background image

Manual   2100-427
Page  14

ADJUSTMENTS

Adjustable Delay on Make and Delay on Break
Timer

The potentiometer is used to select Delay on Break time
from 30 seconds to 5 minutes.  Delay on Make (DOM)
timing on power-up and after power interruptions is
equal to 2 minutes plus 10% of Delay on Break (DOB)
setting:

0.5 minute (30 seconds) DOB = 123 second DOM
1.0 minute (60 seconds) DOB = 126 second DOM
2.0 minute (120 seconds) DOB = 132 second DOM
3.0 minute (180 seconds) DOB = 138 second DOM
4.0 minute (240 seconds) DOB = 144 second DOM
5.0 minute (300 seconds) DOB = 150 second DOM

During routine operation of the unit with no power
interruptions the compressor will operate on demand
with no delay.

Typical Settings for Dual Unit Installation:

Unit 1:  DOB set at 2 minutes, and DOM is 132 seconds

Unit 2:  DOB set at 4 minutes, and DOM is 144 seconds

PHASE MONITOR

All units with three phase scroll compressors are
equipped with a 3 phase line monitor to prevent
compressor damage due to phase reversal.

The phase monitor in this unit is equipped with two
LEDs.  If the Y signal is present at the phase monitor
and phases are correct the green LED will light.

If phases are reversed, the red fault LED will be lit and
compressor operation is inhibited.

If a fault condition occurs, reverse two of the supply
leads to the unit.  Do not reverse any of the unit factory
wires as damage may occur.

PRESSURE SERVICE PORTS

High and low pressure service ports are installed on all
units so that the system operating pressures can be
observed.  A pressure table can be found later in the
manual covering all models. It is imperative to match
the correct pressure table to the unit by model number.

High Pressure Switch and Lockout Sequence

If the high pressure switch opens, the compressor
contactor will de-energize immediately.  The lockout
timer will go into a soft lockout and stay in soft lockout
until the high pressure switch closes and the delay on
break time has expired.   If the high pressure switch
opens again in this same operating cycle the unit will
go into manual lockout condition and the alarm relay
circuit will energize.   Recycling the wall thermostat
resets the manual lockout.

Low Pressure Switch, Bypass, and Lockout
Sequence

If the low pressure switch opens for more than 120
seconds, the compressor contactor will de-energize and
go into a soft lockout.   Regardless the state of the low
pressure switch, the contactor will reenergize after the
delay on make time delay has expired.  If the low
pressure switch remains open, or opens again for longer
than 120 seconds the unit will go into manual lockout
condition and the alarm relay circuit will energize.
Recycling the wall thermostat resets the manual
lockout.

Alarm Relay Output

Alarm terminal is output connection for applications
where alarm relay is employed.  This terminal is
powered whenever compressor is locked out due to
HPC or LPC sequences as described.

NOTE: Both high and low pressure switch controls are

inherently automatic reset devices.  The high
pressure switch and low pressure switch cut out
and cut in settings are fixed by specific air
conditioner or heat pump unit model.  The
lockout features, both soft and manual, are a
function of the Compressor Control Module.

Summary of Contents for WA7013B

Page 1: ...CONDITIONERS Models WA7013B WA7023A INSTALLATION INSTRUCTIONS Manual 2100 427 Supersedes File Volume III Tab 16 Date 01 01 03 Bard Manufacturing Company Bryan Ohio 43506 Since 1914 Moving ahead just a...

Page 2: ...ESP of Operation Electric Heat Only 15 Table 10 Pressure Table 16 Table 11 Optional Accessories 16 Getting Other Information and Publications 1 Wall Mount General Information 2 Air Conditioning Wall...

Page 3: ...ACCA Manual D Winter and Summer Air Conditioning and Equipment Selection For more information contact these publishers ACCA Air Conditioning Contractors of America 1712 New Hampshire Ave N W Washingt...

Page 4: ...7 1 1 8 1 0 0 8 2 1 0 9 7 1 2 0 0 6 0 3 7 8 1 0 3 0 3 2 0 0 1 6 1 4 0 3 1 4 3 2 6 3 0 0 6 5 2 MODEL NUMBER CONTROL MODULES CAPACITY 60 5 Ton VOLTS PHASE A 230 208 60 1 B 230 208 60 3 REVISIONS KW VEN...

Page 5: ...Manual 2100 427 Page 3 FIGURE 1 UNITDIMENSIONS MIS 1456...

Page 6: ...E 2 ELECTRICALSPECIFICATIONS l e d o M T I U C R I C E L G N I S T I U C R I C L A U D d e t a R s t l o V e s a h P o N d l e i F r e w o P s t i u c r i C 3 m u m i n i M t i u c r i C y t i c a p m...

Page 7: ...both conserve energy and prevent condensation or moisture damage These instructions and any instructions packaged with any separate equipment required to make up the entire air conditioning system sh...

Page 8: ...that a 1 inch clearance is used for ease of installation and maintaining the required clearance to combustible material The supply air opening would then be 32 x 12 See Figures 2 and 3 for details WAR...

Page 9: ...Manual 2100 427 Page 7 FIGURE 2 MOUNTINGINSTRUCTIONS MIS 1445...

Page 10: ...NING A minimum of 1 4 inch clearance must be maintained between the supply air duct and combustible materials This is required for the first 3 feet of ducting It is important to insure that the 1 4 in...

Page 11: ...2 X 6 S AND OR STRUCTURAL STEEL THIS STRUCTURAL MEMBER LOCATED TO MATCH STUD SPACING FOR REST OF WALL A SECOND MEMBER MAY BE REQUIRED FOR SOME WALLS RETURN DUCT OPENING SUPPLY DUCT OPENING FIGURE 4 W...

Page 12: ...Manual 2100 427 Page 10 FIGURE 6 COMMONWALLMOUNTINGINSTALLATIONS FREE AIR FLOW NO DUCT DUCTED SUPPLY RETURN AT UNIT FALSE WALL INSTALLATION CLOSETINSTALLATION MIS 550...

Page 13: ...d power circuits required for the various models with heaters The unit rating plate lists a Maximum Time Delay Relay Fuse or HACR type circuit breaker that is to be used with the equipment The correct...

Page 14: ...Manual 2100 427 Page 12 FIGURE 7 UNIT 24V TERMINAL BOARD MIS 1373B...

Page 15: ...nstallation connecting properly phased power leads to the same Fusite terminal should maintain proper rotation direction The direction of rotation of the compressor may be changed by reversing any two...

Page 16: ...ressure table can be found later in the manual covering all models It is imperative to match the correct pressure table to the unit by model number High Pressure Switch and Lockout Sequence If the hig...

Page 17: ...O 0 7 A W d e e p S h g i H l i o C y r D l i o C t e W 0 1 2 5 7 7 1 5 7 6 1 5 7 5 1 0 0 6 1 5 2 5 1 5 2 4 1 TABLE 8 RATED CFM AND ESP j Rated CFM ESP on High Speed tap with 14 x 28 return air filter...

Page 18: ...0 2 2 3 7 4 3 2 4 7 8 4 2 5 7 3 6 2 6 7 9 7 2 7 7 6 9 2 8 7 3 1 3 9 7 2 3 3 0 8 2 5 3 B D g e d 5 8 B W g e d 2 7 e d i S w o L e d i S h g i H 6 7 8 2 2 6 7 2 4 2 7 7 7 5 2 8 7 2 7 2 9 7 9 8 2 0 8 6...

Reviews: