background image

Configuration

 

Instructions

Setting

 Up Your 

MultiHop

 Network

To set up and install your wireless 

MultiHop

 network, follow these steps:

1. If your radios have DIP switches, 

configure

 the DIP switches of all devices.

2. Connect the sensors to the 

MultiHop

 radios if applicable.

3. Apply power to all devices.
4. If your 

MultiHop

 radio has rotary dials, set the 

MultiHop

 Radio (Slave) ID. If your 

MultiHop

 radio has no rotary dials, 

continue

 to

the next step.

5. Form the wireless network by binding the slave and repeater radios to the master radio. If the binding 

instructions

 are not

included in this datasheet, refer to the quick start guide or product manual.

6. Observe the LED behavior to verify the devices are 

communicating

 with each other.

7.

Configure

 any I/O points to use the sensors connected to the Sure Cross devices.

8. Conduct a site survey between the 

MultiHop

 radios. If the site survey 

instructions

 are not included in this datasheet, refer to

the product manual.

9. Install your wireless sensor network components. If the 

installation

 

instructions

 are not included in this datasheet, refer to the

product manual.

For 

additional

 

information,

 including 

installation

 and setup, 

weatherproofing,

 device menu maps, 

troubleshooting,

 and a list of

accessories, refer to one of the following product manuals:

MultiHop

 Data Radio Quick Start Guide: 

152653

MultiHop

 Data Radio 

Instruction

 Manual: 

151317

MultiHop

 Register Guide (End User 

Edition):

 

155289

Configure

 the DIP Switches

Before changing DIP switch 

positions,

 disconnect the power. DIP switch changes are not recognized 

until

 

after

 power is cycled to the

device.

Accessing the Internal DIP Switches

To access the internal DIP switches, follow these steps:

1. Unscrew the four screws that mount the cover to the 

bottom

 housing.

2. Remove the cover from the housing without damaging the ribbon cable or the pins the cable plugs into.
3. Gently unplug the ribbon cable from the board mounted into the 

bottom

 housing.

4. Remove the black cover plate from the 

bottom

 of the device's cover.

The DIP switches are located behind the rotary dials.

After

 making the necessary changes to the DIP switches, place the black cover plate back into 

position

 and

gently push into place. Plug the ribbon cable in 

after

 verifying that the blocked hole lines up with the

missing pin. Mount the cover back onto the housing.

DIP Switch 

Settings

 

(MultiHop)

Switches

Device 

Settings

1

2

3

4

5

6

7

8

Serial line baud rate 19200 OR User 

defined

 receiver slots

OFF ¹

OFF ¹

Serial line baud rate 38400 OR 32 receiver slots

OFF

ON

Serial line baud rate 9600 OR 128 receiver slots

ON

OFF

Serial line baud rate Custom OR 4 receiver slots

ON ²

ON ²

Parity: None

OFF ¹

OFF ¹

Parity: Even

OFF

ON

Parity: Odd

ON

OFF

Disable serial (low power mode) and enable the receiver slots

select for switches 1-2

ON ²

ON ²

 

 

Sure Cross

®

 

MultiHop

 Data Radio

2

www.bannerengineering.com - Tel: +1-763-544-3164

P/N 152416 Rev. H

Summary of Contents for Sure Cross MultiHop DX80DR9M-H5

Page 1: ...ensing device for personnel protection Doing so could lead to serious injury or death This device does not include the self checking redundant circuitry necessary to allow its use in personnel safety...

Page 2: ...ltiHop Data Radio Instruction Manual 151317 MultiHop Register Guide End User Edition 155289 Configure the DIP Switches Before changing DIP switch positions disconnect the power DIP switch changes are...

Page 3: ...ets to provide better throughput In transparent mode there is no access to the radio s I O Baud Rate and Parity The baud rate bits per second is the data transmission rate between the device and whate...

Page 4: ...D DI4 GND DO2 DI2 SP3 AI3 AI1 GND DI3 GND DO1 DI1 G B W TX RX B V V V AI4 SP4 SP3 AI3 AI2 DI4 DO2 DI2 DI1 DO1 DI3 AI1 AIx or Ax Analog IN x DIx Discrete IN x DOx Discrete OUT x GND Ground dc common co...

Page 5: ...using an Ethernet connection to an Ethernet radio master Serial DXM using a USB cable to a DXM Controller to access a MultiHop master radio TCP DXM using an Ethernet connection to a DXM Controller to...

Page 6: ...ed together based on the I O type number analog 1 analog 2 counter 1 etc Not all inputs or outputs may be available for all models To determine which specific I O is available on your model refer to t...

Page 7: ...This device complies with FCC Part 15 Subpart C 15 247 ETSI EN 300 328 V1 8 1 2012 04 IC 7044A DX8024 Communication Hardware MultiHop RS 485 Interface 2 wire half duplex RS 485 Baud rates 9 6k 19 2k d...

Page 8: ...g other antennas verify you are not exceeding the transmit power levels allowed by local governing agencies Consult with Banner Engineering Corp if the destination country is not on this list Banner E...

Reviews: