background image

Manual   2100-427
Page  8

FIGURE  3

ELECTRIC HEAT CLEARANCE

SIDE SECTION VIEW OF SUPPLY AIR DUCT FOR WALL MOUNTED UNIT

SHOWING 1/4 INCH CLEARANCE TO COMBUSTIBLE SURFACES.

MIS-277

         WARNING

minimum

 of 1/4 inch clearance must be maintained between the

supply air duct and combustible materials.  This is required for the
first 3 feet of ducting.

It is important to insure that the 1/4 inch minimum spacing is
maintained at all points.

Failure to do this could result in overheating the combustible material
and may result in a fire causing damage, injury or death.

Summary of Contents for WA7013B

Page 1: ...CONDITIONERS Models WA7013B WA7023A INSTALLATION INSTRUCTIONS Manual 2100 427 Supersedes File Volume III Tab 16 Date 01 01 03 Bard Manufacturing Company Bryan Ohio 43506 Since 1914 Moving ahead just a...

Page 2: ...ESP of Operation Electric Heat Only 15 Table 10 Pressure Table 16 Table 11 Optional Accessories 16 Getting Other Information and Publications 1 Wall Mount General Information 2 Air Conditioning Wall...

Page 3: ...ACCA Manual D Winter and Summer Air Conditioning and Equipment Selection For more information contact these publishers ACCA Air Conditioning Contractors of America 1712 New Hampshire Ave N W Washingt...

Page 4: ...7 1 1 8 1 0 0 8 2 1 0 9 7 1 2 0 0 6 0 3 7 8 1 0 3 0 3 2 0 0 1 6 1 4 0 3 1 4 3 2 6 3 0 0 6 5 2 MODEL NUMBER CONTROL MODULES CAPACITY 60 5 Ton VOLTS PHASE A 230 208 60 1 B 230 208 60 3 REVISIONS KW VEN...

Page 5: ...Manual 2100 427 Page 3 FIGURE 1 UNITDIMENSIONS MIS 1456...

Page 6: ...E 2 ELECTRICALSPECIFICATIONS l e d o M T I U C R I C E L G N I S T I U C R I C L A U D d e t a R s t l o V e s a h P o N d l e i F r e w o P s t i u c r i C 3 m u m i n i M t i u c r i C y t i c a p m...

Page 7: ...both conserve energy and prevent condensation or moisture damage These instructions and any instructions packaged with any separate equipment required to make up the entire air conditioning system sh...

Page 8: ...that a 1 inch clearance is used for ease of installation and maintaining the required clearance to combustible material The supply air opening would then be 32 x 12 See Figures 2 and 3 for details WAR...

Page 9: ...Manual 2100 427 Page 7 FIGURE 2 MOUNTINGINSTRUCTIONS MIS 1445...

Page 10: ...NING A minimum of 1 4 inch clearance must be maintained between the supply air duct and combustible materials This is required for the first 3 feet of ducting It is important to insure that the 1 4 in...

Page 11: ...2 X 6 S AND OR STRUCTURAL STEEL THIS STRUCTURAL MEMBER LOCATED TO MATCH STUD SPACING FOR REST OF WALL A SECOND MEMBER MAY BE REQUIRED FOR SOME WALLS RETURN DUCT OPENING SUPPLY DUCT OPENING FIGURE 4 W...

Page 12: ...Manual 2100 427 Page 10 FIGURE 6 COMMONWALLMOUNTINGINSTALLATIONS FREE AIR FLOW NO DUCT DUCTED SUPPLY RETURN AT UNIT FALSE WALL INSTALLATION CLOSETINSTALLATION MIS 550...

Page 13: ...d power circuits required for the various models with heaters The unit rating plate lists a Maximum Time Delay Relay Fuse or HACR type circuit breaker that is to be used with the equipment The correct...

Page 14: ...Manual 2100 427 Page 12 FIGURE 7 UNIT 24V TERMINAL BOARD MIS 1373B...

Page 15: ...nstallation connecting properly phased power leads to the same Fusite terminal should maintain proper rotation direction The direction of rotation of the compressor may be changed by reversing any two...

Page 16: ...ressure table can be found later in the manual covering all models It is imperative to match the correct pressure table to the unit by model number High Pressure Switch and Lockout Sequence If the hig...

Page 17: ...O 0 7 A W d e e p S h g i H l i o C y r D l i o C t e W 0 1 2 5 7 7 1 5 7 6 1 5 7 5 1 0 0 6 1 5 2 5 1 5 2 4 1 TABLE 8 RATED CFM AND ESP j Rated CFM ESP on High Speed tap with 14 x 28 return air filter...

Page 18: ...0 2 2 3 7 4 3 2 4 7 8 4 2 5 7 3 6 2 6 7 9 7 2 7 7 6 9 2 8 7 3 1 3 9 7 2 3 3 0 8 2 5 3 B D g e d 5 8 B W g e d 2 7 e d i S w o L e d i S h g i H 6 7 8 2 2 6 7 2 4 2 7 7 7 5 2 8 7 2 7 2 9 7 9 8 2 0 8 6...

Reviews: