2100-444-003A
Page 78
6.4.7.7 Enable Zone Dehumidification
The TCS can provide zone dehumidification by running the air conditioners and cycling electric
heat on and off to maintain room temperature. Factory default for this value is disabled. Note: The air-
conditioner circuit breakers and wiring must be sized for concurrent operations air-conditioning and
electric heat. Special dehumidification models are available for use with this feature. These models have
circuit breakers and special MCA and MOP ratings that allow concurrent operation of the air
conditioners and electric heat. These are special, dedicated code models ending in D053, D061, D062,
D064, or D066. Enable this feature if dehumidification is required. Consult your Bard representative for
more information.
6.4.7.8 Model Number
Click on the text box and enter the model number from the TCS serial plate. The model number
is stored in the controller and can be accessed for troubleshooting and parts replacement purposes.
6.4.7.9 Model Serial Number
Click on the text box and enter the serial number from the TCS serial plate. The serial number is
stored in the controller and can be accessed for troubleshooting and parts replacement purposes
6.4.7.10 Software
The factory installed software version is displayed and is required for troubleshooting purposes.
6.4.7.11 Firmware
The factory installed firmware version is displayed and is required for troubleshooting purposes.
Summary of Contents for TCS22 Series
Page 14: ...2100 444 003A Page 8 Figure 1 Front Cover...
Page 15: ...2100 444 003A Page 9 Figure 2 Control Location...
Page 21: ...2100 444 003A Page 15 Figure 4 External Wiring...
Page 22: ...2100 444 003A Page 16 Figure 5 Internal Wiring Figure 6 Power...
Page 23: ...2100 444 003A Page 17 Backup System...