Wiring Power and Ground
Connecting
power to the
communication
pins will cause permanent damage. For FlexPower devices, do not apply more than 5.5 V to
the gray wire. The FlexPower
MultiHop
radios operate equally well when powered from the brown or gray wire; it is not necessary to
supply both. The power for the sensors can be supplied by the radio's SPx terminals or from the 10 to 30 V dc used to power the radio.
5-pin M12/Euro-style Male Connector
Pin
Wire Color
Wiring
Description
1
4
5
3
2
1
Brown
10 to 30 V dc
2
White
RS-485 / D1 / B / +
3
Blue
dc common (GND)
4
Black
RS-485 / D0 / A / -
5
Gray
3.6 to 5.5 V dc
Wiring for DX80...M-HxC Models for Power and Ground
Connecting
power to the
communication
pins will cause permanent damage. For FlexPower devices, do not apply more than 5.5 V to
the gray wire. The FlexPower
MultiHop
radios operate equally well when powered from the brown or gray wire; it is not necessary to
supply both. The power for the sensors can be supplied by the radio's SPx terminals or from the 10 to 30 V dc used to power the radio.
Terminal
Wiring
Description
V+
10 to 30 V dc
Tx/+
RS-485 / D1 / B / +
V-
dc common (GND)
Rx/-
RS-485 / D0 / A / -
B+
3.6 to 5.5 V dc
Terminal Blocks
M-H5 Models
M-H5C Models
SP4
AI4
AI2
GND
DI4
GND
DO2
DI2
SP3
AI3
AI1
GND
DI3
GND
DO1
DI1
G B − W +
TX/+
RX/−
B+
V−
V+
V−
AI4
SP4
SP3
AI3
AI2
DI4
DO2
DI2
DI1
DO1
DI3
AI1
AIx or Ax. Analog IN x
DIx. Discrete IN x
DOx. Discrete OUT x
GND. Ground/dc common
connection
SPx. Switch Power; provides variable
power sources for external devices
B+. 3.6 to 5.5 V dc (use for
battery
powered models only)
PWR. 10 to 30 V dc power
connection
RX/-. Serial
communication
line for the
Gateway. No
connection
for Nodes
TX/+. Serial
communication
line for the
Gateway; no
connection
for Nodes
V+. 10 to 30 V dc power
connection
V–. Ground/dc common
connection
Connecting
power to the
communication
pins will cause permanent damage. For the DX8x...C models, PWR in the wiring diagram refers
to V+ on the wiring board and GND in the wiring diagram refers to V- on the wiring board. To power the sensor using the switch power
output (SPx), replace the PWR with SPx in these wiring diagrams. Refer to the Class I Division 2/Zone 2 control drawings (p/n
)
for wiring
specifications
or
limitations.
Discrete Input Wiring for PNP Sensors
Discrete Input Wiring for NPN Sensors
Discrete Output Wiring (NPN or NMOS)
Discrete IN
PWR
10-30V dc
Discrete IN
GND
dc common
Load
Discrete OUT
GND
PWR
10–30 V dc
dc common
Do not exceed analog input
ratings
for analog inputs. Only connect sensor outputs to analog inputs.
Sure Cross
®
MultiHop
Data Radio
4
www.bannerengineering.com - Tel: +1-763-544-3164