background image

Manual 2100-701
Page 

3 of 16

WALL MOUNT ENERGY RECOVERY VENTILATOR MODEL NOMENCLATURE

GENERAL DESCRIPTION

The energy recovery ventilator was designed to provide 
energy efficient, cost effective ventilation to meet IAQ 
(Indoor Air Quality) requirements while still maintaining 
good indoor comfort and humidity control for a variety 
of applications such as schools, classrooms, lounges, 
conference rooms, beauty salons and others. It provides 
a constant supply of fresh air for control of airborne 
pollutants including CO

2

, smoke, radon, formaldehyde, 

excess moisture, virus and bacteria.

The ventilator incorporates patented rotary heat 
exchanger technology to remove both heat and moisture.

It is designed as a single package which can be easily 
factory or field installed for new installations or retrofit 
to the new Bard W**A and W**H series wall-mounted 
units. The package consists of a unique rotary energy 
recovery cassette that can be easily removed for 
cleaning or maintenance. The ERV-F*3 has two 13" 
diameter heat transfer wheels whereas the ERV-F*2 has 
one 13" diameter heat transfer wheel. The heat transfer 
wheels use a permanently bonded dry desiccant 
coating for total heat recovery.

Ventilation is accomplished with two blower/motor 
assemblies each consisting of a drive motor and dual 
blowers for maximum ventilation at low sound levels. 
The intake and exhaust blowers can be operated at the 
same speed (airflow rate) or different speeds to allow 
flexibility in maintaining desired building pressurization 
conditions. Factory shipped on medium intake and low 
exhaust. See Figure 6 on page 12 to change speeds. 

ELECTRICAL SPECIFICATIONS

The rotating energy wheels provide the heat transfer 
effectively during both summer and winter conditions. 
Provide required ventilation to meet the requirements 
of ASHRAE 62.1 standard.

NOTE:

  During operation below 5

°

F outdoor 

temperature, freezing of moisture in the heat 

transfer wheel can occur. Consult the factory if 

this possibility exists.

GENERAL INFORMATION

The ventilator should only be installed by a trained 
heating and air conditioning technician. These 
instructions serve as a guide to the technician installing 
the ventilator package. They are not intended as a step-
by-step procedure with which the mechanically inclined 
owner can install the package. 

The ventilator housing is shipped in one carton which 
contains the following:
•  Energy recovery ventilator
•  Exhaust damper assembly
•  Service door
•  Rain hood and mist eliminator
•  Installation instructions

UNPACKING

Upon receipt of the equipment, be sure to compare the 
model number found on the shipping label with the 
accessory identification information on the ordering and 
shipping document to verify that the correct accessory 
has been shipped.

Inspect the carton housing of each ventilator as it is 
received and, before signing the freight bill, verify that 
all items have been received and that there is no visible 
damage. Note any shortages or damage on all copies 
of the freight bill. The receiving party must contact 
the last carrier immediately, preferably in writing, 
requesting inspection by the carrier’s agent. Concealed 
damage not discovered until after loading must be 
reported to the carrier within 15 days of its receipt.

    

 

 

 

ERV    F  –  A    3

Energy Recovery Ventilator

Wall Mount Cabinet Size
2 – W18 thru W24A* and H*
3 – W30 thru W36A* and H*
 

(* revision 

letter

)

Electrical

A – 230/208 volt

C – 460 volt

Model

Voltage

Amps

Control 

Voltage

ERV-FA2
ERV-FA3

230/208

2.2

24V

ERV-FC2
ERV-FC3

460

1.2

24V

Fixed (24V ON/OFF)

Summary of Contents for ERV-FA2

Page 1: ...h Exhaust Models INSTALLATION INSTRUCTIONS ERV FA2 ERV FC2 ERV FA3 ERV FC3 Bard Manufacturing Company Inc Bryan Ohio 43506 www bardhvac com Manual 2100 701 Supersedes NEW Date 3 1 19 For Use with Bard...

Page 2: ...Ventilator Maintenance 14 Figures Figure 1 Remove Access Panels 6 Figure 2 Remove Filter Filter Support Bracket and Exhaust Cover Plate and Install Exhaust Damper Assembly 7 Figure 3 Install Ventilato...

Page 3: ...nergy wheels provide the heat transfer effectively during both summer and winter conditions Provide required ventilation to meet the requirements of ASHRAE 62 1 standard NOTE During operation below 5...

Page 4: ...3 4050 4050 4050 4050 4050 4050 4050 13500 7875 2813 0 0 10881 7394 4255 2511 2511 2511 2511 2511 2511 2511 8370 4883 1744 0 0 15788 10727 6173 3643 3643 3643 3643 3643 3643 3643 12145 7084 2530 0 0 9...

Page 5: ...7751 4460 3510 3510 3510 3510 3510 3510 3510 7897 4241 950 0 0 90 80 75 70 65 60 28080 19080 10980 6480 6480 6480 6480 6480 6480 6480 21600 12600 4500 0 0 17690 12020 6917 4082 4082 4082 4082 4082 408...

Page 6: ...W24AB A B W18HB A W24HB A B 230 208V 1 or 3 phase ERV FC2 W24AB C W24HB C 460V 3 phase ERV FA3 W30AB A B W36AB A B W30HB A B W36HB A B 230 208V 1 or 3 phase ERV FC3 W30AB C W36AB C W30HB C W36HB C 46...

Page 7: ...rn air filter Remove left side filter support bracket by unscrewing two 2 screws from left side of unit Remove and save top four 4 screws from front grille see Figure 2 5 Remove and discard exhaust co...

Page 8: ...age wiring harness 3 pin plug from the heat recovery assembly and snap into unit control panel from inside control panel in the hole provided Wire to top of compressor contactor per wiring diagram on...

Page 9: ...or timer See Control Wiring on page 11 FIGURE 4 Install Low and High Voltage Plugs and Wiring 11 Replace inner and outer control panel covers 12 Ventilator checkout A Resupply power to unit B Energize...

Page 10: ...ews 14 Replace the vent option access panel with the new panel provided Attach air intake hood with screws provided see Figure 5 Be sure to insert the top flange of the air intake hood into and throug...

Page 11: ...ontrol system that in some way can control the system based on occupancy IMPORTANT Operating the ERV F during unoccupied periods can result in a buildup of moisture in the structure Recommended Contro...

Page 12: ...Manual 2100 701 Page 12 of 16 FIGURE 6 Speed Tap Label...

Page 13: ...Manual 2100 701 Page 13 of 16 FIGURE 7 Airflow Diagram...

Page 14: ...ation systems energy transfer surfaces must be accessible for washing to remove oils grease tars and dirt that can impede performance or generate odors Washing of the desiccant surfaces is required to...

Page 15: ...result Do not disassemble and immerse the entire heat wheel in a soaking solution as bearing and other damage may result 3 Rinse wheel thoroughly after application of the cleaning solution and allow t...

Page 16: ...Manual 2100 701 Page 16 of 16 FIGURE 9 Hub Assembly with Ball Bearings...

Reviews: