Installation & Operating Instructions

“BAPI-Stat 3” Room Sensor

Building Automation Products, Inc., 750 North Royal Avenue, Gays Mills, WI  54631 USA

Tel:+1-608-735-4800 • Fax+1-608-735-4804 • E-mail:[email protected] • Web:www.bapihvac.com

Specifications subject to change without notice.

rev. 01/30/14

24694_ins_BS3

4 of 6

When the override button is pushed, the override output is active for 

3 to 5 seconds. Simultaneously, the outline and center of the 

HUMAN 

ICON

 on the display will be filled in for 3 to 5 seconds and then go 

blank.
If you need visual indication of the override on the LCD display, the 

controller must have a digital output connected to the sensor’s three-

pin EXT OVR terminal block, J6.  
When appropriate power is connected between the EXT OVR common 

and either 5 VDC or 24 VDC/VAC, both 

the outline and center of the 

HUMAN 

ICON

 will be filled in.  When the external override is canceled, the 

HUMAN ICON’S

 outline will 

remain filled in to show that the external override was used.  
If power to the sensor is removed, the outline will be blank until the next time the external 

override is used. 

This input is optically isolated from the rest of the device’s circuitry.

Display Occupancy Termination Mode (Remote Control)

Fig. 5: 

5VDC Wiring Example

Controller 

Digital 

Output

EXT OVR Display Input

EXT OVR Display Input

5VDC Customer 

Power Supply

Controller Output OPEN =             Controller Output CLOSED (Override) = 

24DC/AC 

Customer 

Power Supply

Fig. 7: 

C11 Jack

Fig. 8: 

C35 Jack

Note:

 Male Jack shown for clarity

Fig. 9: 

View of

BAPI-Stat 3 

wallplate

Optional Communication Jack Wiring

Optional Communication Jack Termination Wiring

Table: 3 

C11/22 Wiring

 Comm Jack Pin 

Wire Color

 

Not Connected 

 

Black 

 

Red 

 

Yellow 

 

White or Green 

 

Not Connected

Table: 4 C35 Female Jack Wiring

 Comm Jack Pin 

Wire Color

 

Ground 

White 

 

Tip 

Black 

 

Ring 

Red

Test & Balance Switch (-TB), (For Passive Sensor Ouput Only)

Optional Test and Balance Switch (SW1)

Norm: Thermistor/RTD will operate normally

High: Will set the sensor value high

Low: Will set the sensor value low

(Output at Temp+ and Temp- Terminals)

Table: 5 

Low Temperature (40º F)  High Temperature (105º F) 

Sensor Type 

Resistance Value 

Resistance Value

1000 RTD 

1.02K 

(41.2ºF) 

1.15K 

(101.5ºF) 

3000 Thermistor 

7.87K 

(39.8ºF) 

1.5 

(106.8ºF) 

10K-2 Thermistor 

30.1K 

(34.9ºF) 

4.75K 

(109.1ºF) 

10K-3 Thermistor 

26.7K 

(35.9ºF) 

5.11K 

(108.4ºF) 

10K-3(11K) Thermistor 

7.32K 

(43.7ºF) 

3.65K 

(105.2ºF)

Fig. 6: 

24VDC/VAC Wiring Example

Controller 

Digital 

Output

Table 2: 

Override Display Termination Table

This [COMMON] is isolated from the other [GND] 

terminal. See Figures 5 & 6 for more details.

Terminal 

Name

ICON

 

ON

5VDC

ICON ON

24VDC

ICON ON

24VAC

COMMON

5VDC

-

+

+

-

~N

~H

24V DC/VAC

Consult Factory for Additional Details

 Human Icon 

Outline

 Human Icon 

Filled In

C11

C35