background image

Manual  2100-200
Page   5

SHIPPING DAMAGE

Upon receipt of equipment, the carton should be checked
for external signs of shipping damage. If damage is
found, the receiving party must contact the last carrier
immediately, preferably in writing, requesting inspection
by the carrier’s agent.

GENERAL

The equipment covered in this manual is to be installed
by trained, experienced service and installation
technicians.

The refrigerant system is completely assembled and
charged. All internal wiring is complete.

The unit is designed for use with or without duct work.
Flanges are provided for attaching the supply and return
ducts.

These instructions explain the recommended method to
install the air cooled self-contained unit and the electrical
wiring connections to the unit.

These instructions and any instructions packaged with
any separate equipment required to make up the entire air
conditioning system should be carefully read before
beginning the installation. Note particularly “Starting
Procedure” and any tags and/or labels attached to the
equipment.

While these instructions are intended as a general
recommended guide, they do not supersede any national
and/or local codes in any way. Authorities having
jurisdiction should be consulted before the installation is
made. See Page 1 for information on codes and
standards.

Size of unit for a proposed installation should be based
on heat loss calculation made according to methods of
Air Conditioning Contractors of America (ACCA). The
air duct should be installed in accordance with the
Standards of the National Fire Protection Association for
the Installation of Air Conditioning and Ventilating
Systems of Other Than Residence Type, NFPA No. 90A,
and Residence Type Warm Air Heating and Air
Conditioning Systems, NFPA No. 90B. Where local
regulations are at a variance with instructions, installer
should adhere to local codes.

DUCT WORK

All duct work, supply and return, must be properly sized
for the design air flow requirement of the equipment. Air
Conditioning Contractors of America (ACCA) is an
excellent guide to proper sizing. All duct work or
portions thereof not in the conditioned space should be
properly insulated in order to both conserve energy and
prevent condensation or moisture damage.

Any grille that meets the 5/8 inch louver criteria may be
used.  It is recommended that Bard Return Air Grille Kit
RG-2 through RG-5 or RFG-2 through RFG-5 be
installed when no return duct is used.  Contact distributor
or factory for ordering information.  If using a return air
filter grille, filters must be of sufficient size to allow a
maximum velocity of 400 fpm.

NOTE: If no return air duct is used, applicable

installation codes may limit this cabinet to
installation only in a single story structure.

FILTERS

A 1 inch throw away filter is suppled with each unit.  The
filter slides into position making it easy to service.  This
filter can be serviced from the outside by removing the
service door.  A 1 inch washable filter and a 2 inch
pleated filter are also available as optional accessories.
The internal filter brackets are adjustable to accommodate
the 2 inch filter by loosening 2 screws in each bracket
assembly and sliding the brackets apart to the required
width and retightening the 4 screws.

Refer to Table 10 for maximum static pressure available
for duct design.

Design the duct work according to methods given by the
Air Conditioning Contractors of America (ACCA). When
duct runs through unheated spaces, it should be insulated
with a minimum of 1 inch of insulation. Use insulation
with a vapor barrier on the outside of the insulation.
Flexible joints should be used to connect the duct work to
the equipment in order to keep the noise transmission to a
minimum.

A 1/4 inch clearance to combustible material for the first
3 feet of duct attached to the outlet air frame is required.
See Wall Mounting Instructions and Figures 3 and 4 for
further details.

Ducts through the walls must be insulated and all joints
taped or sealed to prevent air or moisture entering the
wall cavity.

        CAUTION

Some installations may not require any return
air duct.  A metallic return air grille is required
with installations not requiring a return air duct.
The spacing between louvers on the grille shall
not be larger than 5/8 inches.

Summary of Contents for WA181

Page 1: ...0 200J File Volume III Tab 16 Date 04 19 99 Bard Manufacturing Company Bryan Ohio 43506 Since 1914 Moving ahead just as planned Copyright 1999 MIS 656 Models WA181 WA241 Wall Mounted Packaged Air Cond...

Page 2: ...Blade Setting 14 Tables Table 1 Electric Heat Table 2 Table 2 Electrica Specifications 4 Table 3 Thermostat Wire Size 7 Table 4 Wall Thermostat and Subbase Combinations 7 Table 5 Fan Blade Dimensions...

Page 3: ...al D Winter and Summer Air Conditioning and Equipment Selection For more information contact these publishers ACCA Air Conditioning Contractors of America 1712 New Hampshire Avenue NW Washington DC 20...

Page 4: ...ROL MODULES COIL OPTIONS X Standard 1 Phenolic Coated Evaporator 2 Phenolic Coated Condenser 3 Phenolic Coated Evaporator and Condenser OUTLET OPTIONS X Front Standard T Top on WA30 and WA36 Models NO...

Page 5: ...F G I J K L M N O P Q R S T A B C B 8 1 A W 4 2 A W 0 0 3 3 3 5 2 1 7 1 3 6 5 0 7 8 8 7 8 8 9 1 8 8 1 1 8 8 9 1 0 0 5 3 0 5 8 1 5 7 5 2 6 5 0 2 5 7 6 2 6 0 8 2 5 2 9 2 0 0 7 2 3 6 2 3 1 4 3 6 0 2 2 5...

Page 6: ...0 6 2 1 0 1 0 1 8 6 2 1 0 1 0 1 0 1 0 1 Z 0 B 0 0 B 1 4 2 A W 6 0 B 3 8 0 2 0 3 2 1 1 3 1 2 2 5 1 5 2 4 1 0 1 2 1 0 1 S Q R Maximum size of the time delay fuse or HACR type circuit breaker for protec...

Page 7: ...is an excellent guide to proper sizing All duct work or portions thereof not in the conditioned space should be properly insulated in order to both conserve energy and prevent condensation or moistur...

Page 8: ...of Energy Energyguide Fact Sheets is based upon the fresh air blank off plate in place and is recommended for maximum energy efficiency The blank off plate is available upon request from the factory a...

Page 9: ...b b u S s e r u t a e F e t a n i m o d e r P 2 0 0 3 0 4 8 1 1 1 3 F 7 8 T 3 0 0 4 0 4 8 0 2 2 1 A 9 3 5 Q l o o c e g a t s 1 t a e h e g a t s 1 n o o t u a n a F l o o c f f o t a e h m e t s y S...

Page 10: ...100 200 Page 8 FIGURE 3 MOUNTING INSTRUCTIONS MIS 353 NOTE It is recommended that a bead of silicone caulking be placed behind the side mounting flanges and under the top flashing at the time of insta...

Page 11: ...Page 9 FIGURE 4 WALL MOUNTING INSTRUCTIONS MIS 549 FIGURE 5 WALL MOUNTING INSTRUCTIONS MIS 548 SEE FIGURE 3 MOUNTING INSTRUCTIONS SEE UNIT DIMENSIONS FIGURE 1 FOR ACTUAL DIMENSIONS SEE FIGURE 1 FOR D...

Page 12: ...Manual 2100 200 Page 10 MIS 550 FIGURE 6 COMMON WALL MOUNTING INSTALLATIONS...

Page 13: ...Manual 2100 200 Page 11 FIGURE 7 LOW VOLTAGE WIRING MIS 1373...

Page 14: ...delay On a call for heating circuit R W1 make at the thermostat pulling in heat contact for the strip heat and blower operation On a call for second stage heat R W2 makes bringing on second heat cont...

Page 15: ...tables can be found later in the manual covering all models It is imperative to match the correct pressure table to the unit by model number ADJUSTMENTS Adjustable Delay on Make and Delay on Break Ti...

Page 16: ...eps to reinstall REFRIGERANT CHARGE The correct system R 22 charge is shown on the unit rating plate Optimum unit performance will occur with a refrigerant charge resulting in a suction line temperatu...

Page 17: ...u t e R e r u t a r e p m e T e r u s s e r P 5 7 0 8 5 8 0 9 5 9 0 0 1 5 0 1 0 1 1 5 1 1 1 8 1 A W B D g e d 5 7 B W g e d 2 6 e d i S w o L e d i S h g i H 1 7 4 9 1 3 7 8 0 2 5 7 3 2 2 7 7 8 3 2 9...

Page 18: ...F c i r t e m o r a B X X X 2 D A F M r e p m a D r i A h s e r F d e z i r o t o M X X X 2 V R C t s u a h x E h t i w r o t a l i t n e V l a i c r e m m o C X X X 2 M F I E t s u a h x E h t i w r...

Reviews: