background image

1. Unscrew the four screws that mount the cover to the bottom housing.
2. Remove the cover from the housing without damaging the ribbon cable or the pins the cable plugs into.
3. Gently unplug the ribbon cable from the board mounted into the bottom housing.
4. Remove the black cover plate from the bottom of the device's cover.

The DIP switches are located behind the rotary dials.

After making the necessary changes to the DIP switches, place the black cover plate back into position and
gently push into place. Plug the ribbon cable in after verifying that the blocked hole lines up with the missing
pin. Mount the cover back onto the housing.

DIP Switch Settings

Switches

Device Settings

1

2

3

4

5

6

7

8

Rotary switch address mode

OFF*

Extended address mode

ON

Modbus or UCT configured (overrides DIP
switches 3-8)

OFF*

DIP switch configured

ON

Link loss output: zero

OFF*

OFF*

Link loss output: one

OFF

ON

Link loss output: hold last state

ON

OFF

Link loss output: user configuration

ON

ON

0–20 mA scale (Not used on 0–10V I/O models.)

OFF*

4–20 mA scale (Not used on 0–10V I/O models.)

ON

* Default configuration
Address Mode
The SureCross wireless devices may use one of two types of addressing modes: rotary dial addressing or extended addressing. In
rotary dial address mode, the left rotary dial establishes the network ID and the right rotary dial sets the device ID. The wireless network
is restricted to a maximum of 16 devices.
Extended address mode uses a security code to "bind" Nodes to a specific Gateway. Bound Nodes can only send and receive informa-
tion from the Gateway to which they are bound. In extended address mode, wireless networks may contain up to 48 radio devices. For
more information on extended address mode, refer to the SureCross

 Wireless I/O Network product manual.

The device ships in rotary dial address mode by default, with the DIP switch in the OFF position. To use extended address mode, change
the DIP switch to the ON position.
Link Loss Outputs
The SureCross DX80 wireless devices use a deterministic radio link time-out method to address RF link interruption or failure. When a
radio link fails, all pertinent wired outputs are sent to defined states until the link is recovered, ensuring that disruptions in the communica-
tions link result in predictable system behavior.

Following a radio link time-out, all outputs linked to the Node in question are set to de-energize (discrete outputs to zero, analog outputs
to 0 mA or 4 mA), energize (discrete outputs to one, analog outputs to 20 mA), or to hold the last stable state/value. Use the DIP switches
to select the link loss output state.
Modbus/User Configuration Tool (UCT) or DIP Switch Configured
In Modbus/UCT Configured mode, the device parameters are changed using the User Configuration Tool (UCT) or a Modbus command.
All DIP switch positions are ignored. In DIP Switch Configured mode, use the DIP switches to configure the parameters listed in the table.

SureCross DX80 Gateway

 

 

P/N 136325 Rev. F

www.bannerengineering.com - tel: 763-544-3164

3

Summary of Contents for SureCross DX80G9M6S0P0V4V4C

Page 1: ...ian Electrical Code or applicable local codes regulations see Specifications Models Frequency Environmental Rating I O DX80G9M6S0P0V4V4 900 MHz ISM Band IP67 NEMA 6 Inputs Four 0 to 10V analog Outputs...

Page 2: ...n gineering com wireless Setting Up Your Wireless Network To set up and install your wireless network follow these steps 1 Configure the DIP switches of all devices 2 Connect the sensors to the SureCr...

Page 3: ...m of 16 devices Extended address mode uses a security code to bind Nodes to a specific Gateway Bound Nodes can only send and receive informa tion from the Gateway to which they are bound In extended a...

Page 4: ...dc common GND dc common GND dc common GND Rx RS485 D0 A B 3 6 to 5 5V dc Terminal Blocks Connecting dc power to the communication pins will cause permanent damage Do not exceed analog input ratings fo...

Page 5: ...should be at least two meters apart or the communications may fail LED 1 LED 2 Gateway Status solid green Power ON flashing red flashing red Device Error flashing yellow Modbus Communication Active f...

Page 6: ...247 ETSI EN In accordance with EN 300 328 V1 7 1 2006 05 IC 7044A DX8024 Spread Spectrum Technology FHSS Frequency Hopping Spread Spectrum Link Timeout Gateway Configurable Node Defined by Gateway Rad...

Page 7: ...waterproofing instructions Op erating the devices at the maximum operating conditions for exten ded periods can shorten the life of the device Certifications DX8x C External Wiring Terminal Models CS...

Page 8: ...to change Banner reserves the right to modify product specifications or to update docu mentation at any time For the most recent version of any documentation refer to www bannerengineering com 2006 20...

Reviews: