Installation & Operating Instructions

“BAPI-Stat 3” Room Sensor

Building Automation Products, Inc., 750 North Royal Avenue, Gays Mills, WI  54631 USA

Tel:+1-608-735-4800 • Fax+1-608-735-4804 • E-mail:[email protected] • Web:www.bapihvac.com

Specifications subject to change without notice.

rev. 01/30/14

24694_ins_BS3

3 of 6

Termination

Table 1: 

TerminationTable

* [CH3] and [CH4] are referenced to [GND] if (CG) is selected at time of order.  [CH3] and [CH4] are referenced to each other if (DF) is selected at time of order.
** S1-4, Position (CG) connects [Temp-] terminal to the [GND] terminal internally. The (DF) position makes the [TEMP -] terminal floating. (See Fig.10)
*** This is the current output of the solid state sensor and must be configured as S1-4 set to (DF) to allow the 592 or 334 sensor to operate.
^ The reed contact to override [CH4] can be set up for (CG) which shorts the [CH4] output to [GND] or (DF) shorting the output terminals [CH3/CH4].
^^ The E-POT controls the output resistance setpoint and during override, the E-POT controls the resistance to <100 ohms for 3-5 seconds.
^^^ A reed dry contact across the sensor [TEMP+/-] is configured at time of order as a (-61) option.
~ The [TEMP] terminals are used for an external 10K-2 thermistor connection if the [EXT option] is selected. (wire=25’ max)

Input Power

Terminal 

Name

  GND

 

Pwr- & Sig-                     -------------- Sensor Power Connection--------- 

 

 

Sig- 

Sig- 

**, ^ 

** 

***

 

V+

 

DC or AC                      -------------- Sensor Power Connection--------- 

 

 

 

 

 

 

 

  

 

CH1

 

 

CG 

 

 

Sig+ 

mA + 

 

 

 

  

 

CH2

 

 

CG 

 

 

Sig+ 

mA+ 

 

 

 

  

 

CH3

 

 

CG/DF* per order 

 

 

^^E-POT 

Sig+ 

 

^^*<100KΩ 

*E-POT 

 

 

 

CH4

 

 

CG/DF* per order 

 

 

^^E-POT/^N.O. 

Sig+ 

 

^^*<100KΩ  *E-POT/^N.O. 

 

 

 

TEMP+

 

 

 

Sensor 

 

 

 

^^^N.O 

 

N.O. 

Sensor 

V+

 

TEMP-

 

 

CG/DF, S1-4** 

Sensor 

 

 

 

^^^N.O. 

 

**N.O. 

Sensor 

***V-

Supply 

Power

Internal 

Grounding 

CG=Com. GND 

DF=Isolated

Passive 

RTD or 

Thermistor 

Sensor

592/334 

Solid 

State 

Sensor

Temperature 

Output

Override 

Output

Voltage 

Output

Current 

Output

Resistive 

Output

Signal Override 

Contact

Temperature 

Setpoint 

Output

Humidity 

Setpoint 

Output

Humidity 

Output

Output Variable 

(See your unit label for your configuration)

Output Signal 

(See your unit label for your configuration)

See Table 1 

for terminal 

description

Factory 

setup switch

Occupied/

un-occupied 

BAPI-Man 

power 

(see Table 2, 

Fig 5 & 6)

BAPI recommends

 using twisted pair of at least 22 AWG. Larger gauge wire may be required for long runs. All wiring 

must comply with the National Electric Code (NEC) and local codes. 

Do NOT

 run this device’s wiring in the same conduit 

as AC power wiring of NEC class 1, NEC class 2, NEC class 3 or with wiring used to supply highly inductive loads such 

as motors, contactors and relays. BAPI’s tests show that fluctuating and inaccurate signal levels are possible when AC 

power wiring is present in the same conduit as the signal lines.  

Fig. 4: 

BAPI-Stat Circuit Board

Terminal Notes: (Related to table 1), [  ] = Terminal designation

1.  Only one variable and output type per channel.  [CH3] and [CH4] can be 

overridden. 

2.  The [GND] terminal is always the reference for [V+], [CH1] and [CH2] 

terminals.

3.  The temperature output range is limited to between 32º to 158ºF  

(0º to 70ºC).

4.  Humidity setpoint range is limited between 0 to 100% RH. 
5.  The override is available on [CH3], [CH4] and [TEMP+/TEMP-] only.
6.  Voltage outputs are limited to between 0 to 10 VDC and are only  

referenced to [GND].

7.  Current outputs are limited to between 0 to 20 mA and are only refer-

enced to [GND].

8.  Resistive E-POT outputs are limited to a 1K, 10K, 50K or 100K

W

 linier 

POT, ±30%. 

9.  Resistive sensor [TEMP+/TEMP-] outputs may be any BAPI passive or 

solid state sensor.

10. When using a 592/334 sensor, [TEMP+] is the supply (5 to 30 VDC)  

[TEMP-] is the current output to the analog input @ 1µA/ºC and requires 

S1-4 to be set for (DF).  Reversal of the power will damage the sensor. 

11.  The Test and Balance option (-TB) cannot be used with the 592/334 sen-

sor.

12. If the BAPI-Stat has the external sensor option (-EXT), then it must be a 

10K-2 thermistor purchased separately. The external sensor is wired to 

the temp + and temp - terminals. A humidity signal or passive sensor are 

not allowed in this configuration.