4. Select a COMM port from the drop-down list and click Connect.
5. Click on the Register View tab on the left part of the page.
6. Change the Source Register selection to I/O Board Registers.
7. In the Write Registers area, write Modbus register 4908 to 1 to enable counting on the rising edge of the input signal.
8. Read Modbus registers 4910 and 4911 to get the 32-bit value of the count.
Example: Change Universal Input 2 to a 0 to 10 V dc Input
1. Connect the DXM Controller to the PC.
2. Launch the DXM Configuration Tool software.
3. Connect to the DXM Controller by selecting the Device > Connection Settings menu option. You may connect using
either USB or Ethernet.
4. Select a COMM port from the drop-down list and click Connect.
5. Click on the Register View tab on the left part of the page.
6. Change the Source Register selection to I/O Board Registers.
7. Write a 3 to Modbus register 3326 on Modbus Slave ID 200 (I/O board).
8. Cycle power to the device.
9. Using the Register View tab, read register 3326 to verify it is set to 3.
Example: Change Analog Output 1 to a 0 to 10 V dc Output
1. Connect the DXM Controller to the PC.
2. Launch the DXM Configuration Tool software.
3. Connect to the DXM Controller by selecting the Device > Connection Settings menu option. You may connect using
either USB or Ethernet.
4. Select a COMM port from the drop-down list and click Connect.
5. Click on the Register View tab on the left part of the page.
6. Change the Source Register selection to I/O Board Registers.
7. Set jumper 1 on the I/O base board to the 0 to 10 V position. Refer to the base board image for the analog output
jumper position.
8. Write a 3 to Modbus register 4008 on Modbus Slave ID 200 (I/O board).
9. Cycle power to the device.
10. Using the Register View tab, read register 4008 to verify it is set to 3.
6.6.2 NMOS Outputs
Pin
NMOS Discrete
Outputs
Modbus Register
Description
Wiring
22
4
504
Less than 1 A maximum current at 30 V dc
ON-State Saturation: Less than 0.7 V at 20 mA
ON Condition: Less than 0.7 V
OFF Condition: Open
Output
23
3
503
24
2
502
35
1
501
6.6.3 Analog (DAC) Outputs
The DXM100-B2 and S2 analog outputs are 0 to 10 V dc outputs and cannot be changed.
DXM100-B2 and S2 Models
Pin
Analog
Output
Modbus
Register
Description
20
1
509
0 to 10 V dc output
Accuracy: 0.1% of full scale +0.01% per °C
Resolution: 12-bit
19
2
510
Parameters for Analog Output 1 start at 4001 through 4008. Parameters for Analog Output 2 start at 4021 through 4028.