background image

Manual   2100-427
Page    5

SHIPPING DAMAGE

Upon receipt of equipment, the carton should be
checked for external signs of shipping damage.  If
damage is found, the receiving party must contact the
last carrier immediately, preferably in writing,
requesting inspection by the carrier’s agent.

GENERAL

The equipment covered in this manual is to be installed
by trained, experienced service and installation
technicians.

The refrigerant system is completely assembled and
charged.  All internal wiring is complete.

The unit is designed for use with or without duct work.
Flanges are provided for attaching the supply and return
ducts.

These instructions explain the recommended method to
install the air cooled self-contained unit and the
electrical wiring connections to the unit.

While these instructions are intended as a general
recommended guide, they do not supersede any national
and/or local codes in any way.  Authorities having
jurisdiction should be consulted before the installation
is made.  See Page 1 for information on codes and
standards.

Size of unit for a proposed installation should be based
on heat loss calculation made according to methods of
Air Conditioning Contractors of America (ACCA).  The
air duct should be installed in accordance with the
Standards of the National Fire Protection Association
for the Installation of Air Conditioning and Ventilating
Systems of Other Than Residence Type, NFPA No.
90A, and Residence Type Warm Air Heating and Air
Conditioning Systems, NFPA No. 90B.  Where local
regulations are at a variance with instructions, installer
should adhere to local codes.

DUCT WORK

All duct work, supply and return, must be properly
sized for the design air flow requirement of the
equipment.  Air Conditioning Contractors of America
(ACCA) is an excellent guide to proper sizing.  All duct
work or portions thereof not in the conditioned space
should be properly insulated in order to both conserve
energy and prevent condensation or moisture damage.

These instructions and any instructions packaged with
any separate equipment, required to make up the entire
air conditioning system should be carefully read before
beginning the installation. Note particularly any tags
and/or labels attached to the equipment.

Design the duct work according to methods given by
the Air Conditioning Contractors of America (ACCA).
When duct runs through unheated spaces, it should be
insulated with a minimum of one inch of insulation.
Use insulation with a vapor barrier on the outside of
the insulation.  Flexible joints should be used to
connect the duct work to the equipment in order to
keep the noise transmission to a minimum.

A 1/4 inch clearance to combustible material for the
first three feet of duct attached to the outlet air frame is
required.  See Wall Mounting Instructions and Figures
3 and 3A for further details.

Ducts through the walls must be insulated and all joints
taped or sealed to prevent air or moisture entering the
wall cavity.

Some installations may not require any return air duct.
A metallic return air grille is required with installations
not requiring a return air duct.  The spacing between
louvers on the grille shall not be larger than 5/8 inch.

NOTE:  If no return air duct is used, applicable

installation codes may limit this cabinet to
installation only in a single story structure.

Any grille that meets with 5/8 inch louver criteria may
be used.  It is recommended that Bard Return Air Grille
Kit RG2 through RG5 or RFG2 through RFG5 be
installed when no return duct is used.  Contact
distributor or factory for ordering information.  If using
a return air filter grille, filters must be of sufficient size
to allow a maximum velocity of 400 fpm.

CONDENSATE DRAIN

A plastic drain hose extends from the drain pan at the
top of the unit down to the unit base.  There are
openings in the unit base for the drain hose to pass
through.  In the event the drain hose is connected to a
drain system of some type, it must be an open or
vented type system to assure proper drainage.

Summary of Contents for WA7013B

Page 1: ...CONDITIONERS Models WA7013B WA7023A INSTALLATION INSTRUCTIONS Manual 2100 427 Supersedes File Volume III Tab 16 Date 01 01 03 Bard Manufacturing Company Bryan Ohio 43506 Since 1914 Moving ahead just a...

Page 2: ...ESP of Operation Electric Heat Only 15 Table 10 Pressure Table 16 Table 11 Optional Accessories 16 Getting Other Information and Publications 1 Wall Mount General Information 2 Air Conditioning Wall...

Page 3: ...ACCA Manual D Winter and Summer Air Conditioning and Equipment Selection For more information contact these publishers ACCA Air Conditioning Contractors of America 1712 New Hampshire Ave N W Washingt...

Page 4: ...7 1 1 8 1 0 0 8 2 1 0 9 7 1 2 0 0 6 0 3 7 8 1 0 3 0 3 2 0 0 1 6 1 4 0 3 1 4 3 2 6 3 0 0 6 5 2 MODEL NUMBER CONTROL MODULES CAPACITY 60 5 Ton VOLTS PHASE A 230 208 60 1 B 230 208 60 3 REVISIONS KW VEN...

Page 5: ...Manual 2100 427 Page 3 FIGURE 1 UNITDIMENSIONS MIS 1456...

Page 6: ...E 2 ELECTRICALSPECIFICATIONS l e d o M T I U C R I C E L G N I S T I U C R I C L A U D d e t a R s t l o V e s a h P o N d l e i F r e w o P s t i u c r i C 3 m u m i n i M t i u c r i C y t i c a p m...

Page 7: ...both conserve energy and prevent condensation or moisture damage These instructions and any instructions packaged with any separate equipment required to make up the entire air conditioning system sh...

Page 8: ...that a 1 inch clearance is used for ease of installation and maintaining the required clearance to combustible material The supply air opening would then be 32 x 12 See Figures 2 and 3 for details WAR...

Page 9: ...Manual 2100 427 Page 7 FIGURE 2 MOUNTINGINSTRUCTIONS MIS 1445...

Page 10: ...NING A minimum of 1 4 inch clearance must be maintained between the supply air duct and combustible materials This is required for the first 3 feet of ducting It is important to insure that the 1 4 in...

Page 11: ...2 X 6 S AND OR STRUCTURAL STEEL THIS STRUCTURAL MEMBER LOCATED TO MATCH STUD SPACING FOR REST OF WALL A SECOND MEMBER MAY BE REQUIRED FOR SOME WALLS RETURN DUCT OPENING SUPPLY DUCT OPENING FIGURE 4 W...

Page 12: ...Manual 2100 427 Page 10 FIGURE 6 COMMONWALLMOUNTINGINSTALLATIONS FREE AIR FLOW NO DUCT DUCTED SUPPLY RETURN AT UNIT FALSE WALL INSTALLATION CLOSETINSTALLATION MIS 550...

Page 13: ...d power circuits required for the various models with heaters The unit rating plate lists a Maximum Time Delay Relay Fuse or HACR type circuit breaker that is to be used with the equipment The correct...

Page 14: ...Manual 2100 427 Page 12 FIGURE 7 UNIT 24V TERMINAL BOARD MIS 1373B...

Page 15: ...nstallation connecting properly phased power leads to the same Fusite terminal should maintain proper rotation direction The direction of rotation of the compressor may be changed by reversing any two...

Page 16: ...ressure table can be found later in the manual covering all models It is imperative to match the correct pressure table to the unit by model number High Pressure Switch and Lockout Sequence If the hig...

Page 17: ...O 0 7 A W d e e p S h g i H l i o C y r D l i o C t e W 0 1 2 5 7 7 1 5 7 6 1 5 7 5 1 0 0 6 1 5 2 5 1 5 2 4 1 TABLE 8 RATED CFM AND ESP j Rated CFM ESP on High Speed tap with 14 x 28 return air filter...

Page 18: ...0 2 2 3 7 4 3 2 4 7 8 4 2 5 7 3 6 2 6 7 9 7 2 7 7 6 9 2 8 7 3 1 3 9 7 2 3 3 0 8 2 5 3 B D g e d 5 8 B W g e d 2 7 e d i S w o L e d i S h g i H 6 7 8 2 2 6 7 2 4 2 7 7 7 5 2 8 7 2 7 2 9 7 9 8 2 0 8 6...

Reviews: