
Manual 2100-701
Page
8 of 16
6. Insert ventilator into the unit to the far left side,
making sure to clear the right filter bracket. Once
the ventilator is fully inserted, slide the ventilator
to the right until it is tight against the back of the
control panel (see Figure 3).
IMPORTANT NOTE:
Position front lip of ventilator
over front grille and on top of condenser partition
(see Figure 3 inset). This is important to ensure
proper drainage of any water entering damper
assembly.
FIGURE 3
Install Ventilator
7. Remove outer and inner control panel covers.
8. Remove female plug of high voltage wiring harness
(3-pin plug) from the heat recovery assembly
and snap into unit control panel (from inside
control panel) in the hole provided. Wire to top of
compressor contactor per wiring diagram (on ERV).
Connect high voltage plugs back together (see
Figure 3).
FIGURE 3 (INSET)
HIGH & LOW VOLTAGE
TO PLUG IN SIDE OF
CONTROL PANEL
SCREW
WHEN INSTALLING ERV-F POSITION
SO THAT HOLE IN FROM LIP IS
CENTERED OVER HOLE IN CONDENSER
GRILLE TO INSERT A SELF DRILLING
CAUTION: HOLE IN ERV-F MUST
BE USED TO INSURE CLEARANCE
FROM CONDENSER COIL TUBING
MIS-4004
CONDENSER
VENTILATOR
SERVICE DOOR
SIDE SECTION VIEW
BETWEEN THE CONDENSER
PARTITION
GRILL AND SERVICE DOOR
LIP OF ERV IS TO BE
HEAT RECOVERY
FRONT GRILLE
CAUTION: HOLE IN ERV-F MUST
BE USED TO ENSURE CLEARANCE
FROM CONDENSER COIL TUBING