background image

Manual

2100-234

I

Page

7 of 17

DUCT WORK

All duct work, supply and return must be properly sized
for the design air flow requirement of the equipment.  Air
Conditioning Contractors of America (ACCA) is an
excellent guide to proper sizing.  All duct work or
portions thereof not in the conditioned space should be
properly insulated in order to both conserve energy and
prevent condensation or moisture damage.

Refer to Table 9 for maximum static pressure available
for duct design.

Design the duct work according to methods given by the
Air Conditioning Contractors of America (ACCA).
When duct runs through unheated spaces, it should be
insulated with a minimum of one inch of insulation.  Use
insulation with a vapor barrier on the outside of the
insulation.  Flexible joints should be used to connect the
duct work to the equipment in order to keep the noise
transmission to a minimum.

Ducts through the walls must be insulated and all joints
taped or sealed to prevent air or moisture entering the
wall cavity.

Some installations may not require any return air duct.  It
is recommended that on this type of installation that a
filter grille be located in the wall.  Filters must be of
sufficient size to allow a maximum velocity of 400 FPM.

NOTE: If no return air duct is used, applicable

installation codes may limit this cabinet to
installation only in a single story structure.

FILTERS

A one inch throwaway filter is supplied with each unit.
The filter slides into position making it easy to service.
This filter can be serviced from the outside by removing
the service door.  A 2-inch pleated filter is also available
as an optional accessory.  The internal filter brackets are
adjustable to accommodate the 2-inch filter by bending
the metal tabs holding the 1-inch filter down.  There are
two tabs on each side of the filter.

FRESH AIR INTAKE

All units are built with fresh air inlet slots punched in the
service panel.

If the unit is equipped with a fresh air damper assembly,
the assembly is shipped already attached to the unit.  The
damper blade is locked in the closed position.  To allow
the damper to operate, the maximum and minimum blade
position stops must be installed.  See Figure 2.

All capacity, efficiency and cost of operation information
as required for Department of Energy “Energyguide” Fact
Sheets is based upon the fresh air blank-off plate in place
and is recommended for maximum energy efficiency.

The blank-off plate is available upon request from the
factory and is installed in place of the fresh air damper
shipped with each unit.

CONDENSATE DRAIN

This unit employs an automatic condensate disposal
system consisting of a base drain pan, drain valve and fan
blade with slinger ring.  A plastic drain hose extends from
the evaporator drain pain at the top of the unit to the base
drain pan at the bottom.  At temperatures above 40°, the
drain valve located between the condenser coil and fan
shroud is closed allowing water to build up in the base to
a height of 5/8" to 3/4".  The fan blade with slinger then
rotates in this water and throws the water onto the
condenser coil.  This disposes of the water by
evaporating it on the hot condenser.

At temperatures below 40°, the drain valve opens
draining the base pan and preventing freeze ups that
could damage the coil or fan blade.

FIGURE  2

FRESH AIR DAMPER

Summary of Contents for WA121

Page 1: ...PACKAGE AIR CONDITIONERS Model WA121 INSTALLATION INSTRUCTIONS Manual 2100 234I Supersedes 2100 234H File Volume III Tab 16 Date 08 01 07 Bard Manufacturing Company Inc Bryan Ohio 43506 Since 1914 Mo...

Page 2: ...nsion 16 Refrigerant Charge 16 Pressure Tables 17 Option Field Installed Accessories 17 Figures Figure 1 Unit Dimensions 5 Figure 2 Blower Damper Assembly 7 Figure 3 Mounting Instructions 9 Figure 4 W...

Page 3: ...esign for ACCA Manual D Residential Winter and Summer Air Conditioning and Equipment Selection For more information contact these publishers ACCA Air Conditioning Contractors of America 1712 New Hamps...

Page 4: ...0 8 0 1 5 0 8 0 2 0 4 5 7 1 1 8 1 5 7 2 3 1 1 d e d u l c n i s t t a w r e w o l b h t i W WA 12 1 A 00 X X X X X J MODEL NUMBER REVISIONS CONTROL MODULES E Low Ambient Control J Telecommunication VO...

Page 5: ...Manual 2100 234I Page 5 of 17 FIGURE 1 UNIT DIMENSIONS FACTORY BUILT AT 5 INCHES...

Page 6: ...Conditioning Contractors of America ACCA The air duct should be installed in accordance with the Standards of the National Fire Protection Association for the Installation of Air Conditioning and Vent...

Page 7: ...service door A 2 inch pleated filter is also available as an optional accessory The internal filter brackets are adjustable to accommodate the 2 inch filter by bending the metal tabs holding the 1 in...

Page 8: ...unit a different size wall opening is required 2 Locate and mark lag bolt locations if desired See Figure 3 3 Hook top rain flashing under back bend of top Top rain flashing is shipped attached to the...

Page 9: ...Manual 2100 234I Page 9 of 17 FIGURE 3 MOUNTING INSTRUCTIONS...

Page 10: ...Manual 2100 234I Page 10 of 17 FIGURE 5 WALL MOUNTING INSTRUCTIONS FIGURE 4 WALL MOUNTING INSTRUCTIONS SEE FIGURE 3 MOUNTING INSTRUCTIONS SEE UNIT DIMENSIONS FIGURE 1 FOR ACTUAL DIMENSIONS...

Page 11: ...Manual 2100 234I Page 11 of 17 FIGURE 6 COMMON WALL MOUNTING INSTALLATIONS...

Page 12: ...T E G N A R 0 4 2 3 5 2 6 1 2 8 0 2 0 2 2 7 8 1 NOTE The voltage should be measured at the field power connection point in the unit and while the unit is operating at full load maximum amperage operat...

Page 13: ...Manual 2100 234I Page 13 of 17 FIGURE 7 LOW VOLTAGE WIRING...

Page 14: ...ke is complete and the high pressure switch and low pressure switch if employed is closed the compressor contactor is energized Upon shutdown the delay on break time starts and prevents restart until...

Page 15: ...38 second DOM 4 0 minute 240 seconds DOB 144 second DOM 5 0 minute 300 seconds DOB 150 second DOM During routine operation of the unit with no power interruptions the compressor will operate on demand...

Page 16: ...9 o D O e r u t a r e p m e T 2 8 o D O e r u t a r e p m e T 1 2 1 A W 0 0 4 6 5 4 5 7 6 5 6 TABLE 6 SUCTION LINE TEMPERATURE The suction line temperatures in Table 6 are based upon 80 F dry bulb 67...

Page 17: ...7 2 9 1 9 7 7 0 2 2 8 2 2 2 4 8 8 3 2 7 8 5 5 2 0 9 2 7 2 2 9 0 9 2 5 9 9 0 3 7 9 8 2 3 B D g e d 5 8 B W g e d 2 7 e d i S w o L e d i S h g i H 1 8 8 9 1 5 8 4 1 2 8 8 0 3 2 1 9 7 4 2 4 9 4 6 2 7 9...

Reviews: