background image

Manual   2100-410
Page    7

INSTALLATION INSTRUCTIONS

WALL MOUNTING INFORMATION

1. Two holes for the supply and return air openings

must be cut through the wall as shown in Figure 3.

2. On wood frame walls, the wall construction must be

strong and rigid enough to carry the weight of the
unit without transmitting any unit vibration.

         WARNING

Fire hazard can result if 1/4 inch clearance to
combustible materials for supply air duct is not
maintained.  See Figure 3.

3. Concrete block walls must be thoroughly inspected

to insure that they are capable of carrying the weight
of the installed unit.

MOUNTING THE UNIT

1. These units are secured by wall mounting brackets

which secure the unit to the outside wall surface at
both sides.  A bottom mounting bracket is provided
for ease of installation, but is not required.

2. The unit itself is suitable for 0 inch clearance, but

the supply air duct flange and the first 3 feet of
supply air duct require a minimum of 1/4 inch
clearance to combustible material.  If a combustible
wall use a minimum of 30-1/2” x 10-1/2”
dimensions for sizing.  However it is generally
recommended that a 1 inch clearance is used for
ease of installation and maintaining the required
clearance to combustible material.  The supply air
opening would then be 32” x 12”.  See Figures 3 and
4 for details.

        WARNING

Failure to provide the 1/4 inch clearance
between the supply duct and a combustible
surface for the first 3 feet of duct can result in
fire causing property damage, injury or death.

3. Locate and mark lag bolt locations and bottom

mounting bracket location.  See Figure 3.

4. Mount bottom mounting bracket.

5. Hook top rain flashing under back bend of top.  Top

rain flashing is shipped with unit attached to back of
unit on the right side.

 6. Position unit in opening and secure with 5/16 lag

bolts; use 3/4 inch diameter flat washers on the lag
bolts.

7. Secure rain flashing to wall and caulk across entire

length of top.  See Figure 3.

8. For additional mounting rigidity, the return air and

supply air frames or collars can be drilled and
screwed or welded to the structural wall itself
(depending upon wall construction).  Be sure to
observe required clearance if combustible wall.

9. On side by side installations, maintain a minimum

of 20 inches clearance on right side to allow access
to control panel and heat strips, and to allow proper
airflow to the outdoor coil. Additional clearance
may be required to meet local or national codes.

Summary of Contents for SH431

Page 1: ...LL MOUNTED PACKAGE HEAT PUMPS Models SH381 SH431 SH491 Manual 2100 410B Supersedes 2100 410A File Volume III Tab 17 Date 02 24 04 Bard Manufacturing Company Bryan Ohio 43506 Since 1914 Moving ahead ju...

Page 2: ...n Blade Setting Dimensions 22 Removal of Fan Shroud 22 Refrigerant Charge 22 Pressure Tables 24 Figures Figure 1 Unit Dimensions 3 Figure 2 Fresh Air Damper Assembly 6 Figure 3 Mounting Instructions 8...

Page 3: ...and Summer Air Conditioning Duct Design for Residential ACCA Manual D Winter and Summer Air Conditioning and Equipment Selection For more information contact these publishers ACCA Air Conditioning Co...

Page 4: ...entilator w Built in Exhaust FILTER OPTIONS X 1 Inch Throwaway Standard W 1 Inch Washable P 2 Inch Pleated COLOR OPTIONS X Beige Standard 4 Buckeye Gray COIL OPTIONS X Standard 1 Phenolic Coated Evapo...

Page 5: ...u S n r u t e R W D H A B C B E F G I J K L M N O P Q R S T 1 8 3 H S 1 3 4 H S 1 9 4 H S 5 7 0 2 4 2 3 4 2 2 5 7 8 4 8 8 8 9 8 8 9 2 8 8 5 1 8 8 9 2 8 8 3 4 0 1 9 1 6 6 1 3 0 0 0 3 8 6 2 3 4 9 6 2 9...

Page 6: ...r i W 2 d n u o r G e z i S e r i W T K C A T K C B T K C A T K C B T K C A T K C B T K C A T K C B Z 0 A 0 0 A 1 8 3 H S 5 0 A 8 0 A 0 1 A 1 8 0 2 0 3 2 1 2 r o 1 2 r o 1 2 r o 1 1 3 7 5 3 7 3 8 5 4...

Page 7: ...A 1 inch throwaway filter is supplied with each unit The filter slides into position making it easy to service This filter can be serviced from the outside by removing the service door A 1 inch washa...

Page 8: ...tion as required for Department of Energy Energyguide Fact Sheets is based upon the fresh air Blank off plate in place and is recommended for maximum energy efficiency The blank off plate is available...

Page 9: ...ch clearance is used for ease of installation and maintaining the required clearance to combustible material The supply air opening would then be 32 x 12 See Figures 3 and 4 for details WARNING Failur...

Page 10: ...time of installation MIS 1445 A Top flashing detail view Attach supplied rain flashing Apply caulk between flashing and wall Foam air seal Seal with bead of caulking along entire length of top Supply...

Page 11: ...ired for the first 3 feet of ducting It is important to insure that the 1 4 inch minimum spacing is maintained at all points Failure to do this could result in overheating the combustible material and...

Page 12: ...ORY SUPPLIED RAIN FLASHING MOUNT ON UNIT BEFORE INSTALLATION SEE UNIT DIMENSIONS FIGURE 1 FOR ACTUAL DIMENSIONS ATTACH TO TOP PLATE OF WALL 1 000 CLEARANCE ALL AROUND INTERIOR FINISHED WALL OVER FRAME...

Page 13: ...Manual 2100 410 Page 11 FIGURE 7 COMMONWALLMOUNTINGINSTALLATIONS FREE AIR FLOW NO DUCT DUCTED SUPPLY RETURN AT UNIT FALSE WALL INSTALLATION MIS 550 CLOSETINSTALLATION...

Page 14: ...ary high starting current of the compressor motor The disconnect access door on this unit may be locked to prevent unauthorized access to the disconnect To convert for the locking capability bend the...

Page 15: ...mechanical heating compressor off line and send the compressor signal to energize electric heat in its place to make electric heat first stage heating This can also be applied to bank the quantity of...

Page 16: ...This is done to maximize efficiency by utilizing the heat pump to bring the conditioned space temperature up rather than cycling on the electric heat due a second stage call for heat from the thermost...

Page 17: ...on indicating a problem COMPRESSOR MALFUNCTION LIGHT Actuation of the green check lamp is accomplished by a relay output from the heat pump control board which is factory installed Any condition such...

Page 18: ...le j k TABLE 4 WALLTHERMOSTATANDSUBBASECOMBINATIONS t a t s o m r e h T e s a b b u S s e r u t a e F t n a n i m o d e r P 5 4 0 3 0 4 8 1 6 7 1 A 1 4 8 T b l u b y r u c r e M t a e h g t s 2 l o o...

Page 19: ...ired If improper rotation is corrected at this time there will be no negative impact on the durability of the compressor However reverse operation for over one hour may have a negative impact on the b...

Page 20: ...CE OF OPERATION COOLING Circuit R Y makes at thermostat pulling in compressor contactor starting the compressor and outdoor motor The G indoor motor circuit is automatically completed on any call for...

Page 21: ...or other metallic object or another 1 4 inch QC to short between the SPEEDUP terminals to accelerate the HPC timer and initiate defrost Be careful not to touch any other terminals with the instrument...

Page 22: ...e c a l p e R t o n g n i s a h p r e w o P t c e r r o c e s a h p n o D E L d e r r o f k c e h C y l n o s t i n u e s a h p 3 r o t i n o m t i n u e h t o t s d a e l r e w o p o w t h c t i w S...

Page 23: ...48 0 49 0 50 0 51 0 52 0 53 0 54 0 55 0 56 0 57 0 58 0 59 0 60 0 61 0 62 0 63 0 64 0 65 0 66 0 67 0 68 0 69 0 70 0 71 0 72 0 73 0 74 0 39898 38757 37652 36583 35548 34545 33574 32634 31723 30840 29986...

Page 24: ...4 6 TABLE 8 RECOMMENDEDOPERATINGRANGES Rated CFM and ESP on high speed tap l e d o M d e t a R M F C d e t a R P S E d e d n e m m o c e R e g n a R w o l f r i A 1 8 3 H S 0 0 1 1 5 1 0 5 8 0 5 2 1 1...

Page 25: ...I 2 O 1 8 3 H S 1 9 4 H S 1 3 4 H S d e e p S h g i H d e e p S m u i d e M d e e p S w o L d e e p S h g i H d e e p S m u i d e M y r D l i o C t e W l i o C y r D l i o C t e W l i o C y r D l i o...

Page 26: ...ABLE COOLING Air Temperature Entering Outdoor Coil F l e d o M r i A n r u t e R e r u t a r e p m e T e r u s s e r P 5 7 0 8 5 8 0 9 5 9 0 0 1 5 0 1 0 1 1 5 1 1 1 8 3 H S B D g e d 5 7 B W g e d 2 6...

Reviews: