ADJUSTMENTS

Adjustable Delay on Make and Delay on Break
Timer

The potentiometer is used to select Delay on Break time
from 30 seconds to 5 minutes.  Delay of Make (DOM)
timing on power up and after power interruptions is equal
to 2 minutes plus 10% of Delay of Break (DOB) setting:

0.5 minute (30 seconds)

DOB = 123 second DOM

1.0 minute (60 seconds)

DOB = 126 second DOM

2.0 minute (120 seconds) DOB = 132 second DOM
3.0 minute (180 seconds) DOB = 138 second DOM
4.0 minute (240 seconds) DOB = 144 second DOM
5.0 minute (300 seconds) DOB = 150 second DOM

During routine operation of the unit with no power
interruptions the compressor will operate on demand with
not delay.

Typical Settings for Dual Unit Installation:

Unit No. 1: DOB set at 2 minutes, and DOM is 132

seconds.

Unit No. 2: DOB set at 4 minutes, and DOM is 144

seconds.

PRESSURE SERVICE PORTS

High and low pressure service ports are installed on all
units so that the system operating pressures can be
observed.  Pressure chart can be found later in the manual
covering all models.  It is imperative to match the correct
pressure chart to the unit by model number.

Summary of Contents for WA121

Page 1: ...PACKAGE AIR CONDITIONERS Model WA121 INSTALLATION INSTRUCTIONS Manual 2100 234I Supersedes 2100 234H File Volume III Tab 16 Date 08 01 07 Bard Manufacturing Company Inc Bryan Ohio 43506 Since 1914 Mo...

Page 2: ...nsion 16 Refrigerant Charge 16 Pressure Tables 17 Option Field Installed Accessories 17 Figures Figure 1 Unit Dimensions 5 Figure 2 Blower Damper Assembly 7 Figure 3 Mounting Instructions 9 Figure 4 W...

Page 3: ...esign for ACCA Manual D Residential Winter and Summer Air Conditioning and Equipment Selection For more information contact these publishers ACCA Air Conditioning Contractors of America 1712 New Hamps...

Page 4: ...0 8 0 1 5 0 8 0 2 0 4 5 7 1 1 8 1 5 7 2 3 1 1 d e d u l c n i s t t a w r e w o l b h t i W WA 12 1 A 00 X X X X X J MODEL NUMBER REVISIONS CONTROL MODULES E Low Ambient Control J Telecommunication VO...

Page 5: ...Manual 2100 234I Page 5 of 17 FIGURE 1 UNIT DIMENSIONS FACTORY BUILT AT 5 INCHES...

Page 6: ...Conditioning Contractors of America ACCA The air duct should be installed in accordance with the Standards of the National Fire Protection Association for the Installation of Air Conditioning and Vent...

Page 7: ...service door A 2 inch pleated filter is also available as an optional accessory The internal filter brackets are adjustable to accommodate the 2 inch filter by bending the metal tabs holding the 1 in...

Page 8: ...unit a different size wall opening is required 2 Locate and mark lag bolt locations if desired See Figure 3 3 Hook top rain flashing under back bend of top Top rain flashing is shipped attached to the...

Page 9: ...Manual 2100 234I Page 9 of 17 FIGURE 3 MOUNTING INSTRUCTIONS...

Page 10: ...Manual 2100 234I Page 10 of 17 FIGURE 5 WALL MOUNTING INSTRUCTIONS FIGURE 4 WALL MOUNTING INSTRUCTIONS SEE FIGURE 3 MOUNTING INSTRUCTIONS SEE UNIT DIMENSIONS FIGURE 1 FOR ACTUAL DIMENSIONS...

Page 11: ...Manual 2100 234I Page 11 of 17 FIGURE 6 COMMON WALL MOUNTING INSTALLATIONS...

Page 12: ...T E G N A R 0 4 2 3 5 2 6 1 2 8 0 2 0 2 2 7 8 1 NOTE The voltage should be measured at the field power connection point in the unit and while the unit is operating at full load maximum amperage operat...

Page 13: ...Manual 2100 234I Page 13 of 17 FIGURE 7 LOW VOLTAGE WIRING...

Page 14: ...ke is complete and the high pressure switch and low pressure switch if employed is closed the compressor contactor is energized Upon shutdown the delay on break time starts and prevents restart until...

Page 15: ...38 second DOM 4 0 minute 240 seconds DOB 144 second DOM 5 0 minute 300 seconds DOB 150 second DOM During routine operation of the unit with no power interruptions the compressor will operate on demand...

Page 16: ...9 o D O e r u t a r e p m e T 2 8 o D O e r u t a r e p m e T 1 2 1 A W 0 0 4 6 5 4 5 7 6 5 6 TABLE 6 SUCTION LINE TEMPERATURE The suction line temperatures in Table 6 are based upon 80 F dry bulb 67...

Page 17: ...7 2 9 1 9 7 7 0 2 2 8 2 2 2 4 8 8 3 2 7 8 5 5 2 0 9 2 7 2 2 9 0 9 2 5 9 9 0 3 7 9 8 2 3 B D g e d 5 8 B W g e d 2 7 e d i S w o L e d i S h g i H 1 8 8 9 1 5 8 4 1 2 8 8 0 3 2 1 9 7 4 2 4 9 4 6 2 7 9...

Reviews: