background image

Wiring Power and Ground

Connecting

 power to the 

communication

 pins will cause permanent damage. For FlexPower devices, do not apply more than 5.5 V to

the gray wire. The FlexPower 

MultiHop

 radios operate equally well when powered from the brown or gray wire; it is not necessary to

supply both. The power for the sensors can be supplied by the radio's SPx terminals or from the 10 to 30 V dc used to power the radio.

5-pin M12/Euro-style Male Connector

Pin

Wire Color

Wiring 

Description

1

4

5

3

2

1

Brown

10 to 30 V dc

2

White

RS-485 / D1 / B / +

3

Blue

dc common (GND)

4

Black

RS-485 / D0 / A / -

5

Gray

3.6 to 5.5 V dc

Wiring for DX80...M-HxC Models for Power and Ground

Connecting

 power to the 

communication

 pins will cause permanent damage. For FlexPower devices, do not apply more than 5.5 V to

the gray wire. The FlexPower 

MultiHop

 radios operate equally well when powered from the brown or gray wire; it is not necessary to

supply both. The power for the sensors can be supplied by the radio's SPx terminals or from the 10 to 30 V dc used to power the radio.

Terminal

Wiring 

Description

V+

10 to 30 V dc

Tx/+

RS-485 / D1 / B / +

V-

dc common (GND)

Rx/-

RS-485 / D0 / A / -

B+

3.6 to 5.5 V dc

Terminal Blocks

M-H5 Models

M-H5C Models

SP4

AI4
AI2

GND
DI4

GND
DO2

DI2

SP3

AI3
AI1

GND
DI3

GND
DO1

DI1

G B − W +

TX/+

RX/−

B+

V−

V+

V−

AI4

SP4

SP3

AI3

AI2

DI4

DO2

DI2

DI1

DO1

DI3

AI1

AIx or Ax. Analog IN x

DIx. Discrete IN x

DOx. Discrete OUT x

GND. Ground/dc common 

connection

SPx. Switch Power; provides variable

power sources for external devices

B+. 3.6 to 5.5 V dc (use for 

battery

powered models only)

PWR. 10 to 30 V dc power 

connection

RX/-. Serial 

communication

 line for the

Gateway. No 

connection

 for Nodes

TX/+. Serial 

communication

 line for the

Gateway; no 

connection

 for Nodes

V+. 10 to 30 V dc power 

connection

V–. Ground/dc common 

connection

Connecting

 power to the 

communication

 pins will cause permanent damage. For the DX8x...C models, PWR in the wiring diagram refers

to V+ on the wiring board and GND in the wiring diagram refers to V- on the wiring board. To power the sensor using the switch power

output (SPx), replace the PWR with SPx in these wiring diagrams. Refer to the Class I Division 2/Zone 2 control drawings (p/n 

143086

)

for wiring 

specifications

 or 

limitations.

Discrete Input Wiring for PNP Sensors

Discrete Input Wiring for NPN Sensors

Discrete Output Wiring (NPN or NMOS)

Discrete IN

PWR

10-30V dc

Discrete IN

GND

dc common

Load

Discrete OUT

GND

PWR

10–30 V dc

dc common

Do not exceed analog input 

ratings

 for analog inputs. Only connect sensor outputs to analog inputs.

 

 

Sure Cross

®

 

MultiHop

 Data Radio

4

www.bannerengineering.com - Tel: +1-763-544-3164

P/N 152416 Rev. H

Summary of Contents for Sure Cross MultiHop DX80DR9M-H5

Page 1: ...ensing device for personnel protection Doing so could lead to serious injury or death This device does not include the self checking redundant circuitry necessary to allow its use in personnel safety...

Page 2: ...ltiHop Data Radio Instruction Manual 151317 MultiHop Register Guide End User Edition 155289 Configure the DIP Switches Before changing DIP switch positions disconnect the power DIP switch changes are...

Page 3: ...ets to provide better throughput In transparent mode there is no access to the radio s I O Baud Rate and Parity The baud rate bits per second is the data transmission rate between the device and whate...

Page 4: ...D DI4 GND DO2 DI2 SP3 AI3 AI1 GND DI3 GND DO1 DI1 G B W TX RX B V V V AI4 SP4 SP3 AI3 AI2 DI4 DO2 DI2 DI1 DO1 DI3 AI1 AIx or Ax Analog IN x DIx Discrete IN x DOx Discrete OUT x GND Ground dc common co...

Page 5: ...using an Ethernet connection to an Ethernet radio master Serial DXM using a USB cable to a DXM Controller to access a MultiHop master radio TCP DXM using an Ethernet connection to a DXM Controller to...

Page 6: ...ed together based on the I O type number analog 1 analog 2 counter 1 etc Not all inputs or outputs may be available for all models To determine which specific I O is available on your model refer to t...

Page 7: ...This device complies with FCC Part 15 Subpart C 15 247 ETSI EN 300 328 V1 8 1 2012 04 IC 7044A DX8024 Communication Hardware MultiHop RS 485 Interface 2 wire half duplex RS 485 Baud rates 9 6k 19 2k d...

Page 8: ...g other antennas verify you are not exceeding the transmit power levels allowed by local governing agencies Consult with Banner Engineering Corp if the destination country is not on this list Banner E...

Reviews: