background image

2100-444-003A 

Page 33 

The Fault alarm takes precedence over the Alarm (High) or Alarm (Low) message. If the Sensor 

is failed high or low the Alarm (High) or Alarm (Low) alarms will also be activated but only the Fault 
alarm will be displayed because this is the actual condition causing the other alarms. 

These are all self-clearing alarms and will reset themselves when the alarm condition no longer 

exists. This is a medium priority alarm. 

 

5.3.3.3  

#1 BLOWER ALARM 

 
The Blower Fail alarm item will show one of two different alarm messages. A "No Alarm" 

message indicates that the blower airflow sensor contacts have closed and the blower is functioning 
normally. A Fault alarm message indicates that the blower airflow sensor contacts have not closed. A 
faulty blower motor, wheel or sensor could cause this alarm. 

This alarm must be cleared before operation of the blower can resume. Use the Clr Verify Alr 

action in the Override menu to clear the alarm. This is a critical alarm. 

 

5.3.3.4  

#1 COMPRESSOR ALARM 

 

The Compressor Alarm item will show one of two different alarm messages. "No Alarm" 

message indicates that the compressor verify circuit contacts have closed and the compressor is 
functioning normally. A Fault alarm message indicates that the  compressor verify circuit contacts have 
not closed. A Trip on High or Low pressure, no compressor current, failed blower, or faulty compressor 
current sensor could cause this alarm. 

This alarm must be cleared before operation of the compressor can resume. Use the Clr Verify 

Alr action in the Override menu to clear the alarm. This is a critical alarm. 

 

5.3.3.5  

#1 FILTER ALARM 

 
The Filter alarm item will  show one of two different alarm messages. "No Alarm" message 

indicates that the filter is clean enough to operate. A Fault alarm message indicates that the filter is dirty 
and needs replaced. 

This is a self-clearing alarm and will reset itself when the alarm condition no longer exists. The 

filter sensor is a manually reset device and must be reset once the filter is changed to clear the alarm 
condition. This is a low priority alarm. 
 

5.3.3.6  

UTILITY POWER FAIL 

 
The Utility Power Fail alarm item will show one of two different alarm messages. A "None" 

alarm message indicates that no alarm is present and that utility power is present at the site. A "Fault" 
alarm message indicates that an alarm is present and the system is operating on backup power. This 
feature will operate only if the TCS22 is connected to an uninterruptible power supply. 

This is a self-clearing alarm and will reset itself when the alarm condition no longer exists. This 

is a critical priority alarm. 

 

Summary of Contents for TCS22 Series

Page 1: ...OPERATIONS MANUAL TELCOM CLIMATEWATCH SYSTEM MODEL TCS22 003 Manual 2100 444 003A Supersedes 2100 444 003 File Vol III Tab 19...

Page 2: ...em Points to be Controlled 3 1 5 5 Wallmount Points to be Controlled 3 1 5 6 Alarm Points 3 1 6 Model Nomenclature 5 2 0 SPECIFICATIONS 5 2 1 Electrical Specifications 5 2 2 Mechanical Specifications...

Page 3: ...ied Unoccupied Mode Sequence 22 4 2 5 Alarm Sequence 22 4 2 6 Dehumidification sequence 24 4 2 7 Thermal Shock Protection Sequence 24 4 2 8 Modem Sequence 24 4 2 9 Power Management Sequence 24 4 2 10...

Page 4: ...ng Setpoint 36 5 3 4 2 Unoccupied Cooling Setpoint 36 5 3 4 3 Occupied Heating Setpoint 37 5 3 4 4 Unoccupied Heating Setpoint 37 5 3 4 5 High Temperature Alarm Setpoint 37 5 3 4 6 Low Temperature Ala...

Page 5: ...d ClimateWatch Software 49 6 3 1 Screen Overview 49 6 3 2 TCS communications 51 6 4 TCS Controller Information Screens 59 6 4 1 Main Screen Tab 60 6 4 2 Set Point Tab 62 6 4 3 Override 1 Tab 66 6 4 4...

Page 6: ...rol Location 9 Figure 3 Mounting Template 10 Table 1 Low Voltage Wire Size 12 Figure 4 External Wiring 15 Figure 5 Internal Wiring 16 Figure 6 Power Backup System 16 Table 2 Enthalpy Lookup Table 39 T...

Page 7: ...d in the shelter This provides for ventilation of the structure in case of utility power failure alarming of the power failure condition and acts as an uninterruptible power supply for the TCS22 See F...

Page 8: ...rol system used in conjunction with one 1 Bard Wall Mount air conditioners The system consists of a state of the art direct digital controller the TSC22 one 1 Bard Wall Mount air conditioners and a sp...

Page 9: ...Economizer Unit 1 Compressor Unit 1 Heating Unit 1 Blower Unit 2 1 5 6 ALARM POINTS High Space Temperature Low Space Temperature High Space Humidity Low Space Humidity Blower Failure Unit 1 Compressor...

Page 10: ...ompressor Current Switch Required Standard in V Module 8 Spare 9 Fire Trouble Optional 10 Fire Alarm Optional 11 Spare 12 Door Alarm Optional 13 Main Power Sensor Optional 14 Occupied Override Switch...

Page 11: ...0 Vdc to 10 Vdc Current Rating 5 0 mA at 10 Vdc Binary Relay Outputs 12 Type Form A Relay SPST N O Contact Rating 24 VAC 5 A Resistive 24 VAC 2 A Inductive 2 2 Mechanical Specifications Height 26 25 i...

Page 12: ...ear Interchangeability 3 Temperature Range 40 to 130 o F 40 to 76o C Humidity Range 0 to 99 non condensing 2 4 3 COMPRESSOR CURRENT SENSOR Type Solid State DC Switch Output Form A solid state DC switc...

Page 13: ...anical Airflow Switch Output Form C Contact Supply Voltage Self Powered Maximum Load 300 VA at 24 VAC Temperature Range 40 to 180 o F 40 to 82o C Pressure Range 0 07 to 0 12 in wc Dimensions 6 125 hig...

Page 14: ...2100 444 003A Page 8 Figure 1 Front Cover...

Page 15: ...2100 444 003A Page 9 Figure 2 Control Location...

Page 16: ...2100 444 003A Page 10 Figure 3 Mounting Template 22 288 16 000 3 356 4 856 6 356 7 856 9 356 1 288 1 000 HIGHVOLTAGE WIRING MIS 866...

Page 17: ...power connected to the controller or to either of the Bard Wall Mount air conditioners 3 2 1 HIGH VOLTAGE WIRING IMPORTANT High voltage wiring must not be run in the same conduit as low voltage contro...

Page 18: ...the outside wall of the structure and all wiring to the sensor be made through conduit A one 1 pair shielded cable with 20 gauge copper conductors such as National Wire Cable Corporation NQP series ca...

Page 19: ...ransfer switch when used in conjunction with an inverter to provide emergency ventilation of the shelter during power failures Consult the power failure management sequence section 4 2 10 and section...

Page 20: ...ack accepts a standard a RJ 11 six 6 position modular phone plug 3 2 6 WIRING ETHERNET When the TCS22 is equipped with an Etherlink communications module The LAN WAN should be connected to the back of...

Page 21: ...2100 444 003A Page 15 Figure 4 External Wiring...

Page 22: ...2100 444 003A Page 16 Figure 5 Internal Wiring Figure 6 Power...

Page 23: ...2100 444 003A Page 17 Backup System...

Page 24: ...ctors TCS22 is grounded Check supply voltage Change both transformer taps if necessary See Sec 3 21 Carefully recheck all low voltage wiring for correct connection points Carefully recheck all sensor...

Page 25: ...ltage terminals R to G and observe Blower operation The Blower will continue to run for One 1 minute after the jumper is removed Economizer Test Connect a jumper wire on A C unit low voltage terminals...

Page 26: ...light and stay lit Unit 1 is Lead Unit Unit 2 is Lead Unit Free Cooling Power Failure LEDs will light for 5 seconds and then resume normal operation System Rx and Tx and Local Rx and Tx will all flas...

Page 27: ...or dry bulb temperature Outdoor Enthalpy or Temperature is calculated from Outdoor Temperature and or Outdoor Humidity sensors If the outdoor enthalpy or temperature is below the free cooling setpoin...

Page 28: ...n the Event List and Output 12 Shelter Alarm is energized This is a self clearing alarm High Space Humidity When Space Humidity is above High Humidity Alarm Setpoint a critical alarm is logged in the...

Page 29: ...ed by Unit 1 Compressor Lockout Relay and Unit 1 Compressor Current Switch Dirty Filter Unit 1 If Unit 1 Dirty Filter Switch is closed a low priority alarm is logged in the Event List and Output 12 Sh...

Page 30: ...thermal shock protection sequence protects equipment in the structure from being subjected to rapid changes in temperature after a power outage The thermal shock routine limits the rate of change in t...

Page 31: ...djustable 5 0 DISPLAY KEYPAD OPERATION DAK The display and keypad DAK is used to monitor and change parameters in the controller If DAK is needed it must be ordered as part of the TCS22 It cannot be o...

Page 32: ...st four lines of the Building Status screen will be displayed at power up The current controller date and time will be displayed on the first line of the display Alarm status is shown on the second li...

Page 33: ...equired authority level you will be able to access the screenu to make changes See the Password section for a discussion of the authority levels 5 3 1 Buildings Status Screen Authority Level Required...

Page 34: ...ve Cooling Setpoint will be the same as the Occupied Cooling Setpoint If the controller is in unoccupied mode the Active Cooling Setpoint will be the same as the Unoccupied Cooling Setpoint Occupancy...

Page 35: ...tpoint then Free Cooling is ON If the temperature or enthalpy of the outside air is more than the Free Cooling Setpoint then Free Cooling is Off 5 3 1 8 ROOM OCCUPIED YES NO This display indicates the...

Page 36: ...display item will show On if the unit 1 economizer output of the controller is energized 5 3 2 2 UNIT 1 COMPRESSOR This display item will show Off if the unit 1 compressor output of the controller is...

Page 37: ...zation the alarm can be acknowledged Acknowledging an alarm resets the shelter alarm output so that if another alarm is registered the shelter alarm will reenergize to indicate a new alarm Acknowledgi...

Page 38: ...aulty sensor When a Space Temperature Fault alarm is detected the Zone Temperature value defaults to 74 degrees effectively shutting down heating and cooling until the sensor is replaced An Alarm High...

Page 39: ...lt alarm message indicates that the compressor verify circuit contacts have not closed A Trip on High or Low pressure no compressor current failed blower or faulty compressor current sensor could caus...

Page 40: ...ng normally A Fault alarm message indicates that the Outdoor Temperature Sensor is sensing a value above 120 Fo or below 20 Fo This probably indicates a faulty sensor These are all self clearing alarm...

Page 41: ...a set point scroll up or down until the setpoint that is to be changed is visible on the screen Press the F1 key If more then one setpoint is shown on the screen use the Up and Down keys to highlight...

Page 42: ...noccupied cooling setpoint requires an authority level of Supervisor or higher to change Anyone may view the setpoint value The Unoccupied Cooling Setpoint Range is from 72 0 to 85 0 Fo The default va...

Page 43: ...could occur if this requirement is not followed 5 3 4 6 LOW TEMPERATURE ALARM SETPOINT The low temperature alarm setpoint requires an authority level of Supervisor or higher to change Anyone may view...

Page 44: ...ns that you wish to maintain in the structure Read down the relative humidity column under the percentage RH you wish to maintain Read across the inside temperature row to where it intersects the RH c...

Page 45: ...t until they are either cleared by the operator or power is cut to the controller Use with caution Note Outputs cannot be overridden until alarms have been cleared This applies to blowers and compress...

Page 46: ...override status If you do not have authority to override the outputs will not be highlighted A supervisor authority level is required override outputs If you have authority to override the value will...

Page 47: ...to the unit 1 economizer and it will remain disabled until cleared Once overridden the output will remain overridden until the Clr O R action is sent to the output or power is interrupted to the cont...

Page 48: ...s interrupted to the controller Use the Clr O R to cancel an override action and resume normal operation A supervisor authority level is needed to use this item 5 3 5 5 CONTINUOUS BLOWER This item use...

Page 49: ...he current value of the item This value will be updated every ten 10 seconds Pressing the Up or Down key will scroll forward or backward respectively through the above list displaying the list item on...

Page 50: ...eover setpoint 5 3 6 4 DAYLIGHT SAVINGS TIME If the area of the country where the TCS22 is located uses Daylight Savings Time daylight savings time should be enabled for accurate clock readings Factor...

Page 51: ...nd overriding outputs Supervisor password is 3333 Engineer Engineer level is allowed to view screens one through 7 Engineer level may change any values on screens 1 through 7 This includes acknowledgi...

Page 52: ...Up Arrow Up Arrow Left Arrow Up Arrow Up Arrow Up Arrow Up Arrow Enter If an invalid password is entered the display will flash all asterisks and the authority level will remain as Display Only If a p...

Page 53: ...FREE COOLING NO UNIT 2 ECON OFF Unocc Htg SP ECON OUTPUT OFF ECON OUTPUT OFF FC ENTH CHANGEOVER LEAD UNIT 2 UNIT 2 COMP OFF ALARM TYP ACK A 68 00 F OVR STATUS AUTO OVR STATUS AUTO ENABLED SHELTER POWE...

Page 54: ...ad trend information from the sites and store it in a database file to be viewed from Microsoft Access or Excell The program is used to display the alarm history for troubleshooting purposes 6 2 Insta...

Page 55: ...ct Folders and the right side is the Controller Information Area Expert uses projects to group information about different TCS controllers Each site or building should have its own project The project...

Page 56: ...ptions Options System Options Print Screen Projects Print Project Browser Returns Screen to Projects View Dial Out Options Dialout Net Search View Net Search Not Used Project Reports Allows Viewing of...

Page 57: ...ports and baud rates must be configured to allow communications with the controller Settings must be set for both remote and direct communication modes if they are to be used To configure settings fo...

Page 58: ...er either directly or remotely via a modem For direct communication a cable should be connected between the computer Com port specified in the above step and to the 9 pin RS 232 Monitor port of the TC...

Page 59: ...ite Click OK The Connect to Project Window will appear 6 3 2 3 Direct Connection This section deals with directly connecting to the TCS controller via a computer cable For remote connection informatio...

Page 60: ...roller type in the phone number of the site including any dialing prefixes If the phone number is to be saved in the project folder click the Save Modified Phone Number check box Clicking OK will dial...

Page 61: ...444 003A Page 55 Once the modems have connected the window will change to the Find It screen Make sure the ASIC 2 button is checked Click the Find It button to establish communications with the contro...

Page 62: ...7040 Device Profile window will appear If communications have been established the status bar at the bottom of the window will show ASIC 2 7040 Online If the status bar is flashing red communication h...

Page 63: ...displayed for TCS22 models For TCS22 models refer to the serial plate inside the front cover to determine the software version that is installed The last three numbers of the model number indicate th...

Page 64: ...hat a project has been created for a site It will appear under the projects folder section of the display Once the project is created and saved it can be accessed by double clicking on the project nam...

Page 65: ...configuration If you want to save the changes click OK otherwise click cancel 6 3 2 7 Loading TCS Configuration To reload the device configuration to the setting stored in the device archive click on...

Page 66: ...r conditions This is used to determine if the Economizer can be opened to take advantage of a Free Cooling condition When a Technician enters the structure he she may decide to press the Occupancy Ove...

Page 67: ...nit is in the Cooling Mode and Warmer the Zone Temperature when the unit is in the Heating Mode The Lead Lag status indicates if the unit is the Lead or the Lag unit The Lead unit is the Primary condi...

Page 68: ...nt to a lower temperature if the structure is occupied The Occupied Cooling Setpoint will be the active setpoint if the occupancy override timer has been triggered and if the zone temperature is above...

Page 69: ...row will increase the Occupied Heating Setpoint by 0 50 degrees Fahrenheit until the maximum allowed setpoint of 70 0 degrees is reached Clicking on the left arrow will decrease the Occupied Heating S...

Page 70: ...the Left arrow will decrease the High Humidity Alarm Setpoint by 1 percent relative humidity until the minimum allowed setpoint of 55 RH is reached 6 4 2 8 Low Humidity Alarm SetPoint The Low Humidit...

Page 71: ...f Supervisor or higher to change Anyone may view the setpoint value The Dehumidification Setpoint Range is from 50 to 70 RH The default value is 50 RH 6 4 2 12 Continuous Blower Enable The Continuous...

Page 72: ...r is in Dehumidification mode the Active Heating Setpoint will be 70o the same as the fixed Dehumidification Heating Setpoint 6 4 2 15 Active Dehumidification Setpoint The Active Dehumidification Setp...

Page 73: ...mode This means that when operation is called for by the controller the operation has been suspended manually in the Off mode and cannot operate The third mode is the Override On mode When this mode...

Page 74: ...F To clear an override click the Output Verify Action button Select Clear RAM Override Flag Resume Application and click OK 6 4 3 2 Unit 1 Blower The override status box displays the current override...

Page 75: ...Output status will display OFF To clear an override click the Output Verify Action button Select Clear RAM Override Flag 6 4 3 4 Unit 1 Heater The override status box displays the current override con...

Page 76: ...the alarm on and it will not be able to be cleared or acknowledged until the alarm is re enabled All alarms can be acknowledged Acknowledging an alarm resets the shelter alarm output to normally open...

Page 77: ...he alarm can be cleared from the Unit 1 Override tab See Section 5 3 2 1 Clearing the Alarm before the Compressor can be fixed will cause the Compressor to fail again and another Shelter Alarm to be s...

Page 78: ...e the High Alarm setpoint for that value The third possible state would be the Low Alarm condition stating that the value is below the Low Alarm setpoint The last alarm state is fault alarm indicating...

Page 79: ...tem has been reset the Alarm will be removed 6 4 4 10 Fire Trouble Alarm If a Fire Trouble Alarm occurs the Shelter Alarm indicator on the Main Screen will flash The Fire Trouble Alarm can be acknowle...

Page 80: ...into the Alarm Log screen for viewing and analysis Once the data has been gathered the user may print the file by clicking the print screen button or save the file by right clicking anywhere on the a...

Page 81: ...Offset The Zone Temperature will add the value seen in the textbox from the Zone Temperature to calibrate the sensor 6 4 6 2 Zone Humidity Offset The Zone Humidity Offset will add the value seen in th...

Page 82: ...Unit 1 Supply Air Temperature to calibrate the sensor 6 4 7 MISC TAB The misc tab displays several options that are available in the TCS firmware and other information about the controller hardware Th...

Page 83: ...ooling as long as the outdoor enthalpy is below the Enthalpy changeover setpoint When dry bulb temperature scheme is used the economizers will be used as 1st and 2nd stage cooling as long as the outdo...

Page 84: ...models ending in D053 D061 D062 D064 or D066 Enable this feature if dehumidification is required Consult your Bard representative for more information 6 4 7 8 Model Number Click on the text box and e...

Page 85: ...and Economizer Run Time The controller will store all of these values once per hour and will hold up to 128 hours of data Once the data register has been filled the new data will overwrite the oldest...

Page 86: ...2100 444 003A Page 80 6 4 9 DIAL OUT TAB...

Page 87: ...Primary number is the first phone number that will be dialed for Alarm notification This number can be up to 25 characters long The number may contain hyphens or commas but they are not necessary for...

Page 88: ...ab is just a group of 8 message boxes that can be used to make notes about the controller or leave messages concerning the controller for the next technician Clicking on one of the message boxes allow...

Page 89: ...ight is On but Blower fails to operate Check A C unit 24 Volt power from C to G Check controller switch Remove junction connector J5 Check for continuity from pin 3 to pin 6 on controller with the Blo...

Page 90: ...t Check the AC voltage supply to the Sensor output board inside the door of the TCS22 The voltage should be 24 Volts AC Check Sensor Output Check the DC output voltage from the sensor output board ins...

Page 91: ...ty between terminals 6 and 7 of the A C unit voltage terminal block Compressor Current Sensor 1 or 2 Check Sensor Output Remove plug in connectors J1 J2 and J4 from the TCS22 controller Connect a jump...

Page 92: ...re between R and G of the A C unit low voltage terminal block to operate the blower Check continuity between terminal 8 and 9 of the A C unit low voltage terminal block This should be a Closed circuit...

Page 93: ...DC vs RH Humidity Output RH Volts DC 5 00 0 25 10 00 0 50 15 00 0 75 20 00 1 00 25 00 1 25 30 00 1 50 35 00 1 75 40 00 2 00 45 00 2 25 50 00 2 50 55 00 2 75 60 00 3 00 65 00 3 25 70 00 3 50 75 00 3 7...

Page 94: ...61020 21 868 10 00 14 00 47630 16 589 5 00 23 00 37400 12 694 0 00 32 00 29560 9 795 5 00 41 00 23500 7 619 10 00 50 00 18790 5 971 15 00 59 00 15150 4 714 20 00 68 00 12290 3 748 25 00 77 00 10020 3...

Page 95: ...tinue to run for One 1 minute after the jumper is removed Economizer Test Connect a jumper wire on A C unit low voltage terminals R to G and observe Blower operation After Blower operation is confirme...

Reviews: