background image

Manual  2100-200
Page   13

Low Pressure Switch, Bypass, and Lockout
Sequence

If the low pressure switch opens for more than 120
seconds, the compressor contactor will de-energize and
go into a soft lockout.   Regardless the state of the low
pressure switch, the contactor will reenergize after the
delay on make time delay has expired.  If the low pressure
switch remains open, or opens again for longer than 120
seconds the unit will go into manual lockout condition
and the alarm relay circuit will energize.  Recycling the
wall thermostat resets the manual lockout.

Alarm Relay Output

Alarm terminal is output connection for applications
where alarm relay is employed.  This terminal is powered
whenever compressor is locked out due to HPC or LPC
sequences as described.

NOTE: Both high and low pressure switch controls are

inherently automatic reset devices.  The high
pressure switch and low pressure switch cut out
and cut in settings are fixed by specific air
conditioner or heat pump unit model.  The
lockout features, both soft and manual, are a
function of the Compressor Control Module.

PRESSURE SERVICE PORTS

High and low pressure service ports are installed on all
units so that the system operating pressures can be
observed. Pressure tables can be found later in the manual
covering all models. It is imperative to match the correct
pressure table to the unit by model number.

ADJUSTMENTS

Adjustable Delay on Make and Delay on Break
Timer

The potentiometer is used to select Delay on Break time
from 30 seconds to 5 minutes.  Delay on Make (DOM)
timing on power-up and after power interruptions is equal
to 2 minutes plus 10% of Delay on Break (DOB) setting:

0.5 minute (30 seconds)

DOB =123 second DOM

1.0 minute (60 seconds)

DOB =126 second DOM

2.0 minute (120 seconds) DOB =132 second DOM
3.0 minute (180 seconds) DOB =138 second DOM
4.0 minute (240 seconds) DOB =144 second DOM
5.0 minute (300 seconds) DOB =150 second DOM

During routine operation of the unit with now power
interruptions the compressor will operate on demand with
no delay.

Typical Settings for Dual Unit Installation:

Unit No. 1:  DOB set at 2 minutes, and DOM is 132 sec.

Unit No. 2:  DOB set at 4 minutes, and DOM is 144 sec.

High Pressure Switch and Lockout Sequence

If the high pressure switch opens, the compressor
contactor will de-energize immediately.  The lockout
timer will go into a soft lockout and stay in soft lockout
until the high pressure switch closes and the delay on
break time has expired.   If the high pressure switch opens
again in this same operating cycle the unit will go into
manual lockout condition and the alarm relay circuit will
energize.   Recycling the wall thermostat resets the
manual lockout.

Summary of Contents for WA181

Page 1: ...0 200J File Volume III Tab 16 Date 04 19 99 Bard Manufacturing Company Bryan Ohio 43506 Since 1914 Moving ahead just as planned Copyright 1999 MIS 656 Models WA181 WA241 Wall Mounted Packaged Air Cond...

Page 2: ...Blade Setting 14 Tables Table 1 Electric Heat Table 2 Table 2 Electrica Specifications 4 Table 3 Thermostat Wire Size 7 Table 4 Wall Thermostat and Subbase Combinations 7 Table 5 Fan Blade Dimensions...

Page 3: ...al D Winter and Summer Air Conditioning and Equipment Selection For more information contact these publishers ACCA Air Conditioning Contractors of America 1712 New Hampshire Avenue NW Washington DC 20...

Page 4: ...ROL MODULES COIL OPTIONS X Standard 1 Phenolic Coated Evaporator 2 Phenolic Coated Condenser 3 Phenolic Coated Evaporator and Condenser OUTLET OPTIONS X Front Standard T Top on WA30 and WA36 Models NO...

Page 5: ...F G I J K L M N O P Q R S T A B C B 8 1 A W 4 2 A W 0 0 3 3 3 5 2 1 7 1 3 6 5 0 7 8 8 7 8 8 9 1 8 8 1 1 8 8 9 1 0 0 5 3 0 5 8 1 5 7 5 2 6 5 0 2 5 7 6 2 6 0 8 2 5 2 9 2 0 0 7 2 3 6 2 3 1 4 3 6 0 2 2 5...

Page 6: ...0 6 2 1 0 1 0 1 8 6 2 1 0 1 0 1 0 1 0 1 Z 0 B 0 0 B 1 4 2 A W 6 0 B 3 8 0 2 0 3 2 1 1 3 1 2 2 5 1 5 2 4 1 0 1 2 1 0 1 S Q R Maximum size of the time delay fuse or HACR type circuit breaker for protec...

Page 7: ...is an excellent guide to proper sizing All duct work or portions thereof not in the conditioned space should be properly insulated in order to both conserve energy and prevent condensation or moistur...

Page 8: ...of Energy Energyguide Fact Sheets is based upon the fresh air blank off plate in place and is recommended for maximum energy efficiency The blank off plate is available upon request from the factory a...

Page 9: ...b b u S s e r u t a e F e t a n i m o d e r P 2 0 0 3 0 4 8 1 1 1 3 F 7 8 T 3 0 0 4 0 4 8 0 2 2 1 A 9 3 5 Q l o o c e g a t s 1 t a e h e g a t s 1 n o o t u a n a F l o o c f f o t a e h m e t s y S...

Page 10: ...100 200 Page 8 FIGURE 3 MOUNTING INSTRUCTIONS MIS 353 NOTE It is recommended that a bead of silicone caulking be placed behind the side mounting flanges and under the top flashing at the time of insta...

Page 11: ...Page 9 FIGURE 4 WALL MOUNTING INSTRUCTIONS MIS 549 FIGURE 5 WALL MOUNTING INSTRUCTIONS MIS 548 SEE FIGURE 3 MOUNTING INSTRUCTIONS SEE UNIT DIMENSIONS FIGURE 1 FOR ACTUAL DIMENSIONS SEE FIGURE 1 FOR D...

Page 12: ...Manual 2100 200 Page 10 MIS 550 FIGURE 6 COMMON WALL MOUNTING INSTALLATIONS...

Page 13: ...Manual 2100 200 Page 11 FIGURE 7 LOW VOLTAGE WIRING MIS 1373...

Page 14: ...delay On a call for heating circuit R W1 make at the thermostat pulling in heat contact for the strip heat and blower operation On a call for second stage heat R W2 makes bringing on second heat cont...

Page 15: ...tables can be found later in the manual covering all models It is imperative to match the correct pressure table to the unit by model number ADJUSTMENTS Adjustable Delay on Make and Delay on Break Ti...

Page 16: ...eps to reinstall REFRIGERANT CHARGE The correct system R 22 charge is shown on the unit rating plate Optimum unit performance will occur with a refrigerant charge resulting in a suction line temperatu...

Page 17: ...u t e R e r u t a r e p m e T e r u s s e r P 5 7 0 8 5 8 0 9 5 9 0 0 1 5 0 1 0 1 1 5 1 1 1 8 1 A W B D g e d 5 7 B W g e d 2 6 e d i S w o L e d i S h g i H 1 7 4 9 1 3 7 8 0 2 5 7 3 2 2 7 7 8 3 2 9...

Page 18: ...F c i r t e m o r a B X X X 2 D A F M r e p m a D r i A h s e r F d e z i r o t o M X X X 2 V R C t s u a h x E h t i w r o t a l i t n e V l a i c r e m m o C X X X 2 M F I E t s u a h x E h t i w r...

Reviews: