Manual 7960-857
Page 

2 of 3

Installation

Disconnect all power to wall-mount unit. Remove outer 
and inner control panel covers.
1.  Mount the 910-2069 relay assembly in the control 

panel as shown in Figure 1.   

2.  Route the wires in the cable duct. Connect the 

4 pin male plug to the female plug on the side 
of the low voltage terminal box. Connect the 
pink wire to the ALR terminal on the compressor 
control module. Refer to Figure 2 on page 3 or 
the unit wiring diagram for proper wire connection 
locations.   

3.  Make the desired dry contact connections on the 

front of the low voltage terminal strip. (Normally 
Closed = 1 & 3, or Normally Open = 2 & 3). See 
Figure 2 or the unit wiring diagram. 

4.  Apply “This unit is equipped with CMC-35 control 

module” label to the inside of the inner control 
panel cover above the unit wiring diagram.

5.  Replace the inner and outer control panel covers. 

This completes the installation.

Sequence of Operation

When installed, the alarm relay will indicate one of the 
following has occurred:
•  High refrigerant pressure lockout
•  Low refrigerant pressure lockout
•  Unit power brownout lockout
During any of the listed events, an alarm can be 
signaled to a thermostat or controlling device. The unit 
will remain in a lockout mode until the call for cooling 
is removed (Y1, Y2) or power is reset to the unit.

FIGURE 1

CONTROL ASSEMBLY

PART #910-2069

4 PIN PLUG (MALE)

PLUGS INTO THE SIDE

OF THE LOW VOLTAGE

TERMINAL BLOCK

MIS-4096