Manual 2100-676B
Page
40 of 88
FIGURE 31
Setting Controller Date and Time
4) Press UP or DOWN keys to scroll to
Date/Time
menu; press ENTER key.
5) Press ENTER key to scroll to the desired value
to be changed (see Figure 31).
6) Press UP or DOWN keys to change the value.
7) Press ESCAPE key several times to return to
Main Menu screen.
NOTE:
The LC6000 will sync the time and date
configured to each of the wall-mount units once
communication is established.
DOWN KEY
ALARM KEY
MENU KEY
UP KEY
ENTER KEY
ESCAPE KEY
FIGURE 33
LC6000 Controller Display and Interface (Status Screen Shown)
LC6000 interface key functions are the same as those shown for the TEC-
EYE in Figure 31 on page 34.
5. Configure Sensors
The system will need to be configured for the
number of temperature and humidity sensors
installed. The system is shipped with one
combination temperature and humidity sensor.
Additional combination sensors may be purchased
or alternatively, temperature-only sensors may be
purchased instead. The LC is capable of utilizing
four temperature sensors and three humidity
sensors. The system will need to be configured for
the various configurations.
If necessary, the sensors could be calibrated at this
time too. For information on calibrating the sensors
(adjusting the offset), see page 44.
To enable/disable
Zone 1 Indoor Humidity
:
1) Press MENU key to go to the Main Menu
screen.
2) Press UP or DOWN keys and ENTER key to
enter USER password 2000.
3) Press UP or DOWN keys to scroll to
IO Config
;
press ENTER key.
4) Press UP or DOWN keys to scroll to
Z1 Indoor
Hum C4
.
5) Press ENTER key to scroll to
Enable
(see
Figure 32).
6) Press UP or DOWN key to change value to ON
to enable sensor (or change value to OFF to
disable sensor).
FIGURE 32
Enable/Disable Zone 1 Indoor Humidity Sensor
To enable/disable
Zone 2 Indoor Humidity
:
1) Press MENU key to go to the Main Menu
screen.
2) Press UP or DOWN keys and ENTER key to
enter USER password 2000.
3) Press UP or DOWN keys to scroll to
IO Config
;
press ENTER key.
4) Press UP or DOWN keys to scroll to
Z2 Indoor
Hum C5
.
Summary of Contents for MULTI-TEC W24AAPA
Page 3: ...Page 3 of 88 SECTION 1 MULTI TEC LC6000 INSTALLATION INSTRUCTIONS...
Page 36: ...Manual 2100 676B Page 36 of 88 FIGURE 25 LC6000 Wiring Diagram...
Page 46: ...Manual 2100 676B Page 46 of 88...
Page 47: ...Manual 2100 676B Page 47 of 88 SECTION 2 WR SERIES LC6000 INSTALLATION INSTRUCTIONS...
Page 79: ...Manual 2100 676B Page 79 of 88 FIGURE 32 LC6000 Wiring Diagram...