3. Additional LV1000 Connections
There are factory-installed jumpers across terminals #8 and #9 (smoke detector), #10 and #11 (hydrogen detector)
and #12 and #13 (generator run). Remove the factory-installed jumpers before connecting to the detectors and/or
generator (if applicable).
INPUTS
LV1000 Connections
Sensor Connections
Description
Wire Mark
Terminal
Terminal
Smoke
DI1
8
Varies by sensor used. See general
wiring guideine in Figure x.x
Smoke Detector Input
GND
9
Ground
Hydrogen
DI2
10
Hydrogen Detector Input
GND
11
Ground
Generator
DI3
12
Generator Run Input
GND
13
Ground
Anti-Theft
DI4
14
Anti-Theft Device
GND
15
Ground
Power Loss
Relay - A1
230VAC Power Loss Relay
Relay - A2
230VAC Power Loss Relay
OUTPUTS
LV1000 Connections
External
Connections
Description
Wire Mark
Terminal
Terminal
Humidifier
NO1
34
Varies. See general wiring
guideine in Figure x.x
Humidifier Output
C1
35
Common
HVAC Fail
NO2
36
Alarm Relay – HVAC Fail
C1
37
Common
HVAC Maintenance
NO3
38
Alarm Relay –
HVAC Maintenance
C1
39
Common
Anti-Theft
NO4
40
Alarm Relay – Anti-Theft
C2
41
Common
COMMUNICATIONS
LV1000 Connections
External
Connections
Description
Wire Mark
Terminal
Terminal
Fieldbus 1*
FB-1 (–)
42
1
Wall Unit Daisy Chain
FB-1 (+)
43
2
Wall Unit Daisy Chain
Fieldbus 2*
FB-2 (–)
44
–
IPv6 SNMP Board
FB-2 (+)
45
+
Ground
Ground
FB-2 (–)
46
Shield
Shield for Daisy Chain
* Polarity Sensitive
Page
11 of 36