Analog Input Wiring (10–30 V dc Power)
Analog Input Wiring (4–20 mA, 2-Wire, Externally-Powered
Sensors)
Analog IN
PWR
10-30V dc
GND
−
+
sensor
dc common
Analog IN
GND
dc common
external power
−
+
sensor
Set the
MultiHop
Radio (Slave) ID
On a
MultiHop
radio, use the rotary dials to set the device’s
MultiHop
Radio ID.
Modbus Slave IDs 01 through 10 are reserved for slaves directly connected to the host (local I/O).
Polling messages addressed to these devices are not relayed over the wireless link. Use Modbus Slave
IDs 11 through 60 for
MultiHop
master, repeater, and slave radios. Up to 50 devices (local slaves and
remote slaves) may be used in this system.
With the
left
dial
acting
as the
left
digit and the right dial
acting
as the right digit, the
MultiHop
Radio
ID can be set from 01 through 60.
MultiHop
Configuration
Tool
Use Banner’s
MultiHop
Configuration
Tool
software
to view your
MultiHop
radio network and
configure
the radio and its I/O.
The
MultiHop
Configuration
Tool connects to a
MultiHop
master radio using one of
four methods.
• Serial; using a USB to RS-485 (for RS-485 radios) or a USB to RS-232 (for
RS-232 radios) converter cable.
• Modbus TCP; using an Ethernet
connection
to an Ethernet radio master.
• Serial DXM; using a USB cable to a DXM Controller to access a
MultiHop
master radio.
• TCP DXM: using an Ethernet
connection
to a DXM Controller to access a
MultiHop
master radio.
For
MultiHop
DX80DR* models, Banner recommends using BWA-UCT-900, an RS-485 to USB adapter cable with a wall plug that can
power your 1
Watt
MultiHop
radio while you
configure
it. The adapter cable is not required when
connecting
to a DXM Controller.
Download the most recent
software
revision from Banner Engineering's website:
www.bannerengineering.com/wireless
.
Installing Your Sure Cross
®
Radios
Please refer to one of the following
instruction
manuals for details about successfully installing your wireless network components.
•
MultiHop
Data Radio
Instruction
Manual:
Modbus Registers
Register
(4xxxx)
Input #
Input Type
Units
I/O Range
Holding Register
Representation
Terminal Block
Labels
Min. Value
Max. Value
Min. (Dec.)
Max. (Dec.)
1
1
Discrete IN 1
-
0
1
0
1
DI1
2
2
Discrete IN 2
-
0
1
0
1
DI2
3
3
Discrete IN 3
-
0
1
0
1
DI3
4
4
Discrete IN 4
-
0
1
0
1
DI4
5
5
Analog IN 1
mA
0.0
20.0
0
65535
AI1
6
6
Analog IN 2
mA
0.0
20.0
0
65535
AI2
7
7
Analog IN 3
mA
0.0
20.0
0
65535
AI3
8
8
Analog IN 4
mA
0.0
20.0
0
65535
AI4
Sure Cross
®
MultiHop
Data Radio
P/N 152416 Rev. H
www.bannerengineering.com - Tel: +1-763-544-3164
5