Manual 2100-676B
Page
76 of 88
1. Route the cable from the first wall-mount unit to the
terminal block of the second wall-mount unit. If this is
the last unit to be connected, make a small service loop
and attach EMI filter as shown.
FIGURE 29
Communication Wiring: Termination at Additional Wall-Mount Units
2. Connect the wires matching the terminal
designations (+/-) of the controller terminals.
Cap the loose drain with a wire nut or
electrical tape.
3. Continue daisy chaining units by connecting
"+" to "+", "-" to "-" and wire nutting drain
together until last unit which is capped with
a wire nut.
Attach EMI filter as shown above
at last unit.
Up to 14 wall-mount units can
be connected and controlled by one LC6000
controller.
From Wall-Mount
Unit 1
1
2
4
5
7
9 10
8
12
14
16 17
3
6
11
13
15
Unit 2 Terminal Block
Wall-Mount Unit 2
From Wall-Mount
Unit 1
1
2
4
5
7
9 10
8
12
14
16 17
3
6
11
13
15
Unit 2 Terminal Block
–
+
–
+