Manual   2100-410
Page    19

DEFROST CYCLE

The defrost cycle is controlled by temperature and time
on the solid state heat pump control.  See Figure 14.

When the outdoor temperature is in the lower 40° F
temperature range or colder, the outdoor coil
temperature is 32° F or below.  This coil temperature is
sensed by the coil temperature sensor mounted near the
bottom of the outdoor coil.  Once coil temperature
reaches 30° F or below, the coil temperature sensor
sends a signal to the control logic of the heat pump
control and the defrost timer will start.

After 60 minutes at 30° F or below, the heat pump
control will place the system in the defrost mode.

During the defrost mode, the refrigerant cycle switches
back to the cooling cycle, the outdoor motor stops,
electric heaters are energized, and hot gas passing
through the outdoor coil melts any accumulated frost.
When the temperature rises to approximately 57° F, the
coil temperature sensor will send a signal to the heat
pump control which will return the system to heating
operations automatically.

If some abnormal or temporary condition such as a high
wind causes the heat pump to have a prolonged defrost
cycle, the heat pump control will restore the system to
heating operation automatically after 10 minutes.

The heat pump defrost control board has an option of
30, 60 or 90 minutes setting.  All models are shipped
from the factory on the 60 minute pin.  If special
circumstances require a change to another time, remove
the wire from the 60 minute terminal and reconnect to
the desired terminal.  The manufacturer's
recommendation is for 60 minute defrost cycles.  Refer
to Figure 14

There is a cycle speed up jumper on the control.  This
can be used to reduce the time between defrost cycle
operation without waiting for time to elapse.

Use a small screwdriver or other metallic object, or
another 1/4 inch QC, to short between the SPEEDUP
terminals to accelerate the HPC timer and initiate
defrost.

Be careful not to touch any other terminals with the
instrument used to short the SPEEDUP terminals.  It
may take up to 10 seconds with the SPEEDUP
terminals shorted for  the speedup to be completed and
the defrost cycle to start.

As soon as the defrost cycle kicks in remove the
shorting instrument from the SPEEDUP terminals.
Otherwise the timing will remain accelerated and run
through the 1 minute minimum defrost length sequence
in a matter of seconds and will automatically terminate
the defrost sequence.

There is an initiate defrost jumper (sen jump) on the
control that can be used at any outdoor ambient during
the heating cycle to simulate a  0° coil temperature.
This can be used to check defrost operation of the unit
without waiting for the outdoor ambient to fall into the
defrost region.

By placing a jumper across the SEN JMP terminals (a
1/4 inch QC terminal works best) the defrost sensor
mounted on the outdoor coil is shunted out and will
activate the timing circuit.  This permits the defrost
cycle to be checked out in warmer weather conditions
without the outdoor temperature having to fall into the
defrost region.

In order to terminate the defrost test the SEN JMP
jumper must be removed.  If left in place too long the
compressor could stop due to the high pressure control

opening because of  high
pressure condition created by
operating in the cooling mode
with outdoor fan off.   Pressure
will rise fairly fast as there is
likely no actual frost on the
outdoor coil in this artificial
test condition.

There is also a 5 minute
compressor time delay function
built into the HPC.  This is to
protect the compressor from
short cycling conditions.  In some
instances it is helpful to the
service technician to override or
speed up this timing period, and
shorting out the SPEEDUP
terminals for a few seconds can
do this.

FIGURE  14

DEFROST CONTROL BOARD

MIS-1174

Summary of Contents for SH431

Page 1: ...LL MOUNTED PACKAGE HEAT PUMPS Models SH381 SH431 SH491 Manual 2100 410B Supersedes 2100 410A File Volume III Tab 17 Date 02 24 04 Bard Manufacturing Company Bryan Ohio 43506 Since 1914 Moving ahead ju...

Page 2: ...n Blade Setting Dimensions 22 Removal of Fan Shroud 22 Refrigerant Charge 22 Pressure Tables 24 Figures Figure 1 Unit Dimensions 3 Figure 2 Fresh Air Damper Assembly 6 Figure 3 Mounting Instructions 8...

Page 3: ...and Summer Air Conditioning Duct Design for Residential ACCA Manual D Winter and Summer Air Conditioning and Equipment Selection For more information contact these publishers ACCA Air Conditioning Co...

Page 4: ...entilator w Built in Exhaust FILTER OPTIONS X 1 Inch Throwaway Standard W 1 Inch Washable P 2 Inch Pleated COLOR OPTIONS X Beige Standard 4 Buckeye Gray COIL OPTIONS X Standard 1 Phenolic Coated Evapo...

Page 5: ...u S n r u t e R W D H A B C B E F G I J K L M N O P Q R S T 1 8 3 H S 1 3 4 H S 1 9 4 H S 5 7 0 2 4 2 3 4 2 2 5 7 8 4 8 8 8 9 8 8 9 2 8 8 5 1 8 8 9 2 8 8 3 4 0 1 9 1 6 6 1 3 0 0 0 3 8 6 2 3 4 9 6 2 9...

Page 6: ...r i W 2 d n u o r G e z i S e r i W T K C A T K C B T K C A T K C B T K C A T K C B T K C A T K C B Z 0 A 0 0 A 1 8 3 H S 5 0 A 8 0 A 0 1 A 1 8 0 2 0 3 2 1 2 r o 1 2 r o 1 2 r o 1 1 3 7 5 3 7 3 8 5 4...

Page 7: ...A 1 inch throwaway filter is supplied with each unit The filter slides into position making it easy to service This filter can be serviced from the outside by removing the service door A 1 inch washa...

Page 8: ...tion as required for Department of Energy Energyguide Fact Sheets is based upon the fresh air Blank off plate in place and is recommended for maximum energy efficiency The blank off plate is available...

Page 9: ...ch clearance is used for ease of installation and maintaining the required clearance to combustible material The supply air opening would then be 32 x 12 See Figures 3 and 4 for details WARNING Failur...

Page 10: ...time of installation MIS 1445 A Top flashing detail view Attach supplied rain flashing Apply caulk between flashing and wall Foam air seal Seal with bead of caulking along entire length of top Supply...

Page 11: ...ired for the first 3 feet of ducting It is important to insure that the 1 4 inch minimum spacing is maintained at all points Failure to do this could result in overheating the combustible material and...

Page 12: ...ORY SUPPLIED RAIN FLASHING MOUNT ON UNIT BEFORE INSTALLATION SEE UNIT DIMENSIONS FIGURE 1 FOR ACTUAL DIMENSIONS ATTACH TO TOP PLATE OF WALL 1 000 CLEARANCE ALL AROUND INTERIOR FINISHED WALL OVER FRAME...

Page 13: ...Manual 2100 410 Page 11 FIGURE 7 COMMONWALLMOUNTINGINSTALLATIONS FREE AIR FLOW NO DUCT DUCTED SUPPLY RETURN AT UNIT FALSE WALL INSTALLATION MIS 550 CLOSETINSTALLATION...

Page 14: ...ary high starting current of the compressor motor The disconnect access door on this unit may be locked to prevent unauthorized access to the disconnect To convert for the locking capability bend the...

Page 15: ...mechanical heating compressor off line and send the compressor signal to energize electric heat in its place to make electric heat first stage heating This can also be applied to bank the quantity of...

Page 16: ...This is done to maximize efficiency by utilizing the heat pump to bring the conditioned space temperature up rather than cycling on the electric heat due a second stage call for heat from the thermost...

Page 17: ...on indicating a problem COMPRESSOR MALFUNCTION LIGHT Actuation of the green check lamp is accomplished by a relay output from the heat pump control board which is factory installed Any condition such...

Page 18: ...le j k TABLE 4 WALLTHERMOSTATANDSUBBASECOMBINATIONS t a t s o m r e h T e s a b b u S s e r u t a e F t n a n i m o d e r P 5 4 0 3 0 4 8 1 6 7 1 A 1 4 8 T b l u b y r u c r e M t a e h g t s 2 l o o...

Page 19: ...ired If improper rotation is corrected at this time there will be no negative impact on the durability of the compressor However reverse operation for over one hour may have a negative impact on the b...

Page 20: ...CE OF OPERATION COOLING Circuit R Y makes at thermostat pulling in compressor contactor starting the compressor and outdoor motor The G indoor motor circuit is automatically completed on any call for...

Page 21: ...or other metallic object or another 1 4 inch QC to short between the SPEEDUP terminals to accelerate the HPC timer and initiate defrost Be careful not to touch any other terminals with the instrument...

Page 22: ...e c a l p e R t o n g n i s a h p r e w o P t c e r r o c e s a h p n o D E L d e r r o f k c e h C y l n o s t i n u e s a h p 3 r o t i n o m t i n u e h t o t s d a e l r e w o p o w t h c t i w S...

Page 23: ...48 0 49 0 50 0 51 0 52 0 53 0 54 0 55 0 56 0 57 0 58 0 59 0 60 0 61 0 62 0 63 0 64 0 65 0 66 0 67 0 68 0 69 0 70 0 71 0 72 0 73 0 74 0 39898 38757 37652 36583 35548 34545 33574 32634 31723 30840 29986...

Page 24: ...4 6 TABLE 8 RECOMMENDEDOPERATINGRANGES Rated CFM and ESP on high speed tap l e d o M d e t a R M F C d e t a R P S E d e d n e m m o c e R e g n a R w o l f r i A 1 8 3 H S 0 0 1 1 5 1 0 5 8 0 5 2 1 1...

Page 25: ...I 2 O 1 8 3 H S 1 9 4 H S 1 3 4 H S d e e p S h g i H d e e p S m u i d e M d e e p S w o L d e e p S h g i H d e e p S m u i d e M y r D l i o C t e W l i o C y r D l i o C t e W l i o C y r D l i o...

Page 26: ...ABLE COOLING Air Temperature Entering Outdoor Coil F l e d o M r i A n r u t e R e r u t a r e p m e T e r u s s e r P 5 7 0 8 5 8 0 9 5 9 0 0 1 5 0 1 0 1 1 5 1 1 1 8 3 H S B D g e d 5 7 B W g e d 2 6...

Reviews: