Manual 2100-684B 
Page 

5 of 10

BASIC OPERATION

Basic Setup

These instructions are intended to provide the basic settings to get the equipment started.

FIGURE 2

CompleteStat Buttons and Home, Overide and Configuration Screens

Navigate the menus and change settings by pressing a 
combination of the four arrow buttons and the ENTER 
button.

• 

ENTER

 button to select and/or exit value editing

• 

UP

 or 

DOWN

 button to move among entries

• 

RIGHT

 or 

LEFT

 button to move among value fields

• 

LEFT

 button to return to the home screen

NOTE:

 

Although cooling/heating setpoints can be 
accessed by simply pressing the UP or DOWN 
buttons during normal operation, any changes 
made in this fashion will not be permanent 
but last only for a specific length of time as an 
“override” feature. See 

Setpoints

 on page 9 for 

further information.

NOTE:

 

The screen will revert back to the home screen 
if inactive for “X” number of seconds (factory 
default is 120 seconds). See page 14 in 
the latest version of 

CompleteStat Controller 

Advanced Programming & Features 2100-
685

 for information on adjusting the inactivity 

setting.

NOTE: 

If the screen includes up and down arrows in 
the upper corners (as shown in Figure 7 on 
page 7), additional choices can be found by 
continuing to press the UP or DOWN buttons.

MAIN MENU

SYSTEM

SETPOINTS
DATE/TIME
TECHNICIAN
ABOUT

APPLICATION

DEGREES:

 ºF

UNIT_TYPE: HP
OPT: 2 STAGES
ADDITIONAL SETUP

FIGURE 3

Application Menu

Quick Start Programming

System Selection

To select A/C or HP, stages of heating and cooling, and 
with/without economizer:

1. Press 

RIGHT button to access Main Menu screen.

2. Press 

DOWN button to scroll to TECHNICIAN. 

Press ENTER button.

3.  Controller will ask for password. Press UP and RIGHT 

buttons to enter ‘BARD’. Press ENTER button.

4.  Press ENTER button again to enter the 

APPLICATION menu (see Figure 3).

5.  Press ENTER button again to choose DEGREES.

NOTE:

 The UNIT_TYPE category must be set to “NOT 

CONFIGURED” before the controller will allow 
the scale to be changed (see step 7 on page 6). 

Summary of Contents for CompleteStat CS9B-THOA

Page 1: ...ION OPERATION QUICK START GUIDE Bard Manufacturing Company Inc Bryan Ohio 43506 www bardhvac com Manual 2100 684B Supersedes 2100 684A Date 1 12 22 CompleteStatTM Controller Models CS9B THOA CS9B THOCA CS9BE THOA CS9BE THOCA ...

Page 2: ...t Buttons and Screens 5 Figure 3 Application Menu 5 Figure 4 Additional Setup Air Conditioner 6 Figure 5 Fan Setup Air Conditioner 6 Figure 6 Dehumidification Air Conditioner 7 Figure 7 Additional Setup Heat Pump 7 Figure 8 Aux Heat Setup 7 Figure 9 Fan Setup Heat Pump 8 Figure 10 Dehumidification Heat Pump 9 Figure 11 Additional Setup Heat Pump 9 Figure 12 System Enable 9 Figure 13 Setpoints 9 NO...

Page 3: ...inward until they clear the cover Remove base plate from controller INSTALLATION 3 Route control wiring through base plate 4 With the embossed UP arrows of the base plate pointing in the appropriate direction fasten the base plate to the desired wall location A vertical horizontal 2x4 wall handybox can be used for the CO2 sensing CompleteStat and a vertical only 2x4 wall handybox can be used for n...

Page 4: ...l Setback 15 Heat Setback 16 Standby Time Minutes 17 Motion Sensing Daily Schedule 18 Date 19 Time 20 Occupied Minimum Cooling 21 Occupied Maximum Cooling 22 Unoccupied Minimum Cooling 23 Unoccupied Maximum Cooling 24 CO2 Setpoint 25 CO2 Span NOTES _______________________________________________________________________________________ _______________________________________________________________...

Page 5: ...conds factory default is 120 seconds See page 14 in the latest version of CompleteStat Controller Advanced Programming Features 2100 685 for information on adjusting the inactivity setting NOTE If the screen includes up and down arrows in the upper corners as shown in Figure 7 on page 7 additional choices can be found by continuing to press the UP or DOWN buttons MAIN MENU SYSTEM SETPOINTS DATE TI...

Page 6: ...NE No economizer or standard vent package ERV CRV MFAD EN DIS Economizer in system FAN SETUP SPEEDS CONSTANT SPEED OFF DELAY SECS 0 UNOCC AUTO OCC AUTO FIGURE 5 Fan Setup Air Conditioner 3 Press ENTER button to select save appropriate economizer option 4 Press LEFT button to go back to ADDITIONAL SETUP 5 The indoor blower can be set for ON or AUTO in either occupied or unoccupied conditions To acc...

Page 7: ...e 8 8 Press UP or DOWN button to scroll through AUX HEAT screen choices W O LOCKOUT Auxiliary heat will activate regardless of compressor operation or outdoor air temperature factory default If W O LOCKOUT is chosen proceed to set delay on time Step 9 COMP LOCKOUT Compressor locks out below the selected outdoor air temperature Requires optional Bard 8403 061 Outdoor Air Temperature Sensor NONE No ...

Page 8: ...TIONAL SETUP 7 The indoor blower can be set for ON or AUTO in either occupied or unoccupied conditions To access or change blower settings press DOWN button to scroll to FAN Press ENTER button to enter FAN SETUP see Figure 9 8 Press DOWN button to scroll through selections adjust as necessary Speeds Constant speed nonadjustable Off Delay 0 System fan will run for specified time after call ends 0 6...

Page 9: ...ns use UP or DOWN buttons to scroll through choices AUTO factory default System is in Auto Changeover mode HVAC system will cycle heating and cooling automatically to stay within preset heating and cooling setpoints EMER HT Aux heat only Only available with unit type HP OFF HVAC system is inactive COOLING System is in Cooling Only mode HVAC system will cycle cooling in reference to cooling setpoin...

Page 10: ... The controller will not allow heating cooling setpoints to contradict one another or to be within a degree of conflicting operation NOTE Any system startup with indoor ambient temperatures lower than 56 F or above 86 F or humidity higher than 65 will experience an internal Low Temperature or High Temperature alarm This will not affect normal operation and can be cleared easily Bard CompleteStat s...