background image

Manual 2100-635A
Page 

3 of 18

WALL MOUNT ENERGY RECOVERY VENTILATOR MODEL NOMENCLATURE

GENERAL DESCRIPTION

The Wall Mount Energy Recovery Ventilator was 
designed to provide energy efficient, cost effective 
ventilation to meet IAQ (Indoor Air Quality) 
requirements while still maintaining good indoor 
comfort and humidity control for a variety of 
applications such as schools, classrooms, lounges, 
conference rooms, beauty salons and others.  It 
provides a constant supply of fresh air for control 
of airborne pollutants including CO

2

, smoke, radon, 

formaldehyde, excess moisture, virus and bacteria.

The ventilator incorporates patented rotary heat 
exchanger technology to remove both heat and moisture.

It is designed as a single package which can be easily 
factory or field installed for new installations or retrofit 
to the new Bard W series wall-mounted units.  The 
package consists of a unique rotary Energy Recovery 
Cassette that can be easily removed for cleaning or 
maintenance.  The WERVP*5 has two 15" diameter 
heat transfer wheels for efficient heat transfer.  The 
heat transfer wheels use a permanently bonded dry 
desiccant coating for total heat recovery.  An outdoor 
air shutoff damper is an integral feature of the WERVP 
and prevents infiltration when the ERV is turned off.

Ventilation is accomplished with two blower/motor 
assemblies each consisting of a drive motor and dual 
blowers for maximum ventilation at low sound levels.  
The intake and exhaust blowers can be operated at the 
same speed (airflow rate) or different speeds to allow 
flexibility in maintaining desired building pressurization 
conditions.  Factory shipped on medium intake and low 
exhaust.  See Figure 8 on page 13 to change speeds.  
The rotating energy wheels provide the heat transfer 

ELECTRICAL SPECIFICATIONS

effectively during both summer and winter conditions.  
Provides required ventilation to meet the requirements 
of ASHRAE 62.1 standard.

NOTE:

  During operation below 5

°

F outdoor 

temperature, freezing of moisture in the heat 

transfer wheel can occur.  Consult the factory if 

this possibility exists.

GENERAL INFORMATION

NOTE:

  This manual covers both factory- and field-

installed WERVP assemblies.  For factory-

installed WERVP, skip information pertaining to 

installation of the WERVP system.

The ventilator should only be installed by a trained 
heating and air conditioning technician.  These 
instructions serve as a guide to the technician installing 
the ventilator package.  They are not intended as a step-
by-step procedure with which the mechanically inclined 
owner can install the package.  The ventilator housing is 
shipped in one carton which contains the following:
•  Energy recovery ventilator
•  Service door
•  Rain hood and mist eliminator
•  Installation instructions

UNPACKING

Upon receipt of the equipment, be sure to compare the 
model number found on the shipping label with the 
accessory identification information on the ordering and 
shipping document to verify that the correct accessory 
has been shipped.

Inspect the carton housing of each ventilator as it is 
received and before signing the freight bill, verify that 
all items have been received and that there is no visible 
damage.  Note any shortages or damage on all copies 
of the freight bill.  The receiving party must contact 
the last carrier immediately, preferably in writing, 
requesting inspection by the carrier’s agent.  Concealed 
damage not discovered until after loading must be 
reported to the carrier within 15 days of its receipt.

    

 

 

 

   

W    ERV    P    A    5   –   X

W – Wall Mount

Color
X – Beige
1 – White
4 – Gray
5 – Desert Brown

Energy Recovery Ventilator

Wall Mount – Cabinet Size
5 – W42A* thru W72A*
 

W42H* thru W60H*

 

(* revision 

letter

)

Electrical
A – 230/208 volt
C – 460 volt

Plug-In Vent Connection

8 – Dark Bronze
A – Aluminum
S – Stainless

Model

Voltage

Amps

Control 

Voltage

WERVPA5

230/208

2.2

24V

WERVPC5

460

1.2

24V

Summary of Contents for WERVPA5

Page 1: ...ND OUTDOOR AIR SHUT OFF DAMPER Models INSTALLATION INSTRUCTIONS WERVPA5 WERVPC5 Bard Manufacturing Company Inc Bryan Ohio 43506 www bardhvac com Manual 2100 635A Supersedes 2100 635 Date 3 21 18 For U...

Page 2: ...Assembly and Discard Shipping Plate 5 Figure 2 Remove Access Panels 6 Figure 3 Remove Air Filter and Exhaust Cover Plate 7 Figure 4 Install Exhaust Blower Assembly 8 Figure 5 Plug Exhaust Blower Into...

Page 3: ...mmer and winter conditions Provides required ventilation to meet the requirements of ASHRAE 62 1 standard NOTE During operation below 5 F outdoor temperature freezing of moisture in the heat transfer...

Page 4: ...0 20533 13952 8029 4738 4738 4738 4738 4738 4738 4738 15794 9213 3290 0 0 26325 17887 10293 6075 6075 6075 6075 6075 6075 6075 20250 11812 4218 0 0 17374 11805 6793 4009 4009 4009 4009 4009 4009 4009...

Page 5: ...1 or 3 phase WERVPC5 W42AA W42HA C W48AA W48HA C W60AA W60HA C W72AB C 460 3 phase FIGURE 1 Remove Blower Assembly and Discard Shipping Plate MIS 2233 Discard Shipping plate Remove Exhaust Blower Ass...

Page 6: ...r filter access and service access panels on the Bard wall mount unit see Figure 2 Save the filter access panel and discard service access panel FIGURE 2 Remove Access Panels MIS 3744 SERVICE ACCESS D...

Page 7: ...emove and discard the exhaust cover plate and remove center screw from condenser grille FIGURE 3 Remove Air Filter and Exhaust Cover Plate MIS 3745 REMOVE DISCARD EXHUAST PLATE COVER UNIT AIR FILTER R...

Page 8: ...n top of condenser partition see Figure 5 inset This is important to insure proper drainage of any water entering damper assembly 8 Remove access panel and plug in exhaust blower as shown in Figure 5...

Page 9: ...k together see Figure 5 MIS 3747 VENTILATOR SIDE SECTION VIEW GRILL AND SERVICE DOOR BETWEEN THE CONDENSER PARTITION SERVICE DOOR CONDENSER LIP OF ERV IS TO BE HEAT RECOVERY FRONT GRILLE GRILLE TO INS...

Page 10: ...3748 LOW VOLTAGE AS SHOWN AND WIRE INSTALL 1 480701 0 CAP RECOVERY ASSEMBLY INPUT FROM HEAT PER WIRE DIAGRAM HIGH VOLTAGE WIRES GROUND WIRE NOTE These 24 volt control wires control the starting and st...

Page 11: ...tor checkout 14 Re install the blower access and filter access panels at top of unit and secure with sheet metal screws 15 Replace the vent option access panel with the new panel provided Attach air i...

Page 12: ...3 Run the WERVP only during periods when the conditioned space is occupied Running the WERVP during unoccupied periods wastes energy decreases the expected life of the WERVP and can result in a large...

Page 13: ...ARNING Open disconnect to shut all power OFF before changing motor speeds Failure to do so could result in injury or death due to electrical shock FIGURE 9 Airflow Diagram MIS 3750 ROOM AIR CONDENSER...

Page 14: ...1 Humidity W1 E D YO Brown White Y1 L W2 R A Y2 G L 1 W3 8 Heat Pump Y1 C G R Y2 B W1 W2 A 2 D Wall Mount ONLY NEEDED IF DEHUMIDIFICATION IS USED 1 PROGRAM THERMOSTAT FOR CONTINUOUS BLOWER DURING OCC...

Page 15: ...VAC INPUT CO2 OUTPUT TEMP OUTPUT W2 2 3 6 Brown White Red White RT 1 W1 E Orange Black White C Thermostat With D A W2 B W1 L ONLY NEEDED IF DEHUMIDIFICATION IS USED Optional CO Controller Humidity Hea...

Page 16: ...ation systems energy transfer surfaces must be accessible for washing to remove oils grease tars and dirt that can impede performance or generate odors Washing of the desiccant surfaces is required to...

Page 17: ...moval capacity it is recommended that the energy recovery wheels be sprayed with a diluted nonacid based evaporator coil cleaner or alkaline detergent solution such as 409 NOTE Do not use acid based c...

Page 18: ...Manual 2100 635A Page 18 of 18 FIGURE 13 Hub Assembly with Ball Bearings...

Reviews: