Analog Input Wiring (10–30 V dc Power)

Analog Input Wiring (4–20 mA, 2-Wire, Externally-Powered

Sensors)

Analog IN

PWR

10-30V dc

GND

+

sensor

dc common

Analog IN

GND

dc common

external power

+

sensor

Set the 

MultiHop

 Radio (Slave) ID

On a 

MultiHop

 radio, use the rotary dials to set the device’s 

MultiHop

 Radio ID.

Modbus Slave IDs 01 through 10 are reserved for slaves directly connected to the host (local I/O).

Polling messages addressed to these devices are not relayed over the wireless link. Use Modbus Slave

IDs 11 through 60 for 

MultiHop

 master, repeater, and slave radios. Up to 50 devices (local slaves and

remote slaves) may be used in this system.
With the 

left

 dial 

acting

 as the 

left

 digit and the right dial 

acting

 as the right digit, the 

MultiHop

 Radio

ID can be set from 01 through 60.

MultiHop

 

Configuration

 Tool

Use Banner’s 

MultiHop

 

Configuration

 Tool 

software

 to view your 

MultiHop

 radio network and 

configure

 the radio and its I/O.

The 

MultiHop

 

Configuration

 Tool connects to a 

MultiHop

 master radio using one of

four methods.

• Serial; using a USB to RS-485 (for RS-485 radios) or a USB to RS-232 (for

RS-232 radios) converter cable.

• Modbus TCP; using an Ethernet 

connection

 to an Ethernet radio master.

• Serial DXM; using a USB cable to a DXM Controller to access a 

MultiHop

master radio.

• TCP DXM: using an Ethernet 

connection

 to a DXM Controller to access a

MultiHop

 master radio.

For 

MultiHop

 DX80DR* models, Banner recommends using BWA-UCT-900, an RS-485 to USB adapter cable with a wall plug that can

power your 1 

Watt

 

MultiHop

 radio while you 

configure

 it. The adapter cable is not required when 

connecting

 to a DXM Controller.

Download the most recent 

software

 revision from Banner Engineering's website: 

www.bannerengineering.com/wireless

.

Installing Your Sure Cross

®

 Radios

Please refer to one of the following 

instruction

 manuals for details about successfully installing your wireless network components.

MultiHop

 Data Radio 

Instruction

 Manual: 

151317

Modbus Registers

Register

(4xxxx)

Input #

Input Type

Units

I/O Range

Holding Register

Representation

Terminal Block

Labels

Min. Value

Max. Value

Min. (Dec.)

Max. (Dec.)

1

1

Discrete IN 1

-

0

1

0

1

DI1

2

2

Discrete IN 2

-

0

1

0

1

DI2

3

3

Discrete IN 3

-

0

1

0

1

DI3

4

4

Discrete IN 4

-

0

1

0

1

DI4

5

5

Analog IN 1

mA

0.0

20.0

0

65535

AI1

6

6

Analog IN 2

mA

0.0

20.0

0

65535

AI2

7

7

Analog IN 3

mA

0.0

20.0

0

65535

AI3

8

8

Analog IN 4

mA

0.0

20.0

0

65535

AI4

Sure Cross

®

 

MultiHop

 Data Radio

 

 

P/N 152416 Rev. H

www.bannerengineering.com - Tel: +1-763-544-3164

5

Summary of Contents for Sure Cross MultiHop DX80DR9M-H5

Page 1: ...ensing device for personnel protection Doing so could lead to serious injury or death This device does not include the self checking redundant circuitry necessary to allow its use in personnel safety...

Page 2: ...ltiHop Data Radio Instruction Manual 151317 MultiHop Register Guide End User Edition 155289 Configure the DIP Switches Before changing DIP switch positions disconnect the power DIP switch changes are...

Page 3: ...ets to provide better throughput In transparent mode there is no access to the radio s I O Baud Rate and Parity The baud rate bits per second is the data transmission rate between the device and whate...

Page 4: ...D DI4 GND DO2 DI2 SP3 AI3 AI1 GND DI3 GND DO1 DI1 G B W TX RX B V V V AI4 SP4 SP3 AI3 AI2 DI4 DO2 DI2 DI1 DO1 DI3 AI1 AIx or Ax Analog IN x DIx Discrete IN x DOx Discrete OUT x GND Ground dc common co...

Page 5: ...using an Ethernet connection to an Ethernet radio master Serial DXM using a USB cable to a DXM Controller to access a MultiHop master radio TCP DXM using an Ethernet connection to a DXM Controller to...

Page 6: ...ed together based on the I O type number analog 1 analog 2 counter 1 etc Not all inputs or outputs may be available for all models To determine which specific I O is available on your model refer to t...

Page 7: ...This device complies with FCC Part 15 Subpart C 15 247 ETSI EN 300 328 V1 8 1 2012 04 IC 7044A DX8024 Communication Hardware MultiHop RS 485 Interface 2 wire half duplex RS 485 Baud rates 9 6k 19 2k d...

Page 8: ...g other antennas verify you are not exceeding the transmit power levels allowed by local governing agencies Consult with Banner Engineering Corp if the destination country is not on this list Banner E...

Reviews: