background image

Manual   2100-427
Page    15

The suction line temperatures in table above are based
upon 80° F dry bulb / 67° F wet bulb (50% R.H.)
temperature and rated airflow across the evaporator
during cooling cycle.

REMOVAL OF FAN SHROUD

1. Disconnect all power to the unit.

2. Remove the screws holding both grilles, one on each

side of unit, and remove grilles.

3. Remove screws holding fan shroud to condenser

and bottom.  Nine (9) screws.

4. Unwire condenser fan motor.

TROUBLESHOOTING

5. Slide complete motor, fan blade, and shroud

assembly out the left side of the unit.

6. Service motor/fan as needed.

7. Reverse steps to reinstall.

REFRIGERANT CHARGE

The correct system R-22 charge is shown on the unit
rating plate. Optimum unit performance will occur with
a refrigerant charge resulting in a suction line
temperature (6” from compressor) as shown in Table 7.

FIGURE  8

TABLE  6

INDOOR BLOWER PERFORMANCE

CFM 

@

 230V

.

P

.

S

.

E

H

n

I

2

O

0

7

A

W

d

e

e

p

S

h

g

i

H

li

o

C

y

r

D

li

o

C

t

e

W

0

.

1

.

2

.

5

7

7

1

5

7

6

1

5

7

5

1

0

0

6

1

5

2

5

1

5

2

4

1

TABLE  8

RATED CFM AND ESP

j

Rated CFM & ESP on High Speed tap with
14 x 28 return air filter grille

l

e

d

o

M

d

e

t

a

R

M

F

C

d

e

t

a

R

P

S

E

d

e

d

n

e

m

m

o

c

e

R

e

g

n

a

R

w

o

l

f

r

i

A

0

7

A

W

5

2

4

1

0

2

.

0

5

2

4

1

-

5

7

7

1

1

TABLE  9

MAXIMUM ESP OF OPERATION

ELECTRIC HEAT ONLY

Values shown are for units equipped with
standard 1” throwaway filters or 1” washable
filters.  Derate ESP by .15 for 2” pleated filters.

S

L

E

D

O

M

P

S

E

W

0

7

A

0

1

A

9

0

B

3

.

3

.

TABLE  7

REFRIGERANT CHARGE

l

e

d

o

M

w

o

l

f

r

i

A

D

O

5

9

e

r

u

t

a

r

e

p

m

e

T

D

O

2

8

e

r

u

t

a

r

e

p

m

e

T

0

7

A

W

0

0

7

1

0

6

-

8

5

8

5

-

6

5

TABLE  5

l

e

d

o

M

n

o

i

s

n

e

m

i

D

A

0

7

A

W

5

2

.

1

FAN BLADE SETTING DIMENSIONS

Shown in Figure 10 is the correct fan blade setting
dimension for proper air delivery across the outdoor
coil.

Any service work requiring removal or adjustment in
the fan and/or motor area will require that the
dimensions below be checked and blade adjusted in or
out on the motor shaft accordingly.

Summary of Contents for WA7013B

Page 1: ...CONDITIONERS Models WA7013B WA7023A INSTALLATION INSTRUCTIONS Manual 2100 427 Supersedes File Volume III Tab 16 Date 01 01 03 Bard Manufacturing Company Bryan Ohio 43506 Since 1914 Moving ahead just a...

Page 2: ...ESP of Operation Electric Heat Only 15 Table 10 Pressure Table 16 Table 11 Optional Accessories 16 Getting Other Information and Publications 1 Wall Mount General Information 2 Air Conditioning Wall...

Page 3: ...ACCA Manual D Winter and Summer Air Conditioning and Equipment Selection For more information contact these publishers ACCA Air Conditioning Contractors of America 1712 New Hampshire Ave N W Washingt...

Page 4: ...7 1 1 8 1 0 0 8 2 1 0 9 7 1 2 0 0 6 0 3 7 8 1 0 3 0 3 2 0 0 1 6 1 4 0 3 1 4 3 2 6 3 0 0 6 5 2 MODEL NUMBER CONTROL MODULES CAPACITY 60 5 Ton VOLTS PHASE A 230 208 60 1 B 230 208 60 3 REVISIONS KW VEN...

Page 5: ...Manual 2100 427 Page 3 FIGURE 1 UNITDIMENSIONS MIS 1456...

Page 6: ...E 2 ELECTRICALSPECIFICATIONS l e d o M T I U C R I C E L G N I S T I U C R I C L A U D d e t a R s t l o V e s a h P o N d l e i F r e w o P s t i u c r i C 3 m u m i n i M t i u c r i C y t i c a p m...

Page 7: ...both conserve energy and prevent condensation or moisture damage These instructions and any instructions packaged with any separate equipment required to make up the entire air conditioning system sh...

Page 8: ...that a 1 inch clearance is used for ease of installation and maintaining the required clearance to combustible material The supply air opening would then be 32 x 12 See Figures 2 and 3 for details WAR...

Page 9: ...Manual 2100 427 Page 7 FIGURE 2 MOUNTINGINSTRUCTIONS MIS 1445...

Page 10: ...NING A minimum of 1 4 inch clearance must be maintained between the supply air duct and combustible materials This is required for the first 3 feet of ducting It is important to insure that the 1 4 in...

Page 11: ...2 X 6 S AND OR STRUCTURAL STEEL THIS STRUCTURAL MEMBER LOCATED TO MATCH STUD SPACING FOR REST OF WALL A SECOND MEMBER MAY BE REQUIRED FOR SOME WALLS RETURN DUCT OPENING SUPPLY DUCT OPENING FIGURE 4 W...

Page 12: ...Manual 2100 427 Page 10 FIGURE 6 COMMONWALLMOUNTINGINSTALLATIONS FREE AIR FLOW NO DUCT DUCTED SUPPLY RETURN AT UNIT FALSE WALL INSTALLATION CLOSETINSTALLATION MIS 550...

Page 13: ...d power circuits required for the various models with heaters The unit rating plate lists a Maximum Time Delay Relay Fuse or HACR type circuit breaker that is to be used with the equipment The correct...

Page 14: ...Manual 2100 427 Page 12 FIGURE 7 UNIT 24V TERMINAL BOARD MIS 1373B...

Page 15: ...nstallation connecting properly phased power leads to the same Fusite terminal should maintain proper rotation direction The direction of rotation of the compressor may be changed by reversing any two...

Page 16: ...ressure table can be found later in the manual covering all models It is imperative to match the correct pressure table to the unit by model number High Pressure Switch and Lockout Sequence If the hig...

Page 17: ...O 0 7 A W d e e p S h g i H l i o C y r D l i o C t e W 0 1 2 5 7 7 1 5 7 6 1 5 7 5 1 0 0 6 1 5 2 5 1 5 2 4 1 TABLE 8 RATED CFM AND ESP j Rated CFM ESP on High Speed tap with 14 x 28 return air filter...

Page 18: ...0 2 2 3 7 4 3 2 4 7 8 4 2 5 7 3 6 2 6 7 9 7 2 7 7 6 9 2 8 7 3 1 3 9 7 2 3 3 0 8 2 5 3 B D g e d 5 8 B W g e d 2 7 e d i S w o L e d i S h g i H 6 7 8 2 2 6 7 2 4 2 7 7 7 5 2 8 7 2 7 2 9 7 9 8 2 0 8 6...

Reviews: