5.3.4.3 OCCUPIED HEATING SETPOINT
The occupied heating setpoint requires an authority level of Supervisor or higher to change.
Anyone may view the setpoint value. The Occupied Heating Setpoint Range is from 68.0 to 70.0 F
o
. The
default value is 70.0 F
o
5.3.4.4 UNOCCUPIED HEATING SETPOINT
The unoccupied heating setpoint requires an authority level of Supervisor or higher to change. Anyone
may view the setpoint value. The Unoccupied Heating Setpoint Range is from 60.0 to 70.0 F
o
. The
default value is 68.0 F
o
5.3.4.5 HIGH TEMPERATURE ALARM SETPOINT
The high temperature alarm setpoint requires an authority level of Supervisor or higher to
change. Anyone may view the setpoint value. The High Temperature Alarm Setpoint Range is from 80.0
to 100.0 F
o
. The default value is 90.0 F
o
.
The high alarm setpoint should always be set at least 7 degrees
higher then the unoccupied cooling setpoint. Nuisance alarms could occur if this requirement is not
followed.
5.3.4.6 LOW TEMPERATURE ALARM SETPOINT
The low temperature alarm setpoint requires an authority level of Supervisor or higher to change.
Anyone may view the setpoint value. The Low Temperature Alarm Setpoint Range is from 45.0 to 67.0
F
o
. The default value is 56.0 F
o
.
The low alarm setpoint should always be set at least 4 degrees lower
then the unoccupied heating setpoint. Nuisance alarms could occur if this requirement is not followed.
5.3.4.7 HIGH HUMIDITY ALARM SETPOINT
The high humidity alarm setpoint requires an authority level of Supervisor or higher to change.
Anyone may view the setpoint value. The High Humidity Alarm Setpoint Range is from 55.0 to 85 %
RH. The default value is 60.0 % RH.
5.3.4.8 LOW HUMIDITY ALARM SETPOINT
The low humidity alarm setpoint requires an authority level of Supervisor or higher to change.
Anyone may view the setpoint value. The Low Humidity Alarm Setpoint Range is from 5.0 to 35 % RH.
The default value is 20.0 % RH.
5.3.4.9 DEHUMIDIFICATION SETPOINT
The dehumidification setpoint setpoint requires an authority level of Supervisor or higher to
Summary of Contents for TCS22 Series
Page 14: ...2100 444 003A Page 8 Figure 1 Front Cover...
Page 15: ...2100 444 003A Page 9 Figure 2 Control Location...
Page 21: ...2100 444 003A Page 15 Figure 4 External Wiring...
Page 22: ...2100 444 003A Page 16 Figure 5 Internal Wiring Figure 6 Power...
Page 23: ...2100 444 003A Page 17 Backup System...