 Remove Access Panels 6 Figure 3 Remove Air Filter and Exhaust Cover Plate 7 Figure 4 Install Exhaust Blower Assembly 8 Figure 5 Plug Exhaust Blower Into...

Page 3: ...mmer and winter conditions Provides required ventilation to meet the requirements of ASHRAE 62 1 standard NOTE During operation below 5 F outdoor temperature freezing of moisture in the heat transfer...

Page 4: ...0 20533 13952 8029 4738 4738 4738 4738 4738 4738 4738 15794 9213 3290 0 0 26325 17887 10293 6075 6075 6075 6075 6075 6075 6075 20250 11812 4218 0 0 17374 11805 6793 4009 4009 4009 4009 4009 4009 4009...

Page 5: ...1 or 3 phase WERVPC5 W42AA W42HA C W48AA W48HA C W60AA W60HA C W72AB C 460 3 phase FIGURE 1 Remove Blower Assembly and Discard Shipping Plate MIS 2233 Discard Shipping plate Remove Exhaust Blower Ass...

Page 6: ...r filter access and service access panels on the Bard wall mount unit see Figure 2 Save the filter access panel and discard service access panel FIGURE 2 Remove Access Panels MIS 3744 SERVICE ACCESS D...

Page 7: ...emove and discard the exhaust cover plate and remove center screw from condenser grille FIGURE 3 Remove Air Filter and Exhaust Cover Plate MIS 3745 REMOVE DISCARD EXHUAST PLATE COVER UNIT AIR FILTER R...

Page 8: ...n top of condenser partition see Figure 5 inset This is important to insure proper drainage of any water entering damper assembly 8 Remove access panel and plug in exhaust blower as shown in Figure 5...

Page 9: ...k together see Figure 5 MIS 3747 VENTILATOR SIDE SECTION VIEW GRILL AND SERVICE DOOR BETWEEN THE CONDENSER PARTITION SERVICE DOOR CONDENSER LIP OF ERV IS TO BE HEAT RECOVERY FRONT GRILLE GRILLE TO INS...

Page 10: ...3748 LOW VOLTAGE AS SHOWN AND WIRE INSTALL 1 480701 0 CAP RECOVERY ASSEMBLY INPUT FROM HEAT PER WIRE DIAGRAM HIGH VOLTAGE WIRES GROUND WIRE NOTE These 24 volt control wires control the starting and st...

Page 11: ...tor checkout 14 Re install the blower access and filter access panels at top of unit and secure with sheet metal screws 15 Replace the vent option access panel with the new panel provided Attach air i...

Page 12: ...3 Run the WERVP only during periods when the conditioned space is occupied Running the WERVP during unoccupied periods wastes energy decreases the expected life of the WERVP and can result in a large...

Page 13: ...ARNING Open disconnect to shut all power OFF before changing motor speeds Failure to do so could result in injury or death due to electrical shock FIGURE 9 Airflow Diagram MIS 3750 ROOM AIR CONDENSER...

Page 14: ...1 Humidity W1 E D YO Brown White Y1 L W2 R A Y2 G L 1 W3 8 Heat Pump Y1 C G R Y2 B W1 W2 A 2 D Wall Mount ONLY NEEDED IF DEHUMIDIFICATION IS USED 1 PROGRAM THERMOSTAT FOR CONTINUOUS BLOWER DURING OCC...

Page 15: ...VAC INPUT CO2 OUTPUT TEMP OUTPUT W2 2 3 6 Brown White Red White RT 1 W1 E Orange Black White C Thermostat With D A W2 B W1 L ONLY NEEDED IF DEHUMIDIFICATION IS USED Optional CO Controller Humidity Hea...

Page 16: ...ation systems energy transfer surfaces must be accessible for washing to remove oils grease tars and dirt that can impede performance or generate odors Washing of the desiccant surfaces is required to...

Page 17: ...moval capacity it is recommended that the energy recovery wheels be sprayed with a diluted nonacid based evaporator coil cleaner or alkaline detergent solution such as 409 NOTE Do not use acid based c...

Page 18: ...Manual 2100 635A Page 18 of 18 FIGURE 13 Hub Assembly with Ball Bearings...

Reviews: