background image

Manual

2100-526E

Page

21 of 24

TROUBLESHOOTING  GE  ECM

 MOTORS CONT’D.

Motor

Motor OK when

R > 100k ohm

ECM 2.0

Only remove

Hex Head Bolts

Connector Orientation

Between 4 and 8 o'clock

Drip Loop

Back of

Control

Figure 5

Winding Test

Figure 4

Note:              
Use the shorter 
bolts and 
alignment pin 
supplied when 
replacing an 
ECM 2.0 
control.

Figure 3

ECM 
2.3/2.5

Power Connector
(5-pin)

Control Connector
(16-pin)

Hex-head Screws

Motor Connector
(3-pin)

Motor Connector
(3-pin)

Control Disassembly

Drip Loop

Push until

Latch Seats
Over Ramp

From Motor

Circuit

Board

Replacing ECM Control Module

To replace the control module for the GE variable-speed indoor blower
motor you need to take the following steps:

1. You MUST have the correct replacement module.  The controls are

factory programmed for specific operating modes.  Even though they look
alike, different modules may have completely different functionality.

USING THE WRONG CONTROL MODULE VOIDS ALL PRODUCT
WARRANTIES AND MAY PRODUCE UNEXPECTED RESULTS.

2. Begin by removing AC power from the furnace or air handler being

serviced.  

DO NOT WORK ON THE MOTOR WITH AC POWER

APPLIED.  

To avoid electric shock from the motor’s capacitors, disconnect

power and wait at least 5 minutes before opening motor.

3. It is usually not necessary to remove the motor from the blower

assembly.  However, it is recommended that the whole blower assembly, with
the motor, be removed from the furnace/air handler.  (Follow the
manufacturer’s procedures).  Unplug the two cable connectors to the motor.
There are latches on each connector.  

DO NOT PULL ON THE WIRES.

The plugs remove easily when properly released.

4. Locate the two standard ¼" hex head bolts at the rear of the control

housing (at the back end of the control opposite the shaft end).  

Refer to

Figure 9.  

Remove these two bolts from the motor and control

assembly while holding the motor in a way that will prevent the motor
or control from falling when the bolts are removed.  If an ECM2.0
control is being replaced (recognized by an aluminum casting rather
that a deep-drawn black steel can housing the electronics), remove
only the hex-head bolts.  

DO NOT REMOVE THE TORX-HEAD

SCREWS.

5. The control module is now free of mechanical attachment to the

motor endshield but is still connected by a plug and three wires inside the
control.  Carefully rotate the control to gain access to the plug at the
control end of the wires.  With thumb and forefinger, reach the latch
holding the plug to the control and release it by squeezing the latch tab
and the opposite side of the connector plug and gently pulling the plug out
of the connector socket in the control.  

DO NOT PULL ON THE

WIRES.  GRIP THE PLUG ONLY.

6. The control module is now completely detached from the motor.

Verify with a standard ohmmeter that the resistance from each motor lead
(in the motor plug just removed) to the motor shell is >100K ohms.  

Refer

to Figure 10.  

(Measure to unpainted motor end plate.)  If any motor

lead fails this test, do not proceed to install the control module.  

THE

MOTOR IS DEFECTIVE AND MUST BE REPLACED.

  Installing

the new control module will cause it to fail also.

7. Verify that the replacement control is correct for your

application.  Refer to the manufacturer's authorized replacement list.

USING THE WRONG CONTROL WILL RESULT IN
IMPROPER OR NO BLOWER OPERATION.

  Orient the control

module so that the 3-wire motor plug can be inserted into the socket in
the control.  Carefully insert the plug and press it into the socket until
it latches.  

A SLIGHT CLICK WILL BE HEARD WHEN

PROPERLY INSERTED.

  Finish installing the replacement control per

one of the three following paragraphs, 8a, 8b or 8c.

8a. 

IF REPLACING AN ECM 2.0 CONTROL

 (control in cast

aluminum can with air vents on the back of the can) 

WITH AN ECM 2.3

CONTROL

 (control containing black potting for water protection in

black deep-drawn steel case with no vents in the bottom of the can), locate
the two through-bolts and plastic tab that are packed with the replacement
control.  Insert the plastic tab into the slot at the perimeter of the open end
of the can so that the pin is located on the inside of the perimeter of the
can.  Rotate the can so that the tab inserts into the tab locater hole in the
endshield of the motor.  Using the two through-bolts provided with the
replacement control, reattach the can to the motor.

THE TWO THROUGH-BOLTS PROVIDED WITH THE
REPLACEMENT ECM 2.3 CONTROL ARE SHORTER THAN THE
BOLTS ORIGINALLY REMOVED FROM THE ECM 2.0
CONTROL AND MUST BE USED IF SECURE ATTACHMENT OF
THE CONTROL TO THE MOTOR IS TO BE ACHIEVED.

DO NOT OVERTIGHTEN THE BOLTS.

8b. 

IF REPLACING AN ECM 2.3 CONTROL

 

WITH AN ECM 2.3

CONTROL

, the plastic tab and shorter through-bolts are not needed.  The

control can be oriented in two positions 180° apart.  

MAKE SURE THE

ORIENTATION YOU SELECT FOR REPLACING THE CONTROL
ASSURES THE CONTROL'S CABLE CONNECTORS WILL BE
LOCATED DOWNWARD IN THE APPLICATION SO THAT
WATER CANNOT RUN DOWN THE CABLES AND INTO THE
CONTROL.

  Simply orient the new control to the motor's endshield,

insert bolts, and tighten.  

DO NOT OVERTIGHTEN THE BOLTS.

8c. 

IF REPLACING AN ECM 2.0 CONTROL WITH AN ECM

2.0 CONTROL 

(It is recommended that ECM 2.3 controls be used for

all replacements), 

the new control must be attached to the motor using

through bolts identical to those removed with the original control.  

DO

NOT OVERTIGHTEN THE BOLTS.

9. Reinstall the blower/motor assembly into the HVAC equipment.

Follow the manufacturer's suggested procedures.

10. Plug the 16-pin control plug into the motor.  The plug is keyed.

Make sure the connector is properly seated and latched.

11. Plug the 5-pin power connector into the motor.  Even though the

plug is keyed, 

OBSERVE THE PROPER ORIENTATION.  DO NOT

FORCE THE CONNECTOR.

  It plugs in very easily when properly

oriented.  

REVERSING THIS PLUG WILL CAUSE IMMEDIATE

FAILURE OF THE CONTROL MODULE.

12. Final installation check.  Make sure the motor is installed as follows:

a. Unit is as far INTO the blower housing as possible.
b. Belly bands are not on the control module or covering vent holes.
c. Motor connectors should be oriented between the 4 o’clock and 8

o’clock positions when the blower is positioned in its final
location and orientation.

d. Add a drip loop to the cables so that water cannot enter the motor

by draining down the cables.  

Refer to Figure 11.

The installation is now complete.  Reapply the AC power to the
HVAC equipment and verify that the new motor control module is
working properly.  Follow the manufacturer's procedures for
disposition of the old control module.

Figure 10

Figure 9

Figure 11

Summary of Contents for WA3S3

Page 1: ...III Tab 16 Date 07 16 12 Bard Manufacturing Company Inc Bryan Ohio 43506 Since 1914 Moving ahead just as planned WALL MOUNTED PACKAGED AIR CONDITIONER INSTALLATION INSTRUCTIONS Models WA3S3 WL3S2 WA4S...

Page 2: ...Up General 13 Topping Off System Charge 13 Safety Practices 13 Important Installer Note 14 Crankcase Heaters 14 High Low Pressure Switch 14 Three Phase Scroll Compressor Start Up Information 14 Servi...

Page 3: ...Manual N Summer Air Conditioning Low Pressure Low Velocity ACCA Manual D or Duct System Design for Winter Manual Q and Summer Air Conditioning FOR MORE INFORMATION CONTACT THESE PUBLISHERS ACCA Air C...

Page 4: ...6 0 0 5 1 1 2 7 5 9 1 1 5 y l n o s t i n u V 8 0 2 0 3 2 n i e l b a l i a v a e r a s r e t a e h c i r t c e l e e s e h T 1 y l n o s t i n u V 0 8 4 n i e l b a l i a v a e r a s r e t a e h c i...

Page 5: ...B S 3 L A W 5 7 0 2 4 2 3 4 2 2 5 7 8 4 8 8 8 9 8 8 9 2 8 8 5 1 8 8 9 2 8 8 3 4 0 1 9 1 6 6 1 3 0 0 0 3 8 6 2 3 4 9 6 2 9 6 4 3 3 4 2 3 7 3 3 8 8 2 4 8 8 3 2 0 0 0 1 4 4 1 0 0 6 1 8 8 1 S 4 L A W 5 7...

Page 6: ...2 5 2 5 6 2 5 4 5 4 5 4 0 3 0 6 0 6 0 3 8 8 8 0 1 6 6 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 S 4 L A W Z 0 B 6 0 B 9 0 B 5 1 B 3 8 0 2 0 3 2 1 1 1 1 8 2 9 2 8 3 6 5 0 4 0 4 0 4 0 6 0 1 0 1 8 6 0 1 0 1 0 1 0...

Page 7: ...ons thereof not in the conditioned space should be properly insulated in order to both conserve energy and prevent condensation or moisture damage Refer to Table 10 for maximum static pressure availab...

Page 8: ...nting rigidity the return air and supply air frames or collars can be drilled and screwed or welded to the structural wall itself depending upon wall construction Be sure to observe required clearance...

Page 9: ...commended that a bead of silicone caulking be placed behind the side mounting flanges and under the top flashing at the time of installation B 16 16 16 16 16 1 7 8 6 1 2 6 1 2 2 1 8 7 8 1 3 4 Typ 4 Ty...

Page 10: ...AIR MIS 548 A SIDE VIEW I A C K E 1 000 B 1 000 SUPPLY DUCT OVER FRAME INTERIOR FINISHED WALL ALL AROUND DUCT FRAMING MATERIAL EXTERIOR FINISH WALL OPENING FOR ACTUAL DIMENSIONS 2 x 4 S 2 x 6 S OR ST...

Page 11: ...WALL OPENING W GRILLE SUPPLY DUCT MAYBE LOCATED IN AN ATTIC OR BELOW CEILING RAFTERS AS SHOWN CEILING RAIN RETURN AIR SLEEVE WALL SUPPLY AIR DUCT RAFTERS RAFTERS RETURN AIR OPENING W GRILLE RAIN FALSE...

Page 12: ...t s 3 c i n o r t c e l E e l b a m m a r g o r P n o N e l b a m m a r g o r P l a n o i t n e v n o C r o P H r e v o e g n a h c l a u n a M r o o t u A 8 5 0 3 0 4 8 1 5 1 1 D 0 2 2 5 H T t a e H...

Page 13: ...rigerant composition during multiple leaks and recharges R 410A refrigerant is close to being an azeotropic blend it behaves like a pure compound or single component refrigerant The remaining refriger...

Page 14: ...ation must be made any time a compressor is change or rewired If improper rotation is corrected at this time there will be no negative impact on the durability of the compressor However reverse operat...

Page 15: ...ng When the delay on make is complete and the high pressure and low pressure switches are closed the compressor contactor is energized Upon shutdown the delay or break timer starts and prevents restar...

Page 16: ...o that the system operating pressures can be observed Pressure tables can be found later in the manual covering all models It is imperative to match the correct pressure table to the unit by model num...

Page 17: ...click as the solenoid returns to its original position 3 If clicks can t be heard shut off power and remove the control circuit molded plug from the compressor and measure the solenoid coil resistanc...

Page 18: ...testing with this refrigerant charge quantity The following pressure tables show nominal pressures for the units Since many installation specific situations can affect the pressure readings this info...

Page 19: ...1 6 1 2 9 3 1 7 3 2 0 4 1 8 5 2 1 4 1 9 7 2 2 4 1 0 0 3 3 4 1 1 2 3 6 4 1 6 4 3 8 4 1 0 7 3 1 5 1 5 9 3 3 5 1 9 1 4 5 5 1 7 4 4 7 5 1 4 7 4 8 5 1 2 0 5 0 6 1 9 2 5 G N I L O O C Y T I C A P A C W O L...

Page 20: ...it s air noise cabinet duct or motor noise interview customer if necessary Air noise High static creating high blower speed Is airflow set properly Does removing filter cause blower to slow down Check...

Page 21: ...ication Refer to the manufacturer s authorized replacement list USING THE WRONG CONTROL WILL RESULT IN IMPROPER OR NO BLOWER OPERATION Orient the control module so that the 3 wire motor plug can be in...

Page 22: ...Heat signal from thermostat TABLE 9 INDOOR BLOWER PERFORMANCE 1 1 1 1 1 l e d o M P S E d e t a R P S E X A M 2 2 2 2 2 s u o u n i t n o C M F C 3 3 3 3 3 t s 1 d e t a R M F C e g a t S 4 4 4 4 4 d...

Page 23: ...e g a k c a P r e t a e H X 6 0 B S 3 A W H E e g a k c a P r e t a e H X 6 0 B S 5 A W H E e g a k c a P r e t a e H X X 9 0 B S 5 A W H E e g a k c a P r e t a e H X X X 5 1 B S 5 A W H E e g a k c...

Page 24: ...E e g a k c a P r e t a e H X L 6 0 B S 3 A W H E e g a k c a P r e t a e H X L 6 0 B S 5 A W H E e g a k c a P r e t a e H X X L 9 0 B S 5 A W H E e g a k c a P r e t a e H X X X L 5 1 B S 5 A W H E...

Reviews: