Manual 2100-684B 
Page 

9 of 10

Reversing Valve Setup

1.  Press LEFT button two (2) times to return to 

ADDITIONAL SETUP.

2.  Press UP or DOWN buttons to scroll to VALVE (see 

Figure 11). 

 

NOTE:

 

VALVE does not show up on first screen

Continuing to press the UP or DOWN button 
will display VALVE.

3.  Press ENTER button to highlight choice of ACTIVE 

HTG or ACTIVE CLG. Press UP or DOWN button to 
toggle between the choices. Press ENTER button to 
save choice.

4.  Press LEFT button to return to the home screen.

DEHUMIDIFICATION

DEHUM: 

ENABLE

ALLOW HEATING DEHUM: YES
DEHUM SETPT: 60%RH
DEHUM SPAN: 5%RH

FIGURE 10

Dehumidification (Heat Pump)

ADDITIONAL SETUP

VENTILATION
FAN
HUMIDITY
MOTION SENSOR
SENSORS
STAGING

VALVE

FIGURE 11

Additional Setup (Heat Pump)

SYSTEM

SYSTEM ENABLE:

 AUTO

OCCUPANCY: SCHEDULE
OCC OVRIDE (MINS): 240
SCHEDULE

FIGURE 12

System Enable

System Enable

To enable heating or cooling from the home screen:

1.  Press RIGHT button to access the Main Menu 

screen.

2.  Press ENTER button to enter the SYSTEM menu 

(see Figure 12). 

3.  Press ENTER button to choose from available 

SYSTEM ENABLE options (use UP or DOWN 
buttons to scroll through choices):

 

• 

AUTO (factory default) = System is in “Auto-
Changeover” mode. HVAC system will cycle 
heating and cooling automatically to stay 
within preset heating and cooling setpoints.

 

• 

EMER HT = Aux heat only. Only available with 
unit type HP.

 

• 

OFF = HVAC system is inactive.

 

• 

COOLING = System is in “Cooling-Only” mode. 
HVAC system will cycle cooling in reference 
to cooling setpoint only. Unit will not activate 
heating sequence.

 

• 

HEATING = System is in “Heating-Only” mode. 
HVAC system will cycle heating in reference 
to heating setpoint only. Unit will not activate 
cooling sequence.

4.  Press ENTER button to save choice.

5.  Press LEFT button to return to the home screen.

Setpoints

To access setpoints from the home screen:

1.  Press RIGHT button to access the Main Menu screen.

2.  Press DOWN button to scroll to SETPOINTS. Press 

ENTER button (see Figure 13). Factory default 
values are shown in the figure.

SETPOINTS

COOL SETPT:

 74

°

F

COOL SETBACK: 80

°

F

HEAT SETPT: 70

°

F

HEAT SETBACK: 64

°

F

HUMIDITY
CO2 SETPT (PPM): 1200
CO2 SPAN (PPM): 200

FIGURE 13

Setpoints

3.  Press ENTER button to select COOL SETPT.

4.  Press UP or DOWN buttons to enter appropriate 

cooling setpoint. Press ENTER button to save new 
cooling setpoint.

5.  Press DOWN button to scroll to HEAT SETPT. Press 

ENTER button.

Summary of Contents for CompleteStat CS9B-THOA

Page 1: ...ION OPERATION QUICK START GUIDE Bard Manufacturing Company Inc Bryan Ohio 43506 www bardhvac com Manual 2100 684B Supersedes 2100 684A Date 1 12 22 CompleteStatTM Controller Models CS9B THOA CS9B THOCA CS9BE THOA CS9BE THOCA ...

Page 2: ...t Buttons and Screens 5 Figure 3 Application Menu 5 Figure 4 Additional Setup Air Conditioner 6 Figure 5 Fan Setup Air Conditioner 6 Figure 6 Dehumidification Air Conditioner 7 Figure 7 Additional Setup Heat Pump 7 Figure 8 Aux Heat Setup 7 Figure 9 Fan Setup Heat Pump 8 Figure 10 Dehumidification Heat Pump 9 Figure 11 Additional Setup Heat Pump 9 Figure 12 System Enable 9 Figure 13 Setpoints 9 NO...

Page 3: ...inward until they clear the cover Remove base plate from controller INSTALLATION 3 Route control wiring through base plate 4 With the embossed UP arrows of the base plate pointing in the appropriate direction fasten the base plate to the desired wall location A vertical horizontal 2x4 wall handybox can be used for the CO2 sensing CompleteStat and a vertical only 2x4 wall handybox can be used for n...

Page 4: ...l Setback 15 Heat Setback 16 Standby Time Minutes 17 Motion Sensing Daily Schedule 18 Date 19 Time 20 Occupied Minimum Cooling 21 Occupied Maximum Cooling 22 Unoccupied Minimum Cooling 23 Unoccupied Maximum Cooling 24 CO2 Setpoint 25 CO2 Span NOTES _______________________________________________________________________________________ _______________________________________________________________...

Page 5: ...conds factory default is 120 seconds See page 14 in the latest version of CompleteStat Controller Advanced Programming Features 2100 685 for information on adjusting the inactivity setting NOTE If the screen includes up and down arrows in the upper corners as shown in Figure 7 on page 7 additional choices can be found by continuing to press the UP or DOWN buttons MAIN MENU SYSTEM SETPOINTS DATE TI...

Page 6: ...NE No economizer or standard vent package ERV CRV MFAD EN DIS Economizer in system FAN SETUP SPEEDS CONSTANT SPEED OFF DELAY SECS 0 UNOCC AUTO OCC AUTO FIGURE 5 Fan Setup Air Conditioner 3 Press ENTER button to select save appropriate economizer option 4 Press LEFT button to go back to ADDITIONAL SETUP 5 The indoor blower can be set for ON or AUTO in either occupied or unoccupied conditions To acc...

Page 7: ...e 8 8 Press UP or DOWN button to scroll through AUX HEAT screen choices W O LOCKOUT Auxiliary heat will activate regardless of compressor operation or outdoor air temperature factory default If W O LOCKOUT is chosen proceed to set delay on time Step 9 COMP LOCKOUT Compressor locks out below the selected outdoor air temperature Requires optional Bard 8403 061 Outdoor Air Temperature Sensor NONE No ...

Page 8: ...TIONAL SETUP 7 The indoor blower can be set for ON or AUTO in either occupied or unoccupied conditions To access or change blower settings press DOWN button to scroll to FAN Press ENTER button to enter FAN SETUP see Figure 9 8 Press DOWN button to scroll through selections adjust as necessary Speeds Constant speed nonadjustable Off Delay 0 System fan will run for specified time after call ends 0 6...

Page 9: ...ns use UP or DOWN buttons to scroll through choices AUTO factory default System is in Auto Changeover mode HVAC system will cycle heating and cooling automatically to stay within preset heating and cooling setpoints EMER HT Aux heat only Only available with unit type HP OFF HVAC system is inactive COOLING System is in Cooling Only mode HVAC system will cycle cooling in reference to cooling setpoin...

Page 10: ... The controller will not allow heating cooling setpoints to contradict one another or to be within a degree of conflicting operation NOTE Any system startup with indoor ambient temperatures lower than 56 F or above 86 F or humidity higher than 65 will experience an internal Low Temperature or High Temperature alarm This will not affect normal operation and can be cleared easily Bard CompleteStat s...

Reviews: