background image

Manual   2100-200
Page   12

IMPORTANT INSTALLER NOTE

For improved start-up performance, wash the indoor coil
with a dishwasher detergent.

CRANKCASE HEATERS

All units are provided with some form of compressor
crankcase heat.

All single and three phase models have an insertion well-
type

heater located in the lower section of the compressor
housing.  This is a self-regulating type heater that draws
only enough power to maintain the compressor at a safe
temperature.

Some form of crankcase heat is essential to prevent liquid
refrigerant from migrating to the compressor, causing oil
pump out on compressor start up and possible valve
failure due to compressing a liquid.

The decal in Figure 8 is affixed to all outdoor units
detailing start up procedure.  This is very important.
Please read carefully.

SERVICE HINTS

1. Caution homeowner to maintain clean air filters at all

times. Also, not to needlessly close off supply and
return air registers. This reduces air flow through the
system, which shortens equipment service life as well
as increasing operating costs.

2. Check all power fuses or circuit breakers to be sure

they are the correct rating.

3. Periodic cleaning of the outdoor coil to permit full and

unrestricted airflow circulation is essential.

SEQUENCE OF OPERATION

Cooling—Circuit R-Y makes at thermostat pulling in
compressor contactor, starting the compressor and
outdoor motor. The G (indoor motor) circuit is
automatically completed on any call for cooling operation
or can be energized by manual fan switch on subbase for
constant air circulation. On all 230 volt units there is a
one minute off delay on the blower motor.  460 volt
models do not have an off delay. On a call for heating,
circuit R-W1 make at the thermostat pulling in heat
contact for the strip heat and blower operation. On a call
for second stage heat, R-W2 makes bringing on second
heat contactor, if so equipped.

START UP

COMPRESSOR CONTROL MODULE

The compressor control module is optional on the models
covered by this manual.  The compressor control is an
anti-short cycle/lockout timer with high and low pressure
switch monitoring and alarm relay output.

Adjustable Delay On Make And Break Timer

On initial power up or any time power is interrupted to
the unit  the delay on make period begins which will be 2
minutes plus 10% of the delay on break setting.  When
the delay on make is complete and the high pressure
switch (and low pressure switch if employed) is closed,
the compressor contactor is energized.  Upon shutdown
the delay or break timer starts and prevents restart until
the delay on break and delay on make periods have
expired.  During routine operation of the unit with no
power interruptions the compressor will operate on
demand with no delay.

FIGURE 8

START UP LABEL

IMPORTANT

These procedures must be
followed at initial start up and at
any time power has been removed
for 12 hours or longer.

To prevent compressor damage which may
result from the presence of liquid refrigerant
in the compressor crankcase:

1.  Make certain the room thermostat is in the
"off" position (the compressor is not to
operate).

2.  Apply power by closing the system
disconnect switch.  This energizes the
compressor heater which evaporates the
liquid refrigerant in the crankcase.

3.  Allow 4 hours or 60 minutes per poind of
refrigerant in the system as noted on the unit
rating plate, whichever is greater.

4.  After properly elapsed time, the thermostat
may be set to operate the compressor.

5.  Except as required for safety while
servicing,   do not open system disconnect
switch
.

           

 7961-061

Summary of Contents for WA181

Page 1: ...0 200J File Volume III Tab 16 Date 04 19 99 Bard Manufacturing Company Bryan Ohio 43506 Since 1914 Moving ahead just as planned Copyright 1999 MIS 656 Models WA181 WA241 Wall Mounted Packaged Air Cond...

Page 2: ...Blade Setting 14 Tables Table 1 Electric Heat Table 2 Table 2 Electrica Specifications 4 Table 3 Thermostat Wire Size 7 Table 4 Wall Thermostat and Subbase Combinations 7 Table 5 Fan Blade Dimensions...

Page 3: ...al D Winter and Summer Air Conditioning and Equipment Selection For more information contact these publishers ACCA Air Conditioning Contractors of America 1712 New Hampshire Avenue NW Washington DC 20...

Page 4: ...ROL MODULES COIL OPTIONS X Standard 1 Phenolic Coated Evaporator 2 Phenolic Coated Condenser 3 Phenolic Coated Evaporator and Condenser OUTLET OPTIONS X Front Standard T Top on WA30 and WA36 Models NO...

Page 5: ...F G I J K L M N O P Q R S T A B C B 8 1 A W 4 2 A W 0 0 3 3 3 5 2 1 7 1 3 6 5 0 7 8 8 7 8 8 9 1 8 8 1 1 8 8 9 1 0 0 5 3 0 5 8 1 5 7 5 2 6 5 0 2 5 7 6 2 6 0 8 2 5 2 9 2 0 0 7 2 3 6 2 3 1 4 3 6 0 2 2 5...

Page 6: ...0 6 2 1 0 1 0 1 8 6 2 1 0 1 0 1 0 1 0 1 Z 0 B 0 0 B 1 4 2 A W 6 0 B 3 8 0 2 0 3 2 1 1 3 1 2 2 5 1 5 2 4 1 0 1 2 1 0 1 S Q R Maximum size of the time delay fuse or HACR type circuit breaker for protec...

Page 7: ...is an excellent guide to proper sizing All duct work or portions thereof not in the conditioned space should be properly insulated in order to both conserve energy and prevent condensation or moistur...

Page 8: ...of Energy Energyguide Fact Sheets is based upon the fresh air blank off plate in place and is recommended for maximum energy efficiency The blank off plate is available upon request from the factory a...

Page 9: ...b b u S s e r u t a e F e t a n i m o d e r P 2 0 0 3 0 4 8 1 1 1 3 F 7 8 T 3 0 0 4 0 4 8 0 2 2 1 A 9 3 5 Q l o o c e g a t s 1 t a e h e g a t s 1 n o o t u a n a F l o o c f f o t a e h m e t s y S...

Page 10: ...100 200 Page 8 FIGURE 3 MOUNTING INSTRUCTIONS MIS 353 NOTE It is recommended that a bead of silicone caulking be placed behind the side mounting flanges and under the top flashing at the time of insta...

Page 11: ...Page 9 FIGURE 4 WALL MOUNTING INSTRUCTIONS MIS 549 FIGURE 5 WALL MOUNTING INSTRUCTIONS MIS 548 SEE FIGURE 3 MOUNTING INSTRUCTIONS SEE UNIT DIMENSIONS FIGURE 1 FOR ACTUAL DIMENSIONS SEE FIGURE 1 FOR D...

Page 12: ...Manual 2100 200 Page 10 MIS 550 FIGURE 6 COMMON WALL MOUNTING INSTALLATIONS...

Page 13: ...Manual 2100 200 Page 11 FIGURE 7 LOW VOLTAGE WIRING MIS 1373...

Page 14: ...delay On a call for heating circuit R W1 make at the thermostat pulling in heat contact for the strip heat and blower operation On a call for second stage heat R W2 makes bringing on second heat cont...

Page 15: ...tables can be found later in the manual covering all models It is imperative to match the correct pressure table to the unit by model number ADJUSTMENTS Adjustable Delay on Make and Delay on Break Ti...

Page 16: ...eps to reinstall REFRIGERANT CHARGE The correct system R 22 charge is shown on the unit rating plate Optimum unit performance will occur with a refrigerant charge resulting in a suction line temperatu...

Page 17: ...u t e R e r u t a r e p m e T e r u s s e r P 5 7 0 8 5 8 0 9 5 9 0 0 1 5 0 1 0 1 1 5 1 1 1 8 1 A W B D g e d 5 7 B W g e d 2 6 e d i S w o L e d i S h g i H 1 7 4 9 1 3 7 8 0 2 5 7 3 2 2 7 7 8 3 2 9...

Page 18: ...F c i r t e m o r a B X X X 2 D A F M r e p m a D r i A h s e r F d e z i r o t o M X X X 2 V R C t s u a h x E h t i w r o t a l i t n e V l a i c r e m m o C X X X 2 M F I E t s u a h x E h t i w r...

Reviews: